background image

Installation Guide, V130/V350/V430/SM35/SM43/SM70 COM Modules 

2/15

Unitronics 

 

V130/V350/SM35

 

1.  Locate the two screws that fasten the board to 

the controller and remove them. 

2.  Hold the main board by Port 1 and by the I/O 

expansion port, and pull it out of the controller.  

 

 

3.  Remove the plastic tab marked A and B, and 

then break the tab in two. 

 

4.  Install the module as shown in the 

accompanying figure. 

 
       

 

5. If you are installing the V100-17-PB1,  pay attention to the cable direction. 

6. If you are installing the V100-17-RS4/X, Pay attention to RS232 to RS485: DIP Switch Settings: 

 

Switch Settings 

 

 

RS232* 

ON 

ON 

OFF 

OFF 

ON 

ON 

RS485 

OFF 

OFF 

ON 

ON 

OFF 

OFF 

RS485 with 
termination** 

ON 

ON 

ON 

ON 

OFF 

OFF 

*Default factory setting

 

**Causes the unit to function as an end unit in an RS485 network

 

7.  If you are installing: 

 - V100-17-RS4/X Return plastic tab 

B

 over the new port. 

 - V100-17-ET2, V100-S-ET2 or V100-17-PB1 Return plastic tab 

A

 over the new port. 

8.  Replace the main board, including the fastening screws. 

V130 only

 

1.  Replace the ribbon cable. 
2.   Push the cable connector down to lock the 

cable in place. 

 

 

Содержание V100-17-RS4X

Страница 1: ...ocal and national standards and regulations Only qualified service personnel should open this device or carry out repairs Failure to comply with appropriate safety guidelines can cause severe injury or property damage Do not attempt to use this device with parameters that exceed permissible levels To avoid damaging the system do not connect disconnect the device when power is on Environmental Cons...

Страница 2: ...le Cover under the arrow direction Follow the instructions below for installing the appropriate module type Installing V100 17 RS4 X V100 17 ET2 V100 S ET2 V100 17 PB1 Note that the procedures below include the V130 V350 V430 SM35 SM43 and SM70 However if you are installing the module into the V130 the keypad must be disconnected and reconnected Separate instructions are provided for this procedur...

Страница 3: ...tention to the cable direction 6 If you are installing the V100 17 RS4 X Pay attention to RS232 to RS485 DIP Switch Settings Switch Settings 1 2 3 4 5 6 RS232 ON ON OFF OFF ON ON RS485 OFF OFF ON ON OFF OFF RS485 with termination ON ON ON ON OFF OFF Default factory setting Causes the unit to function as an end unit in an RS485 network 7 If you are installing V100 17 RS4 X Return plastic tab B over...

Страница 4: ...tures designs materials and other specifications of its products and to either permanently or temporarily withdraw any of the forgoing from the market All information in this document is provided as is without warranty of any kind either expressed or implied including but not limited to any implied warranties of merchantability fitness for a particular purpose or non infringement Unitronics assume...

Отзывы: