Vision™PLC+HMI Installation Guide  

 

 

Unitronics 

 

Transistor Outputs (pnp) 

 

  The 0V signals of the transistor and the analog outputs 

must be connected to the controller’s 0V. 

  Outputs 1 to 6 can be used as PWM outputs. 

   

   

   

Power Supply 

The controller requires an external 24VDC power supply. 

 

  The power supply must include double insulation. Outputs must be rated as  

SELV/PELV/Class2/Limited Power. 

 

  Use separate wires to connect the functional 

earth line (pin 3) and the 0V line (pin 2) to the 
system earth ground. 

  Install an external circuit breaker. Guard 

against short-circuiting in external wiring. 

  Double-check all wiring before turning  

on the power supply. 

 

Do not connect either the ‘Neutral’ or ‘Line’  

signal of the 110/220VAC to device’s 0V pin 

  In the event of voltage fluctuations or non-

conformity to voltage power supply 
specifications, connect the device to  
a regulated power supply. 

 

     

Earthing the PLC+HMI  

To maximize system performance, avoid electromagnetic interference by: 

  Mounting the controller on a metal panel. 

  Connect each common and ground connection directly to the earth ground of your system. 

  For ground wiring uses the shortest and thickest possible wire. 

   

Communication  

  

V350-35-TU24/V350-J-TU24

 models comprise built-in ports: 1 USB and 1 RS232/RS485 (Port 1). 

 
Note that physically connecting a PC to the controller via USB suspends RS232/RS485 
communications via Port 1. When the PC is disconnected, RS232/RS485 resumes. 

 

Содержание Vision V350-35-TU24

Страница 1: ... Screen 3 5 Color Touch Keypad None Function Keys Yes Com Port Built in RS232 485 Yes USB device mini B Yes Com Ports separate order user installed The user may install a CANbus port V100 17 CAN and one of the following RS232 RS485 port V100 17 RS4 V100 17 RS4X Ethernet V100 17 ET2 Profibus Slave V100 17 PB1 V350 35 TU24 V350 J TU24 comprise both RS232 485 and USB ports note that only one channel ...

Страница 2: ... carry out repairs Failure to comply with appropriate safety guidelines can cause severe injury or property damage Do not attempt to use this device with parameters that exceed permissible levels To avoid damaging the system do not connect disconnect the device when power is on Environmental Considerations Do not install in areas with excessive or conductive dust corrosive or flammable gas moistur...

Страница 3: ...r seal is in place 3 Push the mounting brackets into their slots on the sides of the panel as shown in the figure below 4 Tighten the bracket s screws against the panel Hold the bracket securely against the unit while tightening the screw 5 When properly mounted the controller is squarely situated in the panel cut out as shown in the accompanying figures DIN rail Mounting 1 Snap the controller ont...

Страница 4: ...e from pulling free Input or output cables should not be run through the same multi core cable or share the same wire Allow for voltage drop and noise interference with I O lines used over an extended distance Use wire that is properly sized for the load The controller and I O signals must be connected to the same 0V signal I Os V350 35 TU24 V350 J TU24 models comprise a total 12 inputs 12 digital...

Страница 5: ...0 11 Set Type Set to JP12 all Inputs npn sink A pnp source B Inputs 7 8 Set Type Digital or RTD TC 1 Set to JP1 JP2 JP3 Digital A A A Thermocouple B B B PT100 B A B Inputs 9 10 Set Type Digital or RTD TC 0 Set to JP5 JP6 JP7 Digital A A A Thermocouple B B B PT100 B A B Input 11 Set Type Digital or CM for PT100 Set to JP11 Digital A CM for PT100 B Input 5 Set Type Digital or Analog 3 Set to JP4 JP1...

Страница 6: ...Vision PLC HMI Installation Guide 6 Unitronics I O Wiring npn sink Input Input wiring HSC input wiring pnp source Input Input wiring HSC input wiring Shaft encoder ...

Страница 7: ...Blue J 200 to 760 C 328 to 1400 F White Red Yellow Blue K 200 to 1250 C 328 to 2282 F Yellow Red Brown Blue N 200 to 1300 C 328 to 2372 F Orange Red Orange Blue R 0 to 1768 C 32 to 3214 F Black Red White Blue S 0 to 1768 C 32 to 3214 F Black Red White Blue T 200 to 400 C 328 to 752 F Blue Red White Blue Thermocouple 0 use Input 9 as negative input and 10 as positive Thermocouple 1 use Input 7 as n...

Страница 8: ...g before turning on the power supply Do not connect either the Neutral or Line signal of the 110 220VAC to device s 0V pin In the event of voltage fluctuations or non conformity to voltage power supply specifications connect the device to a regulated power supply Earthing the PLC HMI To maximize system performance avoid electromagnetic interference by Mounting the controller on a metal panel Conne...

Страница 9: ...32 signal 6 DSR signal 6 B signal Standard programming cables do not provide connection points for pins 1 and 6 When a port is adapted to RS485 Pin 1 DTR is used for signal A and Pin 6 DSR signal is used for signal B Note that it is possible to establish a PC to PLC connection using RS232 even when the PLC is set to RS485 this eliminates the need to open the controller to set jumpers To do so remo...

Страница 10: ... the controller 2 Replace the back cover of the controller and fasten the corner screws Note that you must replace the back cover securely before powering up the controller The information in this document reflects products at the date of printing Unitronics reserves the right subject to all applicable laws at any time at its sole discretion and without notice to discontinue or change the features...

Отзывы: