USSC Ashley EC95 Скачать руководство пользователя страница 5

EC95

5

There are five allowable ways that a chimney connector can be connected to a masonry chimney by passing
through a combustible wall.  NFPA Standard 211 allows the following wall pass-through systems.

Use a minimum 3-1/2" thick brick masonry wall framed into the combustible wall.  A fireclay liner (ASTM C315 or
equivalent) having a 5/8" minimum wall thickness must be used and it must be at least 12" away from any material that
could catch fire.  The inside diameter of the fireclay liner shall be sized for the proper snug fit of a 6" diameter chimney
con nector pipe. The fireclay liner shall run from the outer surface of the brick wall to, but not beyond, the inner surface
of the chimney flue and shall be firmly cemented in place. See Part A of Figure 7.
Use a solid insulated listed factory-built chimney length having an inside diameter of 6" and having 1" or more of solid
insulation.  There must be at least a 9" air space between the outer wall of the chimney length and any combustible
materials.  The inner end of the chimney length shall be flush with the inside of the masonry chimney flue shall be
sealed to the flue and to the brick masonry penetration with nonwater-soluble refractory cement.  Sheet steel supports
which are at least 24 gauge(0.024") in thickness shall be securely fastened to wall surfaces on all sides.  Fasteners
between supports and the chimney length shall not penetrate the chimney liner. See Part B of Figure 7.
Use a 10" diameter ventilated thimble made of at least 24 gauge(0.024") steel having two 1" air channels.  The
ventilated thimble must be separated from combustible materials by a minimum of 6" glass fiber insulation.  The
opening in the combustible wall shall be covered and the thimble supported with sheet steel supports which are at
least 24 gauge (0.024") in thickness.  The sheet steel supports shall be securely fastened to wall surfaces on all sides
and shall be sized to fit and hold the chimney section.  Fasteners used to secure chimney sections shall not penetrate
chimney flue liner.  See Part C of Figure 7.
Use an 8" inside diameter solid insulated listed factory-built chimney length which has 1" or more of solid insulation.
The minimum length of this chimney section shall be 12" and will serve as a pass-through for the 6" diameter chimney
connector.  There must be at least a 12" air space between the outer wall of the chimney section and any combustible
materials.  The chimney section shall be concentric with and spaced 1" away from the chimney connector by means of
sheet steel support plates on both ends of the chimney section.  The opening in the combustible wall shall be covered
and the chimney section supported on both sides with sheet steel supports which are at least 24 gauge (0.024") in
thickness.  The sheet steel supports shall be securely fastened to wall surfaces on all sides and shall be sized to fit and
hold the chimney section.  Fasteners used to secure chimney sections shall not penetrate chimney flue liner.  See Part
C of Figure 7.
A listed factory-built wall pass-through system may be purchased and installed according to the instructions packaged
with it to provide a safe method of passing the chimney connector through a combustible wall for connection to a
masonry chimney.

Additional requirements pertaining to Figure 5 and the above wall pass-through systems:

1.

2.

3.

4.

5.

Insulation material used as part of wall pass-through system shall be of noncombustible material and shall have a
thermal conductivity of 1.0 Btu • in./ft.² • °F (4.88 kg • cal/hr • m² • °C) or less
All clearances and thicknesses are minimums:  larger clearances and thickness are acceptable.
A chimney thimble, as shown for 3" and 4" above (Parts C and D respectively of Figure 7) shall be for types "3" and "4"
connections to facilitate removal of the chimney connector for cleaning.  The chimney thimble shall be of  ASTM C315
fireclay with 5/8" minimum wall thickness , or material or equivalent durability.  The inside diameter of the thimble shall
be sized for the proper snug fit of a 6" diameter chimney connector pipe.  The thimble shall be installed without damage
to the chimney flue.  The thimble shall extend through the chimney wall to, but not beyond, the inner surface of the
chimney flue and shall be permanently cemented in place with high temperature cement.
A chimney connector to a masonry chimney, except for 2" above (Part B of Figure 7), shall extend through the wall
pass-through system to the inner face of the chimney flue, but not beyond.  It does not have to be fastened in place so
long as it cannot accidently be pulled out of the chimney or shoved into the chimney flue.  If fasteners are used to
secure the chimney connector to a masonry chimney, the fasteners shall not penetrate the chimney flue liner.
Any material used to close up any opening for the connector shall be noncombustible.

1.

2.
3.

4.

5.

If the chimney connector does not have to pass through a combustible wall to get to a masonry chimney, connect the
chimney connector to the masonry chimney as shown in figure 8.  The fireclay liner shown by figure 8 should be sized for
the proper snug fit of a 6” diameter chimney connector pipe.  The fireclay liner should be firmly cemented in place as
shown.  As previously stated, any metal prefabricated chimney this heater is connected to must be a listed Hi-Temp Type
HT Factory Built Residential Type and Building Heating Appliance Chimney.
When a metal prefabricated chimney is used, the manufacturer’s installation instructions must be followed precisely.  You must
also purchase (from the same manufacturer) and install the ceiling support package or wall pass through and “T” section
package, firestops (when needed), insulation shield, roof flashing, chimney cap, etc.  Maintain the proper clearance to the
structure as recommended by the manufacturer.  This clearance is usually a minimum of 2 inches, although it may vary by
manufacturer or for certain components.
A listed chimney cap should be installed to prevent entrance of rain and help eliminate down drafts.  An unapproved
chimney cap, protector or spark arrester can become clogged when leaves or other matter.  This blocks the chimney and
causes smoke, and the dangerous carbon monoxide in smoke, to spill back into your home where it can kill you.

Содержание Ashley EC95

Страница 1: ...SULT FOR YOUR SAFETY FOLLOW THE INSTALLATION INSTRUCTIONS CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRIC TIONS AND INSTALLATION INSPECTION REQUIREMENTS IN YOUR AREA To assure that satisfactory and safe service is received from this heater 1 Read these instructions entirely before beginning any part of the installation 2 Use these instructions as a guide during the installation of the heate...

Страница 2: ...e chance of drafts blowing smoke ashes or sparks out of the heater during refueling or ash removal 7 The heater should be located where a small supply of wood may be kept conveniently close but not within 36 inches of the heater 8 Locate the heater so that drapes curtains furniture and other combustible materials will not be closer than the clearances shown by figures 1 2 3 and 4 OR install a clea...

Страница 3: ...EC95 3 FIGURE 3 MINIMUM CLEARANCES TO COMBUSTIBLES FIGURE 4 MINIMUM CLEARANCES TO COMBUSTIBLES SIDE SECTION VIEW PLAN SECTION VIEW ...

Страница 4: ...obtained from N F P A Inc Batterymarch Park Quincy MA 02269 The Chimney connector pipe from heater to chimney must be 6 inches in diameter and made from 24 gauge or heavier steel The length of the chimney connector and number of elbows used should be kept to a minimum Moisture that might collect in the chimney should be directed to the heater by providing a slope of 1 4 inch per foot in a horizont...

Страница 5: ...built wall pass through system may be purchased and installed according to the instructions packaged with it to provide a safe method of passing the chimney connector through a combustible wall for connection to a masonry chimney Additional requirements pertaining to Figure 5 and the above wall pass through systems 1 2 3 4 5 Insulation material used as part of wall pass through system shall be of ...

Страница 6: ...BRICK ALL AROUND CHIMNEY CONNECTOR TO HEATER FIRE CLAY LINER 5 8 MIN WALL THICKNESS MIN 3 1 2 THICK BRICK MASONRY WALL MASONRY CHIMNEY CONSTRUCTED TO NFPA 211 MINIMUM 12 IN TO COMBUSTIBLES PART A FIGURE 7 FIGURE 7 CONTINUED ON NEXT PAGE There are basically two methods of metal prefabricated chimney installation One method is to install the chimney inside the residence through the ceiling and the r...

Страница 7: ...NRY CHIMNEY CONSTRUCTED TO NFPA 211 SHEET STEEL SUPPORTS 24 GAUGE MIN THICKNESS CHIMNEY CONNECTOR TO HEATER MINIMUM CHIMNEY CLEARANCES FROM MASONRY TO SHEET STEEL SUPPORTS AND COMBUSTIBLES 2 IN MINIMUM 6 IN GLASS FIBER INSULATION ALL AROUND 24 GAUGE VENTILATED THIMBLE WITH TWO 1 INCH AIR CHANNELS CHIMNEY THIMBLE CHIMNEY FLUE PART E Figure 5 In addition to the methods shown by A B C and D of Figure...

Страница 8: ...WO APPLIANCES OR HEATERS ARE CONNECTED TO THE SAME FLUE CAUTION THE HEATER MUST BE PLACED ON A LISTED FLOOR PROTECTOR AS NOTED IN THIS MANUAL IF THE FLOOR IS WOOD OR OTHER COMBUSTIBLE FLOORING IF CARPET IS PRESENT IT MUST BE REMOVED THE FLOOR PROTECTOR MUST NOT BE PLACED ON CARPET SEE FIGURE 5 CAUTION MOST WALLS AND CEILINGS CONTAIN WOOD EVEN THOUGH THEY ARE MADE OF SHEETROCK OR PLASTER ON THE OUT...

Страница 9: ... obtain the fireplace items called for by figure 4 3 If the heater is to be installed on a combustible floor purchase a listed noncombustible floor protector as described in this manual and install it in the proper location The floor protector MUST protect the floor beneath and around the heater and chimney connector as shown by figure 5 4 Assemble the chimney connector pipe sections to determine ...

Страница 10: ...BUILD A FIRE 1 Set the heater s thermostat control knob to the Hi position See figure 9 2 Open the feed door see figure 10 and lay paper and kindling on the rate in sufficient quantities to ensure good ignition WARNING NEVER USE GASOLINE GASOLINE TYPE LANTERN FUEL KEROSENE CHARCOAL LIGHTER FLUID OR SIMILAR LIQUIDS TO START OR FRESHEN UP A FIRE IN THIS HEATER KEEP ALL SUCH LIQUIDS WELL AWAY FROM TH...

Страница 11: ...e driven off and shortens the length of time the dense smoke is likely to deposit creosote on the chimney walls 5 DO NOT TAMPER WITH THE INTERNAL THERMOSTAT MECHANISM The thermostat has been designed and calibrated to provide continuous control of the fire for safety and efficiency Thermostat adjustments are made with the thermostat control knob only See figure 9 6 PREPARE THE HEATER TO HOLD FIRE ...

Страница 12: ...for several days when embedded in ashes VENTING SYSTEM CHIMNEY CONNECTOR AND CHIMNEY The venting system consists of the heater s chimney connector the pipe which connects the heater to the chimney and the chimney itself When wood is burned slowly it produces tar and other organic vapors which combine the expelled moisture to form creosote The creosote vapors condense in the relatively cool chimney...

Страница 13: ...hat has grown tall can affect the draft of a chimney that was previously trouble free and other factors The common unit used to measure draft is INCHES IF WATER To determine the draft of your chimney a draft pressure reading should be taken with a DRAFT METER or a WATER MANOMETER This requires someone with proper equipment and knowledge of how to use it Your heater dealer should be able to preform...

Страница 14: ...rns as cleanly as possible Thus you should adjust the amount of wood you put in the heater to the outdoor temperature Placing excessive wood in the heater will cause excessive creosote formation in the chimney waste wood and make the room uncomfortably warm 2 If the heater burns too rapidly or overheats it may be because air is leaking around a loose door gasket or a fuel feed door or ash door lat...

Страница 15: ...composition fire starters specifically designed for starting a fire The use of liquid fire starters can cause an explosion within the heater 14 Do use only a Listed High Temperature Type HT Factory built Residential Type and Building Heating Appliance Chimney or a properly constructed and maintained masonry chimney to vent this heater 15 Do use 6 inch diameter chimney connector pipes made from a m...

Страница 16: ...nt 11 Don t install this heater in a chimney flue that is used by another appliance 12 Don t neglect to clean and inspect your chimney regularly 13 Don t operate this heater with the doors open 14 Don t use the heater with missing or damaged parts SAFETY NOTICE In the unlikely event that your heater overfires a condition evidence by elbows stovepipes and connectors glowing red in appearance or oth...

Страница 17: ...EC95 17 FIGURE 12 ILLUSTRATION OF REPAIR PARTS SEE LEDGER ON NEXT PAGE FOR PART NAMES AND PART NUMBERS 47 58 ...

Страница 18: ...et for Ash Door 1 88057 18 Feed Door Assy 1 69229 19 Latch 1 25048 20 Liner Front 1 40412 22 Shield Door Ptd 1 24870 23 Pan Ash Welded 1 69206 24 Grate 2 40394 25 Angle Grate Support Assy 2 69205 26 Leveler 4 83479 27 Gasket Manifold 1 88090 28 Manifold Assy Ptd 1 24812 29 Plate Draft Assy Ptd 1 69207B 30 Clip Spring 1 83818 31 Draft Pin 1 17200 32 S Hook 2 83482 33 Chain 2 5 Ft 86318 34 Thermosta...

Страница 19: ... for Mechanical Engineers by Baumeister and Marks 6 K C and R factors are explained as follows A The K factor represents the thermal conductivity of a material and is the time rate of heat flow through a homogeneous material under steady state conditions through unit area per unit temperature gradient in the direction perpendicular to a surface BTU or Btu in _______________ _______________________...

Страница 20: ...20 EC95 ...

Отзывы: