7 Troubleshooting
In the event of an UPS fault, shoot the trouble according to Table 7-1 or Table
7-2. If the fault still persists, please contact our customer service center.
Problem
Possible cause
Solution
LED display
Alarm
The 1# Fault
LED and 6#
LED are on
Beep
continuously
Internal
overheat
Ensure that the UPS is not
overloaded and the ventilation
opening is not blocked and ambient
temperature is not too high. Wait
for 10 minutes for the UPS to cool
down before turning it on again. If
it does not work. Please contact the
distributor or service center.
The1#
Fault
LED and 5#
LED are on
Beep
continuously
Internal fault.
Please contact the distributor or
Service center
The 1# Fault
LED and 4#
LED are on
Beep
continuously
Internal fault
Please contact the distributor or
Service center
The 1# Fault
LED and 3#
LED are on
Beep
continuously
Over-charging
Protection
The charger of the UPS is
defective.
Please
contact
the
distributor or Service center
The 1# Fault
LED and 2#
LED are on
Beep
continuously
The
UPS
overloaded or
the load device
Check the load and remove the
non-Critical device. Recalculate the
load power and reduce the member
of loads connected to the UPS.
Check whether the load device is
fault
The 1# Fault
LED and 2#
LED and 6#
are on
Beep once
every second
Fan of UPS is
not connected
or fault
Please contact the distributor or
Service center
The 1# Fault
LED and 2#
LED and 5#
are on
Beep
continuously
The
UPS
output is short
circuited
Turn off the UPS. Remove all
loads. Ensure that the loads are not
failed or the UPS has no internal
short before turn on it again. If
failed, please contact the distributor
or service center