background image

 

2 / 2 

 

P/N 3102365-

EN • REV 003 • ISS 14FEB18 

To perform an initial installation test: 

1.  Visually inspect each detector and verify that it is installed in the 

correct location. Make sure it is not adversely affected by factors 
not apparent on the plans. 

2.  Remove the detector from its base and verify that the proper 

detector address, trouble signals, and messages are reported. 

3.  If wired for Class A operation, verify that the detector continues to 

operate first with SLC_IN disconnected, and then with SLC_OUT 
disconnected. (Refer to the installation sheet for the base.) 

4.  Place a momentary ground fault on the SLC to verify operation of 

ground fault detection circuitry. 

5.  Perform a function test, as described below. 

To perform a function test: 

1.  If desired, use the fire alarm control panel to put the detector or 

zone into a service group for testing. (Refer to the panel technical 
reference manual for instructions.) 

2.  Activate the heat sensor using a hair dryer (maintaining a distance 

of three inches) or using a Testifire detector tester per the 
manufacturer’s instructions. 

Maintenance 

To ensure proper operation, plan maintenance in accordance with the 
requirements of the authority having jurisdiction. Refer to  
CAN/ULC-S536 

Standard for the Inspection and Testing of Fire Alarm 

Systems

 and NFPA 

72 National Fire Alarm and Signaling Code.

 

Refer to application bulletin P/N 3102403-EN for additional information 
and cleaning instructions. 

Specifications 

 

Operating voltage 

15.20 to 19.95 VDC 

Current 
 

Normal operating 

 

Alarm 

 
51 µA 
68 µA 

Vibration level 

10 to 35 Hz, with an amplitude of 
0.01 in. 

Maximum spacing [1] 

50 ft. (15.2 m) centers 

Compatible bases 
 

Standard 

 

Relay 

 

Isolator 

 

Audible 

 
SIGA-SB, SIGA-SB4 
SIGA-RB, SIGA-RB4 
SIGA-IB, SIGA-IB4 
SIGA-AB4, SIGA-AB4G  
SIGA-AB4GT, SIGA-AB4G-LF 

Compatible detector testers [2] 

Testifire 2000 

Operating environment 
 

Temperature 

 

Relative humidity 

 
32 to 100°F (0 to 38°C) 
0 to 93% noncondensing 

Storage temperature 

−4 to 140°F (−20 to 60°C) 

[1] When replacing SIGA-HRS and SIGA-HFS detectors with the 
SIGA-HFD, ensure that the spacing is 50 ft. (15.2 m) or less. 

[2] Requires the SIGA2-TSTSPACER Testifire adapter assembly. 

Regulatory information 

 

North American 
standards 

CAN/ULC-S530-M91, UL 521 

UL and ULC fixed-
temp alarm rating 

135°F (57.2°C) 

Actual alarm point 

129 to 141°F (53.9 to 60.6°C) 

Response time  
index 

Quick(evaluated by FM Approvals) 

FCC compliance 

This device complies with part 15 of the FCC 
Rules. Operation is subject to the following two 
conditions: (1) This device may not cause harmful 
interference, and (2) this device must accept any 
interference received, including interference that 
may cause undesired operation. 

Industry Canada 
compliance 

This Class A digital apparatus complies with 
Canadian ICES-003. 

Contact information 

For contact information, see www.edwardsfiresafety.com 
 

Отзывы: