background image

In this figure, the jumper settings will cause

the controller to function as follows:

Digital inputs: npn, 24VDC inputs
Analog input 1: Voltage input
Analog input 0: Current input

®

4

The tables below show how to set a specific jumper to change the functionality of the controller.

To open the controller and access the jumpers, refer to the directions at the end of these specifications.

Important:

Incompatible jumper settings and wiring connections may severely damage the controller.

Jumper #

NPN

PNP*

Jumper #

Voltage

Current

Digital*

JP1

A

A

B

Digital Inputs

JP3

A

B

Analog 1 / I14

JP4

A

BB

JP2

A

A

B

Analog 0 / I15

JP5

A

BB

V120-22-R34

I/O Jumper Setting

5410-1231-9

V120-22-R34

06/09

*Default factory setting

Opening the controller enclosure

1. Locate the 4 slots on the sides of the enclosure
2. Using the blade of a flat-bladed screwdriver, gently pry off the

back of the controller as shown in the figure below, exposing the
controller's board.

Unitronics reserves the right to revise this publication from time to time and to

amend its contents and related hardware and software at any time.
Technical updates (if any) may be included in subsequent editions (if any).
Unitronics product sold hereunder can be used with certain products of other

manufacturers at the user’s sole responsibility.

A   B

1

2

3

4

5

Содержание V120-22-R34

Страница 1: ...ts are wired for use as a high speed counter input shaft encoder See Notes 4 and 5 Resolution 32 bit Input freq 10kHz max Minimum pulse 40µs 1 Notes 1 The total number of inputs is 22 All of these may be used as normal digital inputs Via jumper settings and wiring certain of these inputs may be adapted to analog inputs 2 All 22 inputs can be set to pnp source or npn sink via a single jumper and ap...

Страница 2: ...an time Absolute max rating 15V 30mA Full scale error 2 LSB Linearity error 2 LSB Status indication Yes See Note Note The analog value can also indicate when the input is functioning out of range If an analog input deviates above the permissible range its value will be 1024 2 Relay outputs 12 relay in 3 groups See Note Output type SPST NO Form A Type of relay Tyco PCN 124D3MHZ or compatible Isolat...

Страница 3: ...umber of I Os may vary according to expansion model V120 22 R34 06 09 Keypad Sealed membrane Number of keys 16 Program Application memory 448K Memory Bits coils 4096 Memory Integers registers 2048 Long Integers 32 bit 256 Double Word 32 bit unsigned 64 Floats 24 Timers 192 Counters 24 Data Tables 120K RAM 64K FLASH HMI displays Up to 255 Execution time 0 8µs for bit operations Graphic Display STN ...

Страница 4: ...uts JP3 A B Analog 1 I14 JP4 A B B JP2 A A B Analog 0 I15 JP5 A B B V120 22 R34 I O Jumper Setting 5410 1231 9 V120 22 R34 06 09 Default factory setting Opening the controller enclosure 1 Locate the 4 slots on the sides of the enclosure 2 Using the blade of a flat bladed screwdriver gently pry off the back of the controller as shown in the figure below exposing the controller s board Unitronics re...

Отзывы: