Mobile Home Installation:

For minimum protection, smoke alarms  should be installed in compliance with H .U .D . Manu-
factured Home Construction Safety Standards, Title 24 CFR, Section 3280.208 and Section 
3282 . For additional protection, see Single Story Residence smoke alarm requirements/rec-
ommendations for Existing Homes and New Construction Homes .
Note: For mobile homes built before 1978, install smoke alarms or combination alarms on in-
side walls between 4” and 12” from the ceiling (older mobile homes have little or no insulation 
in the ceiling). This is especially important if the ceiling is unusually hot or cold.
Install smoke alarms or combination alarms inside each bedroom and in the hallway outside 
each separate sleeping area .

RECOMMENDED PLACEMENT:

NOTE:

 For any location, make sure no door or other obstruction could prevent the smoke or 

carbon monoxide from reaching the alarm .

WHERE THIS ALARM SHOULD NOT BE INSTALLED

Installation in an improper location can affect the sensitive electronic components in this alarm . 

This alarm is not suitable for installation in hazardous locations as defined in the National Electri-

cal Code . 

To avoid causing damage to this alarm, to provide maximum protection, and to prevent 
unnecessary alarms, DO NOT LOCATE THIS ALARM:

•  In extremely humid areas. This alarm should be at least 10 feet (3m) from a bath or show-

er, sauna, humidifier, vaporizer, dishwasher, laundry room, utility room or other source of 

high humidity .

•  In very cold or very hot environments or in unheated buildings or outdoor rooms where the 

temperature can go below or above the operating range of the alarm .

•  In garages, kitchens crawl spaces and unfinished attics. 
•  In turbulent air, such as near ceiling fans, heat vents, air conditioners, fresh air returns or 

open windows . Blowing air may prevent smoke or CO gas from reaching the sensors . 

•  In extremely dusty, dirty or greasy areas . Installation in these areas could lead to nuisance 

alarms, may expose the sensor to substances which could damage or contaminate the 

alarm .

•  In the garage, vehicle exhaust can contain some carbon monoxide . These levels are higher 

when the engine is first started. Within hours of starting a vehicle and backing it out of the 

garage, the levels present over time can activate the alarm and become a nuisance . 

Содержание MIC3510S

Страница 1: ...Potential Sources of CO 11 What To Do If Alarm Sounds Smoke Detected 12 How Can I Protect My Family from Fire 12 Develop An Escape Plan 12 Quick Reference Guide 13 Troubleshooting Information 13 Warra...

Страница 2: ...HOUT POWER Therefore installing an alarm with a sealed battery or an alarm powered from two different power sources can give an extra measure of protection A hardwired alarm with backup battery power...

Страница 3: ...alfunction the service signal will warn it is time to replace the alarm Alarms should always be replaced after 10 years DO NOT PAINT THE ALARM Paint may clog the openings to the sensing chambers and p...

Страница 4: ...wall with the top edge of the smoke alarm up to a maximum of 12 30 5cm below the ceiling wall intersec tions See Diagram A Existing Homes The NFPA requires smoke alarms or combination alarms on every...

Страница 5: ...s not suitable for installation in hazardous locations as defined in the National Electri cal Code To avoid causing damage to this alarm to provide maximum protection and to prevent unnecessary alarms...

Страница 6: ...above situations These placement recommendations are intended to keep alarms at a reasonable distance from a fuel burning source and reduce unwanted nuisance alarms Nuisance alarms may occur if an ala...

Страница 7: ...ntial board and care occupancy small facility including base ments and excluding crawl spaces and unfinished attics 5 In the living area s of a guest suite 6 In the living area s of a residential boar...

Страница 8: ...e the Silence feature until the source of the alarm has been identified and safe conditions exist The Silence feature is intended to temporarily silence the horn while identifying and correcting the p...

Страница 9: ...he alarm ALARM AND BATTERY DEACTIVATION This alarm uses a sealed battery for power The battery should last for approximately 10 years under normal operating conditions Deactivation of the alarm is per...

Страница 10: ...m to stop a nuisance alarm Doing so will disable the alarm and remove the protection In the case of a true unwanted alarm use the silence feature The silence feature is intended to temporarily silence...

Страница 11: ...Vent pipe connections improperly designed or becoming loose Improper use of appliances by operating a barbeque grill using charcoal gas or wood pel lets hibachi in an enclosed area such as a garage o...

Страница 12: ...our home when they hear the sound Identify children s bedrooms with red stickers placed in the upper left corner of the windows They are available from your local fire department Practice a fire drill...

Страница 13: ...oses no threat 4 Beeps 5 second pause repeat Blinks on approx every 2 minutes Blinks On in sync with the 4 beeps Nuisance alarm Smoke alarm when cause of alarm is known and poses no threat Horn sounds...

Страница 14: ...Page 14...

Страница 15: ...not allow the exclusion or limitation of incidental or consequential damages so the above limitations or exclusions may not apply to you No agent representative dealer or employee of the company has t...

Отзывы: