Electro-Pneumatic Positioners
unstable, the regulator must be replaced.
▶
Hysteresis is too low.
(1) In case of double acting actuator, check if seat adjustment has been properly
performed. Please contact YTC for any further inquiries regarding the seat
adjustment.
(2) Backlash can occur when the feedback lever and lever spring are loosen. To avoid
backlashing, please adjust the lever spring.
(3) Check if the connection bar to the feedback lever is tightly fastened.
- 18 -