Vision™PLC+HMI
Installation Guide
8
Unitronics
Analog Input
Analog input wiring, current (2/3-wire)
Analog input wiring, current (4-wire), voltage
Shields should be connected at the signal’s source.
The 0V signal of the analog input must be connected to the controller’s 0
V.
Thermocouple
Type Temp. Range
Wire Color
ANSI (USA) BS1843 (UK)
mV
-5 to 56mV
B
200 to 1820
˚
C
(300 to 3276
˚F)
+Grey
-Red
+None
-Blue
E
-200 to 750
˚
C
(-328 to 1382
˚
F)
+Violet
-Red
+Brown
-Blue
J
-200 to 760
˚
C
(-328 to 1400
˚
F)
+White
-Red
+Yellow
-Blue
K
-200 to 1250
˚
C
(-328 to 2282
˚
F)
+Yellow
-Red
+Brown
-Blue
N
-200 to 1300
˚
C
(-328 to 2372
˚
F)
+Orange
-Red
+Orange
-Blue
R
0 to 1768
˚
C
(32 to 3214
˚
F)
+Black
-Red
+White
-Blue
S
0 to 1768
˚
C
(32 to 3214
˚
F)
+Black
-Red
+White
-Blue
T
-200 to 400
˚
C
(-328 to 752
˚
F)
+Blue
-Red
+White
-Blue
Thermocouple 0: use Input 9
as negative input and 10 as positive.
Thermocouple 1: use Input 7
as negative input and 8 as positive.
RTD
PT100 (Sensor 0): use Input 9 and 10, related to CM signal.
PT100 (Sensor 1): use Input 7 and 8, related to CM signal.
4 wire PT100 can be used by leaving one of the sensor leads unconnected