IO-DI16   

I / O   E x p a n s i o n   M o d u l e  

1 1 / 0 0

 

Unitronics Industrial Automation Systems 

 

 

Connecting Expansion Modules 

An adapter provides the interface between the OPLC and an expansion module. To connect the I/O module to the 
adapter or to another module: 

Push the module-to-module connector into the port located on the right side of the device. 

Note that there is a protective cap provided with the adapter.  This cap covers the port of the 

final 

 I/O module in the system. 

 

 

To avoid damaging the system, do not connect or disconnect the device when the  
power is on. 

 

Component identification 

1 Module-to-module 

connector 

2 Protective 

cap 

 

 

1

2

 

Wiring 

Wire Size  

Use 26-12 AWG wire (0.13 mm 

2

–3.31 mm

2

) for all wiring purposes. 

Wiring Considerations 

 

Note that the adapter and input signals must be connected to the same 0V signal. 

 

Do not use tin, solder or any other substance on the stripped wire that might cause the wire strand to break.  

 

We recommend that you use crimp terminals for wiring. 

 

Install at maximum distance from high-voltage cables and power equipment. 

 

General Wiring Procedures  

 

Strip the wire to a length of 7±0.5mm (0.250–0.300 inches).  

Unscrew the terminal to its widest position before inserting a wire.  

Insert the wire completely into the terminal to ensure that a proper 
connection can be made. 

Tighten enough to keep the wire from pulling free.  

To avoid damaging the wire, do not exceed a maximum torque of 0.5 N·m (5 kgf·m). 

 

 

Do not touch live wires. 

 

Double-check all the wiring before turning on the power supply. 

 

Содержание IO-DI16

Страница 1: ...hnician or engineer trained in the local and national electrical standards should perform tasks associated with the electrical wiring of this device Under no circumstances will Unitronics be liable or responsible for any consequential damage that may arise as a result of installation or use of this equipment and is not responsible for problems resulting from improper or irresponsible use of this d...

Страница 2: ...om edges of the device and the enclosure walls Do not place in water or let water leak onto the unit Do not allow debris to fall inside the unit during installation DIN rail mounting Snap the device onto the DIN rail as shown below the module will be squarely situated on the DIN rail 60mm 3 5mm 14mm 80mm 93mm 44 5mm IO DI16 9 8 10 11 12 13 14 15 I7 I6 I5 I4 I3 I2 I1 I0 I8 I9 I10 I11 I12 I13 I14 I1...

Страница 3: ...11 00 IO DI16 I O Expansion Module Unitronics Industrial Automation Systems 3 4mm 5 8mm 85mm 80mm 68 4mm 93mm 4mm x2 ...

Страница 4: ... AWG wire 0 13 mm 2 3 31 mm2 for all wiring purposes Wiring Considerations Note that the adapter and input signals must be connected to the same 0V signal Do not use tin solder or any other substance on the stripped wire that might cause the wire strand to break We recommend that you use crimp terminals for wiring Install at maximum distance from high voltage cables and power equipment General Wir...

Страница 5: ...inputs may be wired as either pnp or npn inputs npn sink input wiring shown in top group of inputs high speed counter frequency measurer npn sink I8 I9 I10 I11 I12 I13 I14 I15 P N 0V 0V V Circuit Protection Device High speed Counter Reset High speed Counter pnp source IO DI16 9 8 10 11 12 13 14 15 I7 I6 I5 I4 I3 I2 I1 I0 I8 I9 I10 I11 I12 I13 I14 I15 P N 0V P N 0V 0V V Circuit Protection Device 0V...

Страница 6: ...gic 0 0 5VDC 4 3mA for Logic 1 Input current 6mA 24VDC Response time 10mSec typical Input 15 The specifications below apply when this input is wired for use as a high speed counter input frequency measurer See Notes 1 and 2 Resolution 16 bit Frequency 5kHz maximum Minimum pulse width 80µs Environmental IP20 Operating temperature 0 to 50 C Storage temperature 20 to 60 C Relative Humidity RH 5 to 95...

Страница 7: ...dule identification number Adapter The formula below is used to assign addresses for I O modules used in conjunction with the M90 OPLC X is the number representing a specific module s location 0 7 Y is the number of the input or output on that specific module 0 15 The number that represents the I O s location is equal to 32 x 16 y Examples Input 3 located on expansion module 2 in the system will b...

Страница 8: ...conjunction with the EX A1 adapter 12 bit sign 2 outputs 10V 0 20mA 4 20mA 12 bit 4 inputs 0 10V 0 20mA 4 20mA IO AI4 AO2 Analog I O To order the expansion module that best fits your system contact your local distributor For a list of Unitronics distributors check our website http www unitronic com contact htm 12 bit 4 PT100 50 to 460 C IO PT4 PT 100 8 8 8 8 8 8 8 8 C C C C C C C C o o o o o o o o...

Отзывы: