background image

Vision™ OPLC™  

Unitronics  

7

Analog Input Wiring 

Analog input wiring, current (2/3 wire) 

Analog input wiring, current/voltage (4-wire) 

Shields should be connected at the signal’s source. 
The 0V signal of the analog input and output must be connected to the controller’s 0V. 

 

Thermocouple 

Thermocouple 0: use Input 9 as 
negative input and 10 as positive. 
Thermocouple 1: use Input 7 as 
negative input and 8 as positive. 

RTD 

Type Temp. Range 

Wire Color 

 

ANSI (USA) BS1843 (UK)

mV -5 

to 

56mV 

 

 

 

B

200 to 1820

P

C

(300 to 3276

P

F) 

+Grey 
-Red 

+None 
-Blue 

 

E

-200 to 750

P

C

(-328 to 1382

P

F) 

+Violet 
-Red 

+Brown 
-Blue 

 

J

-200 to 760

P

C

(-328 to 1400

P

F) 

+White 
-Red

 

+Yellow 
-Blue 

 

K

-200 to 1250

P

C

(-328 to 2282

P

F) 

+Yellow 
-Red 

+Brown 
-Blue 

 

N

-200 to 1300

P

C

(-328 to 2372

P

F) 

+Orange 
-Red 

+Orange 
-Blue 

 

R

0 to 1768

P

C

(32 to 3214

P

F) 

+Black 
-Red 

+White 
-Blue 

 

S

0 to 1768

P

C

(32 to 3214

P

F) 

+Black 
-Red 

+White 
-Blue 

 

T

-200 to 400

P

C

(-328 to 752

P

F) 

+Blue 
-Red 

+White 
-Blue 

 

PT100 (Sensor 0): use Input 9 and 10, related 
to CM signal. 
PT100 (Sensor 1): use Input 7 and 8, related to 
CM signal. 
4 wire PT100 can be used by leaving one of 
the sensor leads unconnected. 

 

Содержание Vision OPLC V350-35-TA24

Страница 1: ...d analog weight and temperature measurement I Os via On board I O configuration Model dependent I O Expansion Modules Local or remote I Os may be added via expansion port or CANbus Information Mode This mode enables you to View Edit operand values COM port settings RTC and screen contrast brightness settings Calibrate the touchscreen Stop initialize and reset the PLC To enter Information Mode pres...

Страница 2: ...g this product the user must read and understand this document All examples and diagrams are intended to aid understanding and do not guarantee operation Unitronics accepts no responsibility for actual use of this product based on these examples Please dispose of this product according to local and national standards and regulations Only qualified service personnel should open this device or carry...

Страница 3: ...ller into the cut out ensuring that the rubber seal is in place 3 Push the 2 mounting brackets into their slots on the sides of the controller as shown in the figure to the right 4 Tighten the bracket screws against the panel Hold the bracket securely against the unit while tightening the screw 5 When properly mounted the controller is squarely situated in the panel cut out as shown in the figure ...

Страница 4: ...5 kgf cm Do not use tin solder or any substance on stripped wire that might cause the wire strand to break Install at maximum distance from high voltage cables and power equipment Wiring Procedure Use crimp terminals for wiring use 26 12 AWG wire 0 13 mm 2 3 31 mm2 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest position before inserting a wire 3 Ins...

Страница 5: ... PT100 Input and Output Jumper Settings The tables below show how to set a specific jumper to change input functionality To access the I O jumpers you must open the controller according to the instructions beginning on page 10 Incompatible jumper settings and wiring connections may seriously damage the controller Digital Inputs 0 11 Set Type Set to JP12 all Inputs npn sink A pnp source B Inputs 7 ...

Страница 6: ...24 Installation Guide 6 Unitronics I O Wiring I O Configuration npn Input Wiring Input wiring npn sink HSC input wiring npn sink pnp Input Wiring Input wiring pnp source HSC input wiring pnp source Shaft encoder ...

Страница 7: ...Wire Color ANSI USA BS1843 UK mV 5 to 56mV B 200 to 1820PC 300 to 3276PF Grey Red None Blue E 200 to 750PC 328 to 1382PF Violet Red Brown Blue J 200 to 760PC 328 to 1400PF White Red Yellow Blue K 200 to 1250PC 328 to 2282PF Yellow Red Brown Blue N 200 to 1300PC 328 to 2372PF Orange Red Orange Blue R 0 to 1768PC 32 to 3214PF Black Red White Blue S 0 to 1768PC 32 to 3214PF Black Red White Blue T 200...

Страница 8: ...wer supply Do not connect either the Neutral or Line signal of the 110 220VAC to device s 0V pin In the event of voltage fluctuations or non conformity to voltage power supply specifications connect the device to a regulated power supply Earthing the Power Supply To maximize system performance avoid electromagnetic interference by Mounting the controller on a metal panel Earthing the controller s ...

Страница 9: ...ve the RS485 connector and connect the PC to the PLC via the programming cable Note that this is possible only if flow control signals are not used which is the standard case RS232 RS485 Controller Port Pin Description Pin Description 1 DTR signal 1 A signal 2 0V reference 2 RS232 signal 3 TXD signal 3 RS232 signal 4 RXD signal 4 RS232 signal 5 0V reference 5 RS232 signal 6 DSR signal 6 B signal P...

Страница 10: ... must replace the back cover securely before powering up the controller The information in this document reflects products at the date of printing Unitronics reserves the right subject to all applicable laws at any time at its sole discretion and without notice to discontinue or change the features designs materials and other specifications of its products and to either permanently or temporarily ...

Отзывы: