![Unitronics UniStream USC-B10-RA28 Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/unitronics/unistream-usc-b10-ra28/unistream-usc-b10-ra28_installation-manual_845632009.webp)
UniStream® PLC
Unitronics
9
Note that below, the letters “xx” that is used in the model numbers
means that the section
refers both to B5/C5 and B10/C10 models.
I/O Connection Points
The IOs for these models are arranged in
three groups of fifteen points each, as
shown in the figures to the right.
Top groups
Input connection points
Bottom group
Output connection points
The function of certain I/Os may be
adapted via wiring and software settings.
USC-xx-RA28
USC-xx-TA30
Wiring the Digital Inputs
The digital inputs are arranged in two isolated groups:
▪
I0-I9 share common CM0
▪
I10-I13 share common CM1
Each group may be wired together as sink or source.
Inputs I10, I11, I12 and I13 can be configured as either normal digital inputs or as high
speed inputs that can receive high speed pulse signals from sensors or shaft encoders.
High Speed Input Modes
Following are the different pin assignments for the high speed channels:
Channel 1
Channel 2
I10
I11
I12
I13
Quadrature
Phase A
Phase B
Phase A
Phase B
Pulse+Direction
Pulse
Direction
Pulse
Direction
Pulse
Pulse
Normal digital
Pulse
Normal digital
N
OTE
▪
Input modes are set both by wiring and software.
Input wiring, sink
Input wiring, source