United Technologies Edwards SIGA-CT1 Скачать руководство пользователя страница 2

 

2 / 3 

 

P/N 387021P-EN • REV 14 • ISS 14MAR17 

Figure 1: Installing the SIGA-CT1 module 

 

(1)  Compatible electrical box 
(2) SIGA-CT1 

module 

(3) Wall 

plate 

  (4)  #6-32 × 5/8 machine screw 

(2X) 

(5)  #4 × 1/2 self-tapping screw 

 

Wiring 

Wire this device in accordance with applicable national and 
local codes, ordinances, and regulations. 

Notes 

• 

Refer to the Signature loop controller installation sheet for 
SLC wiring specifications for additional details. 

• 

All wiring is power-limited and supervised. 

• 

A test resistor is supplied with the SIGA-CT1 to prevent 
trouble signals on unused circuits during installation. 
When connecting field wires, remove the test resistors and 
install a UL/ULC Listed 47 k

 EOLR at the end of the 

circuit. 

To wire the module: 

1.  Verify that all field wiring is free of opens, shorts, and 

ground faults. 

2.  Strip 1/4 in. (about 6 mm) from the ends of all wires that 

connect to the terminal block of the module. 

When stripping wire ends, exposing more wire may cause 
a ground fault; exposing less wire may result in a faulty 
connection. 

3.  Make all wiring connections as shown in Figure 2. 

Figure 2: Wiring diagram 

 

(1)  EOL resistor (PN EOL-47) 
(2) 22 

k

 resistor for use with 

personality code 18 

(3)  Typical NO initiating device 
(4)  10 VDC at 350 µA, max. 
(5)  Red LED (alarm/active) 

  (6)  Green LED (normal) 

(7)  Signaling line circuit (from 

previous device) 

(8)  Signaling line circuit (to next 

device) 

Specifications 

 
Operating voltage 

15.20 to 19.95 VDC 

Current 
 Standby 
 Activated 

 
300 µA 
450 µA 

Ground fault impedance 

10 k

 

Initiating device circuit (IDC)
 

EOL resistor value 

 

Circuit resistance  

 Circuit 

capacitance 

 
47 k

, UL/ULC Listed 

50 

 (25 

 per wire), max. 

0.1 µF max. 

Circuit designation 
 

Signaling line circuit 

 

Notification line circuit 

 
Class A, Style 6 or Class B, Style 4 
Class B, Style B 

Wire sizes 

12 to 18 AWG wire (1.0 to 4.0 mm²) 

Compatible electrical boxes 

2-1/2 in. (64 mm) deep single-gang 
box; 4-in. square box 1-1/2 in (38 mm) 
deep with single-gang cover 

LPCB/CPR electrical box 
 Requirements 
 
 

Minimum (W × H × D) 

 
Plastic box with cover plate, no gaps or 
unused holes 
2.4 × 3.5 × 1.5 in. (60 × 85 × 38 mm) 

Operating environment 
 Temperature 
 Relative 

humidity 

 
32 to 120°F (0 to 49°C) 
0 to 93% noncondensing 

Storage temperature range 

4 to 140°F (

20 to 60°C) 

(1)

(2)

(3)

(4)

(4)

(5)

7

8

1

2

3

4

+

+

(1)

(3)

(4)

(6)

(8)

(7)

(5)

(2)

(4)

(1)

(3)

Отзывы: