DS138-003A
operATion
In case of overcurrent, device thermal protection interrupts power supply to connected devices.
The thermal protection will interrupt only one conductor, the other one will be kept connected to the
respective input terminal pin.
To activate again the device, press the restore button; in case of short-circuit or overload, restart will not
be possible.
Turned on led indicates the presence of power supply voltage and active protection.
Turned off led indicates a protection intervention and this must be replaced (the load is kept powered, but
without protection).
Indicator led
Restore button
The led stays off also in case of mains failure.
TeCHniCAL FeATureS
Nominal operating voltage: ...................................................................................................
230Vac 50-60Hz
Max. continuous operating voltage (Uc): .............................................................................................
255Vac
350Vdc
EMI filter attenuation: ......................................................................................................
>40dB (0,5÷30MHz
)
>50dB (2÷20MHz)
Grounding system: .......................................................................................................................................
TT
Operating temperature range: ..........................................................................................................
-5÷+40°C
Relative humidity: ................................................................................................................................
10÷80%
Overcurrent protection: .......................................................................................................................
thermal
Nominal operating current: ........................................................................................................................
1,8A
Overcurrent protection: ..................................................................................................................
4A (0,2÷4s
)
Number of intervention cycles:...................................................................................................................
500
Max. short-circuit current: ..........................................................................................................................
18A
Compliant with: ....................................................................................................................
en61643-11/A11
Class test: .......................................................................................................................................................
3
Number of ports: ............................................................................................................................................
2
Discharge nominal voltage L-N (8/20) (Uoc): ............................................................................................
6kV
Discharge nominal voltage L-N/PE (8/20) (Uoc): ........................................................................................
6kV
Protection level L-N (Up): ....................................................................................................................
<1500V
Protection level L-N/PE (Up): ...............................................................................................................
<1500V
TOV voltage (Ut): .....................................................................................
392Vac (L-pe) / 333Vac (L-n) @ 5s
1430Vac (L-pe) / 1200Vac (n-pe) @ 200 ms
§
§