28
12.2
95-8616
APPENDIX G
SENSOR COMPARISON/CROSS SENSITIVITY
Electrochemical Gas Sensors
1
Time to reach percentage of final reading when gas concentration equal to full scale is applied to sensor.
2
Background concentrations of ammonia may shorten lifetime of sensor.
3
Sensor approved for oxygen depletion (< 21% V/V) only.
4
Factory Mutual Performance Approved.
Gas
Range
Response
Time
1
Accuracy of
Reading
(Whichever
is Greater)
Operating
Temperature Range
Zero Drift
Performance
Approved Standard
Hydrogen Sulfide
(H
2
S)
0-20 PPM
T20 = ≤7 Sec
T50 = ≤10 Sec.
T90 = ≤16 Sec.
±2 ppm or
±10% of Reading
–40°C to +50°C
± 1 ppm/Mo.
ISA 92.00.01
4
Hydrogen Sulfide
(H
2
S)
0-50 PPM
T20 = ≤4 Sec
T50 = ≤7 Sec.
T90 = ≤16 Sec.
±2 ppm or
±10% of Reading
–40°C to +50°C
± 1 ppm/Mo.
ISA 92.00.01
4
Hydrogen Sulfide
(H
2
S)
0-100 PPM
T20 = ≤5 Sec
T50 = ≤8 Sec.
T90 = ≤21 Sec.
±2 ppm or
±10% of Reading
–40°C to +50°C
± 2 ppm/Mo.
ISA 92.00.01
4
Hydrogen
(H
2
S+)
0-20 PPM
T20 = ≤10 Sec
T50 = ≤13 Sec.
T90 = ≤23 Sec.
±2 ppm or
±10% of Reading
–40°C to +55°C
± 1 ppm/Mo.
ISA 92.00.01
4
Hydrogen
(H
2
S+)
0-50 PPM
T20 = ≤6 Sec
T50 = ≤9 Sec.
T90 = ≤15 Sec.
±2 ppm or
±10% of Reading
–40°C to +55°C
± 1 ppm/Mo.
ISA 92.00.01
4
Hydrogen
(H
2
S+)
0-100 PPM
T20 = ≤6 Sec
T50 = ≤8 Sec.
T90 = ≤15 Sec.
±2 ppm or
±10% of Reading
–40°C to +55°C
± 2 ppm/Mo.
ISA 92.00.01
4
Ammonia (NH
3
)
0-100 PPM
2
T50 = 24 Sec.
T90 = 65 Sec.
±4 ppm or
±10% of Reading
–20°C to +40°C
± 2 ppm/Mo.
FM6340
4
Ammonia (NH
3
)
0-500 PPM
2
T50 = 30 Sec.
T90 = 120 Sec.
±4 ppm or
±10% of Reading
–20°C to +40°C
± 10 ppm/Mo.
Det-Tronics Verified
(CSA Exd)
Oxygen (O
2
)
0-25% V/V
3
T20 = 7 Sec.
T90 = 30 Sec.
< 0.5% V/V
–20°C to +50°C
< 2 %/Mo.
BS EN 50104
4
Carbon
Monoxide (CO)
0-100 PPM
T50 = 15 Sec.
T90 = 40 Sec.
±5 ppm or
±10% of Reading
–20°C to +50°C
± 2 ppm/Mo.
ISA 92.00.01
4
Carbon
Monoxide (CO)
0-500 PPM
T50 = 12 Sec.
T90 = 25 Sec.
±5 ppm or
±10% of Reading
–20°C to +50°C
± 9 ppm/Mo.
ISA 92.00.01
4
Sulfur
(SO
2
+)
0-20 PPM
T50 = 12 Sec.
T90 = 30 Sec.
±0.6 ppm or
±10% of Reading
–40°C to +55°C
± 0.4 ppm/Mo.
Det-Tronics Verified
(CSA Exd)
Sulfur
(SO
2
+)
0-100 PPM
T50 = 15 Sec.
T90 = 35 Sec.
±0.6 ppm or
±10% of Reading
–40°C to +55°C
± 0.4 ppm/Mo.
Det-Tronics Verified
(CSA Exd)
Chlorine
(Cl
2
)
0-10 PPM
T50 = ≤14 Sec.
T90 = ≤34 Sec.
±0.6 ppm or
±10% of Reading
–20°C to +50°C
< 0.2 ppm/Mo.
FM6340
4
Hydrogen
(H
2
)
0-1,000 PPM
T50 = 8 Sec.
T90 = 60 Sec.
±50 ppm or
±10% of Reading
–20°C to +40°C
± 20 ppm/Mo.
Det-Tronics Verified
(CSA Exd)
Nitrogen Dioxide
(NO
2
)
0-20 PPM
T50 = 7 Sec.
T90 = 31 Sec.
±2 ppm or
±10% of Reading
–20°C to +40°C
± 0.1 ppm/Mo.
Det-Tronics Verified