SPECIFICATIONS:
UPS UNITEK
MODEL
ALPHA 750Ps, 1000Ps & 1200Ps
CAPACITY
VA/W
750VA/360W, 1000VA/480W & 1200VA/600W
INPUT
Voltage
220, 230, 240VAC
Voltage Range
+/- 25%
Frequency
50Hz / 60Hz Auto sensing
OUTPUT
Voltage
220, 230, 240VAC
Voltage Regulation
+/- 10% with Automatic Voltage Regulation
Frequency
50Hz or 60Hz
Frequency Regulation
(Battery Mode)
+/- 0.5%
Output Waveform
Modified Sinewave
Topology
Line Interactive
Transfer Time
4ms Typical
Number of sockets
4 IEC with Back-up
BATTERY
Battery Type
Sealed, Lead Acid, Maintenance Free,
Rechargeable
Battery Quantity and
Capacity
1 x 12V/7.2AH, 1 x 12V/7.2AH & 1 x 12V/9AH
Recharge Time
4 Hours to 90% after complete discharge
Protection
Self-Diagnostics Upon Power On
INDICATOR
AC Mode
Green LED lighting
Battery Mode
Yellow LED lighting
Fault
Red LED lighting
AUDIBLE
ALARM
Battery Mode
Sounding every 4 seconds / Alarm Reset
Function
Low Battery
Sounding every second
Overload
Continuously sounding
PROTECTION
Switch Function
UPS Automatic Switch for City Power &
Battery
Unit Input
Fuse for Overload & Short Circuit Protection
Overload Protection
UPS Automatic Shutdown if Overload:
Over 110% of Nominal at 60 Seconds and
130% at 5 Seconds
Short Circuit
UPS Output Cut Off Immediately and Input
Fuse Protection
Spike Protection
80 Joules, Over 2ms
Green Mode
Inverter will Automatically Shutdown without
Load
Modem / Network
RJ-11
APPROVALS
Noise Suppression
MEETS CE (EN 50091) and FCC Class B
Surge Suppression
MEET IEEE 587
PHYSICAL
Dimension, DxWxH
275 x 110 x 202 (mm)
Weight: Net / Gross
5.3 / 5.8 (kgs), 5.9 / 6.4 (kgs) & 6.5 / 7 (kgs)
ENVIRONMENT
Altitude
Less than 5000 meters
Temperature
0 °C ~ 50 °C
Relative Humidity
0 ~ 90 % (non-condensing)
Audible Noise Level
Less than 40dB (1 meter from surface)
INTERFACE
Smart RS-232 or USB,
cable included
Support Windows: 95, NT4.0, 98SE, ME, 2K,
XP, Server2003
Linux: Redhat7.0~7.3 & Mandrake8.2, Novell:
4.X & 5.1
www.unitekamerica.com
Содержание ALPHA 750 PS
Страница 13: ...ESPECIFICACIONES ...