background image

Unitronics 

Vision™ OPLC™ 

Installation Guide 

V130-33-B1/V130-J-B1 

V350-35-B1/V350-J-B1 

V430-J-B1 

General Description 

 

All of the controllers covered in this guide are micro-OPLCs, rugged programmable logic controllers that 

comprise built-in operating panels. 

Item 

V130-B1 

V130J-B1 

V350-B1 

V350J-B1 

   V430J-B1 

Screen 

2.4" 

3.5" Color Touch 

4.3" Color Touch 

Keypad 

Yes 

None 

Function Keys 

None 

Yes 

Com Port, Built-in 

RS232/485 

Yes 

Yes 

Yes 

Yes 

Yes* 

USB device, 

mini-B 

None 

None 

None 

None 

Yes* 

Com Ports, separate 

order, user-installed  

The user may install a CANbus port (V100-17-CAN), and 

one

 of the following: 

RS232/RS485 port (V100-17-RS4/V100-17-RS4X) 

Ethernet (V100-17-ET2)

Profibus Slave (V100-17-PB1)

* V430J comprises both RS232/485 and USB ports; note that only 

one

 channel may be used at a time.

1B

Standard Kit Contents 

 

Item 

V130-B1 

V130J-B1 

V350-B1 

V350J-B1 

V430J-B1 

Controller 

Yes 

Terminal Blocks 

Yes 

Battery (installed) 

Yes 

Slides  

(2 sets of key labels) 

None 

Yes 

None 

Mounting Brackets 

Yes (2 parts) 

Yes (4 parts) 

Rubber Seal 

Yes 

Programming cable 

+ RS232 adapter 

Yes 

None 

USB  

programming cable 

None

 

Yes

 

 

Содержание Vision OPLC V130-33-B1

Страница 1: ...B device mini B None None None None Yes Com Ports separate order user installed The user may install a CANbus port V100 17 CAN and one of the following RS232 RS485 port V100 17 RS4 V100 17 RS4X Ethernet V100 17 ET2 Profibus Slave V100 17 PB1 V430J comprises both RS232 485 and USB ports note that only one channel may be used at a time 1BStandard Kit Contents Item V130 B1 V130J B1 V350 B1 V350J B1 V...

Страница 2: ...airs Failure to comply with appropriate safety guidelines can cause severe injury or property damage Do not attempt to use this device with parameters that exceed permissible levels To avoid damaging the system do not connect disconnect the device when power is on Environmental Considerations Do not install in areas with excessive or conductive dust corrosive or flammable gas moisture or rain exce...

Страница 3: ...30J V350J 92x92 mm 3 622 x3 622 V430J 122 5x91 5 mm 4 82 x3 6 2 Slide the controller into the cut out ensuring that the rubber seal is in place 3 Push the mounting brackets into their slots on the sides of the panel as shown in the figure below 4 Tighten the bracket s screws against the panel Hold the bracket securely against the unit while tightening the screw 5 When properly mounted the controll...

Страница 4: ...an external circuit breaker Guard against short circuiting in external wiring Use appropriate circuit protection devices Unused pins should not be connected Ignoring this directive may damage the device Double check all wiring before turning on the power supply Caution To avoid damaging the wire do not exceed a maximum torque of 0 5 N m 5 kgf cm Do not use tin solder or any substance on stripped w...

Страница 5: ...ontroller requires an external 12VDC or 24VDC power supply The power supply must include double insulation Outputs must be rated as SELV PELV Class2 Limited Power Use separate wires to connect the functional earth line pin 3 and the 0V line pin 2 to the system earth ground Install an external circuit breaker Guard against short circuiting in external wiring Double check all wiring before turning o...

Страница 6: ...ommunicate with serial devices and applications such as SCADA Use RS485 to create a multi drop network containing up to 32 devices Pinouts The pinouts below show the PLC port signals RS232 RS485 Controller Port Pin Description Pin Description Pin 1 1 DTR signal 1 A signal 2 0V reference 2 RS232 signal 3 TXD signal 3 RS232 signal 4 RXD signal 4 RS232 signal 5 0V reference 5 RS232 signal 6 DSR signa...

Страница 7: ...n RS485 network USB Port Caution The USB port is not isolated Make sure that the PC and the controller are grounded to same potential The USB port may be used for programming OS download and PC access Setting RS232 RS485 Communication Parameters V130 V350 V130J V350J This port may be set to either RS232 or RS485 via jumper The accompanying figure shows the jumper factory default settings These jum...

Страница 8: ...shown on page 7 Closing the Controller V130 V350 V130J V350J Only 1 Gently replace the board Make certain that the pins fit correctly into their matching receptacle Do not force the board into place doing so may damage the controller 2 Replace the back cover of the controller and fasten the corner screws Note that you must replace the back cover securely before powering up the controller Samara te...

Отзывы: