
V200-18-E3XBW
S n a p - i n I / O M o d u l e
Unitronics
15
Table 1: Thermocouple input ranges
Type
Temperature range
Wire Color
ANSI (USA) BS 1843 (UK)
mV -5
to
56mV
-
-
B
200 to 1820
°
C
(300 to 3276
°
F)
+Grey
-Red
+None
-Blue
E
-200 to 750
°
C
(-328 to 1382
°
F)
+Violet
-Red
+Brown
-Blue
J
-200 to 760
°
C
(-328 to 1400
°
F)
+White
-Red
+Yellow
-Blue
K
-200 to 1250
°
C
(-328 to 2282
°
F)
+Yellow
-Red
+Brown
-Blue
N
-200 to 1300
°
C
(-328 to 2372
°
F)
+Orange
-Red
+Orange
-Blue
R
0 to 1768
°
C
(32 to 3214
°
F)
+Black
-Red
+White
-Blue
S
0 to 1768
°
C
(32 to 3214
°
F)
+Black
-Red
+White
-Blue
T
-200 to 400
°
C
(-328 to 752
°
F)
+Blue
-Red
+White
-Blue
Analog Outputs
Number of outputs
4 (single-ended)
Output range
0-10V, 0-20mA. See Note 12.
Resolution
12-bit (4096 units)
Conversion time
Synchronized to scan time.
Load impedance
1k
V
minimum—voltage
500
V
maximum—current
Galvanic isolation
Analog outputs to bus
Yes
Analog outputs to
Analog/PT/TC inputs
Yes
Analog outputs to analog
outputs
No
Linearity error
±0.1%
Operational error limits
±0.2%
Notes:
12. Note that the range of each I/O is defined by wiring, jumper settings, and within the controller’s
software.
Environmental
IP20 / NEMA1
Operating temperature
0
°
to 45
°
C (32
°
to 113
°
F)
Storage temperature
-20
°
to 60
°
C (-4
°
to 140
°
F)
Relative Humidity (RH)
5% to 90% (non-condensing)
Dimensions (WxHxD)
138x23x123mm (5.43x0.9x4.84”)
Weight
279g (9.87 oz)