Unitronics JZ20-J-T20HS Скачать руководство пользователя страница 3

JZ20-T1X/JZ20-J-T1X/JZ20-J-T20HS 

 

01/16 

 

Unitronics 

 

 

Caution

 

  To avoid damaging the wire, use a maximum torque of 0.5 N·m (5 kgf·cm). 

  Do not use tin, solder, or any substance on stripped wire that might cause the wire 

strand to break. 

  Install at maximum distance from high-voltage cables and power equipment. 

 

Wiring Procedure 

Use crimp terminals for wiring; use 3.31 mm ² 

–0.13 mm² wire (12-26 AWG): 

1. 

Strip the wire to a length of 7±0.5mm (0.270

–0.300“). 

2. 

Unscrew the terminal to its widest position before inserting a wire.  

3. 

Insert the wire completely into the terminal to ensure a proper connection. 

4. 

Tighten enough to keep the wire from pulling free. 

Wiring Guidelines 

  Use separate wiring ducts for each of the following groups:  

o

 

Group 1: Low voltage I/O and supply lines, communication lines.  

o

 

Group 2: High voltage Lines, Low voltage noisy lines like motor driver outputs.  

Separate these groups by at least 10cm (4"). If this is not possible, cross the ducts at a 90˚angle. 

  For proper system operation, all 0V points in the system should be connected to the system 0V  

supply rail. 

Allow for voltage drop and noise interference with input lines used over an extended distance.  
Use wire that is properly sized for the load. 

Earthing the product 

To maximize system performance, avoid electromagnetic interference as follows: 

 

Use a metal cabinet. 

 

Connect the 0V terminal directly to the earth ground of the system. 

 

Use the shortest, less than 1m (3.3 ft.) and thickest, 2.08mm² (14AWG) min, wires possible.

 

Inputs 

1. 

All the products comprise I0-I5; these digital inputs are arranged in a single group. Via wiring, 
the entire group may be set to either pnp or npn. 

2. 

The following information concerns JZ20-T10/JZ20-J-T10 and JZ20-T18/JZ20-J-T18: 
I0 and I1 can function as high-speed counters or as normal digital inputs. 

3. 

The following information concerns JZ20-J-T20HS:  

  I0, I1, and I4 can function as high-speed counters, as part of a shaft-encoder, or as           

normal digital inputs.  

  I2, I3, and I5 can function as either counter reset, as part of a shaft-encoder, or as 

    

  

normal digital inputs.  

  If I0, I1, I4 are set as high-speed counters (without reset), I2, I3, I5 can function as normal 

digital inputs.  

4. 

The following information concerns JZ20-T18/JZ20-J-T18 and JZ20-J-T20HS in addition to I0-
I5, these comprise the following: 

I6 and I7 may be wired as either digital or analog inputs. These may be wired as either: 

  npn digital inputs 

  pnp digital inputs 

  analog (voltage) inputs 

In addition, one input may be wired as a pnp input, while the other is wired as an analog input. 
Note that if one input is wired as an npn input, the other may not be wired as an analog input. 

5. 

The following information concerns JZ20-T18/JZ20-J-T18 and JZ20-J-T20HS: 
AN0 and AN1 are analog (current) inputs. 

Содержание JZ20-J-T20HS

Страница 1: ...ese examples Please dispose of this product according to local and national standards and regulations Only qualified service personnel should open this device or carry out repairs Failure to comply with appropriate safety guidelines can cause severe injury or property damage Do not attempt to use this device with parameters that exceed permissible levels To avoid damaging the system do not connect...

Страница 2: ...oximately 40mm 1 58 For UL listed module in order to meet the UL508 standard panel mount this device on the flat surface of a Type 1 enclosure Wiring This equipment is designed to operate only in SELV PELV Class 2 Limited Power environments All power supplies in the system must include double insulation Power supply outputs must be rated as SELV PELV Class 2 Limited Power Do not connect either the...

Страница 3: ...electromagnetic interference as follows Use a metal cabinet Connect the 0V terminal directly to the earth ground of the system Use the shortest less than 1m 3 3 ft and thickest 2 08mm 14AWG min wires possible Inputs 1 All the products comprise I0 I5 these digital inputs are arranged in a single group Via wiring the entire group may be set to either pnp or npn 2 The following information concerns J...

Страница 4: ...s npn and the other as pnp or wire both groups as npn or as pnp In either case the n p pins must be connected Input wiring I0 I7 npn sink Input wiring I0 I7 pnp source Input wiring I0 I5 pnp source I6 I7 npn sink JZ20 J T20HS Note The inputs are arranged in two groups You can wire one group as npn and the other as pnp or wire both groups as npn or as pnp In either case the n p pins must be connect...

Страница 5: ...T1X JZ20 J T1X JZ20 J T20HS 01 16 Unitronics 5 Input wiring I0 I5 pnp source I6 I7 npn sink HSC input wiring npn sink HSC input wiring pnp source Shaft encoder wiring npn sink Shaft encoder wiring pnp source ...

Страница 6: ...of its products and to either permanently or temporarily withdraw any of the forgoing from the market All information in this document is provided as is without warranty of any kind either expressed or implied including but not limited to any implied warranties of merchantability fitness for a particular purpose or non infringement Unitronics assumes no responsibility for errors or omissions in th...

Отзывы: