2

You can enter the programming mode with 2 seconds push on the button.

The programming menu structure is described on the follow page. Mind

that once you have entered the programming menu you can exit it at the

last item only. All programming settings are stored in a non-volatile

memory and remain stored even if the controller was disconnected from

the battery.

Programming your Solar Controller

The button switch has three push modes:

1

Short push

Shorter than 1 seconds

2

Long push

2 to 8 seconds

3

Lock push

8 seconds or longer

By pushing the button for 8 sec in normal operation mode the

programming lock-out is activated to prevent any accidental settings

change. Another 8 sec push releases the lock-out.
With a long push, you can enter the programming mode. The

programming menu structure is described in the back page. A wide arrow

means a long push (2s-8s), a narrow dotted line arrow means a short push

(<1sec).

Testing Function

During the daytime the testing function of SLAC-SL can help the user to

verify correct installation or for troubleshooting a system problem. Short

pushing the button will light up the lamp which is connected to the load

terminals. The lights will be on in the day for 3 minutes intervals. Within

3 minutes the lights can be turned off via pushing button. The lights can

turned on repeatedly with pushing button besides when the system is in

LVD (load disconnect/red LED on). In LVD this testing function is not

valid. If pressing the button cause a load disconnects (LVD) the light will

turn off.

Safety Features

PV terminals

Battery terminals

Load

terminals

Reverse

polarity

24V system: no

12V system: yes

Protected

Protected

Short circuit

Protected

Protected (with fuse

on battery) (3)

Protected

Over current

Protected

Protected

Switches off

with

a delay (3)

Reverse

charge

Protected

No effect

No effect

Over voltage

Max. 55V

Max. 55V

Switches off

with a

delay

Under voltage

No effect

No effect

Switches off

above

15.5/31.0 V

Over

temperature

When over temperature occurs, the controller will

reduce the charging current. If the temperature of

controller reaches a high level, the load will

automatically be switched off.

(1) Controller can protect itself, but load might be damaged.

(2) We strongly recommend that add a fuse between battery and controller.

The battery may be permanent damaged when short circuit occurs.

(3) > 200% rated current: Load will be switched off with 3s delay.

Warning: Two or more error conditions at the same time may cause

damage to the controller. Always remove the present fault condition

before next operation

SLAC-SL Technical Characteristics

Model

SLAC-SL

5A

10A

20A

Max. charge/load current

5A

10A

20A

Rated System voltage

12V/24V auto recognition

Main charge

14.4V/28.8 V (25 °C), 30 min. (daily)

Boost charge

14.4/28.8 V (25 °C), 2 h Activation:

battery voltage < 12.3/24.6 V

Equalization voltage

14.8/29.6V(25 °C)

Float charge

13.8/27.6 V (25 °C)

Deep discharge protection,

Cut-off voltage

11 – 12 V/22 – 24 V

Reconnect level

12.8/25.6V

Under voltage protection

10.8/21.6V

Overvoltage protection

15.5/31.0 V

Self consumption

4mA-5mA

12V

6mA-8mA

24V

Max. panel voltage

50V

Temperature compensation

-4mV/Cell*K

Grounding

Positive grounding

Battery type

Lead acid (GEL, AGM, flooded)

Evening hours

0 – 12 h

Ambient temperature

-40°C-+60°C

Dimensions

50mm*56.6mm*20mm

Wire Length/size

150mm/2.5m²

Ambient temperature

-40°C-+60°C

IP grade

IP67

Max. altitude

4000m

Weight

130g

Subject to change without notice.