Load Resistor vs. Power Supply
This is the only output from this transmitter, representing the process flow measurement, linearized and scaled according to the
configured range of the instrument. This output corresponds to the Primary Variable. HART Communication is supported on this
loop.
A guaranteed linear over-range is provided. Device malfunction can be indicated by the up-scale current of 24mA. Current
values are shown in the table below.
Direction
Values (percent of
range)
Values (mA or V)
Linear over-range
Down
0%
0.5%
3.92 to 4.08 mA
Up
+106.25%
0.1%
20.84 mA to 21.16 mA
Device malfunction
indication
Down
N/A
N/A
Up
+125.0%
0.1%
23.98 mA to 24.02 mA
Maximum current
+106.25%
1%
20.84 mA to 21.16 mA
Multi-Drop current draw
4.0 mA
Lift-off voltage
10.5 V
A typical 4-20mA wiring diagram is shown below:
LOCAL INTERFACES, JUMPERS AND SWITCHES
This device has no local controls. The HART version of the ME Transmitter is a blind unit fully controlled through HART
commands.