FUNCTION
DESCRIPTION
DEFAULT
External synchronization
Synchronization source of inverter output
From bypass line
External temperature
Activation of the external temperature probe
Disable
Bypass mode
Mode of use of the bypass line
Enabled /
High sensibility
Bypass active in stand-by
Load powering from bypass with UPS in stand-by
Disabled (load NOT
powered)
Bypass frequency tolerance
Range permitted for the input frequency for switching to the
bypass and for output synchronization
±5%
Bypass min.-max. threshold
Permitted voltage range for switching to the bypass
Low: 180V
High: 264V
Eco mode sensibility
Intervention sensitivity during ECO mode operation
Normal
Eco mode
min.-max. threshold
Permitted voltage range for ECO mode operation
Low: 200V
High: 253V
UPS without battery
Operating mode without batteries (for frequency
converters/stabilisers)
Operation with
batteries
Battery low time
Estimated autonomy time remaining for the battery low
warning
3min.
Automatic battery test
Interval of time for the automatic battery test
40 hours
Parallel common battery
Parallel system with single battery (common between all
system UPS)
Disable
Internal battery capacity
Nominal internal battery capacity
Variable depending
on UPS model and
size
External battery capacity
Nominal external battery capacity
7Ah for UPS without
internal batteries, 0Ah
in all other cases
Battery charging algorithm
Battery algorithm and charging threshold
Two levels
Battery recharging current
Percentage of charging current compared to nominal battery
capacity
12%
www.upsdirect.com