Vision™ OPLC™
Unitronics
7
Analog Input Wiring
Analog input wiring, current (2/3 wire)
Analog input wiring, current/voltage (4-wire)
Shields should be connected at the signal’s source.
The 0V signal of the analog input and output must be connected to the controller’s 0V.
Thermocouple
Thermocouple 0: use Input 9 as
negative input and 10 as positive.
Thermocouple 1: use Input 7 as
negative input and 8 as positive.
RTD
Type Temp. Range
Wire Color
ANSI (USA) BS1843 (UK)
mV -5
to
56mV
B
200 to 1820
P
C
(300 to 3276
P
F)
+Grey
-Red
+None
-Blue
E
-200 to 750
P
C
(-328 to 1382
P
F)
+Violet
-Red
+Brown
-Blue
J
-200 to 760
P
C
(-328 to 1400
P
F)
+White
-Red
+Yellow
-Blue
K
-200 to 1250
P
C
(-328 to 2282
P
F)
+Yellow
-Red
+Brown
-Blue
N
-200 to 1300
P
C
(-328 to 2372
P
F)
+Orange
-Red
+Orange
-Blue
R
0 to 1768
P
C
(32 to 3214
P
F)
+Black
-Red
+White
-Blue
S
0 to 1768
P
C
(32 to 3214
P
F)
+Black
-Red
+White
-Blue
T
-200 to 400
P
C
(-328 to 752
P
F)
+Blue
-Red
+White
-Blue
PT100 (Sensor 0): use Input 9 and 10, related
to CM signal.
PT100 (Sensor 1): use Input 7 and 8, related to
CM signal.
4 wire PT100 can be used by leaving one of
the sensor leads unconnected.