22
USSC
CONTROL BOARD FUNCTIONS
START-UP SEQUENCE OF EVENTS
Once the control panel is turned on, a timer begins that will start, stop and continue operation of the Multi-fuel
Heater as a preset temperature is achieved.
COMPONENT
OPERATION START
OPERATION END
Draft Fan
Starts Immediately
Will continue until shutdown. Shutdown will occur
when the operating temperature is below approx. 90
degrees.
Agitator
Begins to turn once the heater reaches op
-
erating temperature
Will continue intermediately, as determined by the
“HEAT SETTING”, until shutdown.
Auger
In Pellet mode: Auger turns immediately.
In Corn mode: Three minutes after starting,
the auger will begin to turn
The auger will continue at the feed rate specified by
the “HEAT SETTING”.
NOTE: Safety switches, HI limit and vacuum sensor,
must be activated to continue proper operation.
Room Fan
Begins to run when heater reaches operat
-
ing temperature
Will continue to operate until the heater cools down to
below approx. 90 degrees. This may take several hours.
Automatic Shutdown
If after 15 minutes, the heater has not
reached the preset operating temperature,
the unit will begin to automatically shut
down.
Should the timer expire before the preset operating
temperature is achieved, simply reset the heater by
pressing the “ON” button.
Normal Operation
If after 15 minutes the preset operating tem
-
perature of approx. 110 degrees is achieved,
normal operation will continue.
Operation will continue until either the heater’s control
is to the “OFF” position, or the operating temperature
falls below approx. 90 degrees. At such time the heater
will default to the “Automatic Shut Down”.
Igniter
Starts immediately
Will continue operation for a preset time, then shut-off
SHUTDOWN SEQUENCE OF EVENTS
Once the Heater has reached the normal operating temperature and switched to the “OFF” position, the unit will
initiate a slow down, reducing the fuel rate until the heater’s “LOW LIMIT SAFETY” sensor tells the control board it
is safe to shutdown.
COMPONENT
SHUTDOWN
OPERATION END
Draft Fan
Unchanged operation until preset “OFF”
temperature is achieved.
Continues until the operating temperature falls below
approx. 90 degrees. May take several
hours.
Agitator
Rotates continuously until preset “OFF” tem
-
perature is achieved.
Continues until the operating temperature falls below
approx. 90 degrees.
Auger
Slows down to a
reduced fuel setting until
preset “OFF” temperature is achieved.
The auger will continue at the reduced feed rates
until the operating temperature falls below approx.
90 degrees.
NOTE: Safety switches, HI limit and vacuum sensor,
must be activated to continue proper operation.
Room Fan
Unchanged operation until preset “OFF”
temperature is achieved.
Will continue to operate until the heater cools down to
below approx. 90 degrees. This may take several hours.
Automatic Shutdown
If the heater’s “HI LIMIT” sensor snaps open,
this will cause an automatic shutdown. An
error code will be displayed (Err1)
.
NOTE:
“HI LIMIT” errors are usually the result of
operating at the highest heat setting for long
periods of time, room fan failure or loose
wire connection.
It is rare that the HI LIMIT temperature is reached.
However, should this error occur, let the heater cool
down for an hour then restart.
CAUTION:
When performing any internal electrical maintenance
• Moving parts inside of the cabinet may cause injury. Do not operate unit with panels removed or open.
•
HOT
parts. Do not operate the unit with panel open.
• Risk of electric shock. Disconnect power before servicing unit.
• In the event of component failure, replace with the original factory equipment.
Содержание American Harvest 6041
Страница 5: ...USSC 5 COMPONENT LOCATION ...
Страница 9: ...USSC 9 CLEARANCES TO COMBUSTIBLES 6041I ...
Страница 25: ...USSC 25 WIRING DIAGRAM WIRING SCHEMATIC ...
Страница 28: ...28 USSC PARTS DIAGRAM 6041I 21 22 19 20 23 24 25 26 17 16 7 6 3 4 6 5 11 10 2 9 8 10 14 13 15 12 18 22 1 27 28 ...
Страница 31: ...USSC 31 NOTE ...