96
Table 100 — Alert and Alarm Codes
ALARM OR
ALERT
NUMBER
DESCRIPTION
ACTION TAKEN BY CONTROL
RESET
METHOD
PROBABLE CAUSE
A051
Circuit A, Compressor 1 Stuck On Failure
Turn off all compressors
Manual
Welded contact
P051
Circuit A, Compressor 1 Failure
Add strike to compressor
Automatic
(max 3)
High pressure switch, compressor
current, wiring error
T051
Circuit A, Compressor 1 Failure
Compressor locked off
Manual
Exceeded 3 strike limit
A052
Circuit A, Compressor 2 Stuck On Failure
Turn off all compressors
Manual
Welded contact
P052
Circuit A, Compressor 2 Failure
Add strike to compressor
Automatic
(max 3)
High pressure switch, compressor
current, wiring error
T052
Circuit A, Compressor 2 Failure
Compressor locked off
Manual
Exceeded 3 strike limit
A055
Circuit B, Compressor 1 Stuck On Failure
Turn off all compressors
Manual
Welded contact
P055
Circuit B, Compressor 1 Failure
Add strike to compressor
Automatic
(max 3)
High pressure switch, compressor
current, wiring error
T055
Circuit B, Compressor 1 Failure
Compressor locked off
Manual
Exceeded 3 strike limit
A056
Circuit B, Compressor 2 Stuck On Failure
Turn off all compressors
Manual
Welded contact
P056
Circuit B, Compressor 2 Failure
Add strike to compressor
Automatic
(max 3)
High pressure switch, compressor
current, wiring error
T056
Circuit B, Compressor 2 Failure
Compressor locked off
Manual
Exceeded 3 strike limit
T072
Evaporator Discharge Reset Sensor Failure
Unit shutdown
Automatic Faulty remote input on CEM board
T073
Outside Air Temperature Thermistor Failure
Stop use of economizer
Automatic Faulty thermistor or wiring error
T074
Space Temperature Thermistor Failure
Unit shutdown
Automatic Faulty thermistor or wiring error
T075
Return Air Thermistor Failure
Continue to run unit
Automatic Faulty thermistor or wiring error
T076
Outside Air Relative Humidity Sensor Failure
Use OAT changeover control
Automatic Faulty sensor or wiring error
T078
Return Air Relative Humidity Sensor Failure
Use differential dry bulb changeover
Automatic Faulty sensor or wiring error
T082
Space Temperature Offset Sensor Failure
Use Space temperature without offset
Automatic Faulty sensor or wiring error
T090
Circuit A Discharge Pressure Transducer Failure
Stop circuit
Automatic
Faulty sensor, wiring error
T091
Circuit B Discharge Pressure Transducer Failure
Stop circuit
Automatic
Faulty sensor, wiring error
T092
Circuit A Suction Pressure Transducer Failure
Stop circuit
Automatic
Faulty sensor, wiring error
T093
Circuit B Suction Pressure Transducer Failure
Stop circuit
Automatic
Faulty sensor, wiring error
T110
Circuit A Loss of Charge
Stop circuit
Manual
Low refrigerant charge
T111
Circuit B Loss of Charge
Stop circuit
Manual
Low refrigerant charge
A120
Circuit A Low Saturated Suction Temperature Alarm.
Stop circuit
Manual
Low refrigerant charge, low airflow,
dirty coil, broken fan belt, TXV
problem
P120
Circuit A Low Saturated Suction Temp-Comp A2 Shutdown
Compressor A2 shutdown
Automatic
Low refrigerant charge, low airflow,
dirty coil, broken fan belt, TXV
problem
T120
Circuit A Low Saturated Suction Temperature Alert.
Stop circuit
Automatic
Low refrigerant charge, low airflow,
dirty coil, broken fan belt, TXV
problem
A121
Circuit B Low Saturated Suction Temperature Alarm.
Stop circuit
Manual
Low refrigerant charge, low airflow,
dirty coil, broken fan belt, TXV
problem
P121
Circuit B Low Saturated Suction Temp-Comp B2 Shutdown
Compressor B2 shutdown
Automatic
Low refrigerant charge, low airflow,
dirty coil, broken fan belt, TXV
problem
T121
Circuit B Low Saturated Suction Temperature Alert.
Stop circuit
Automatic
Low refrigerant charge, low airflow,
dirty coil, broken fan belt, TXV
problem
T122
Circuit A High Saturated Suction Temperature
Stop circuit
Manual
TXV problem, high load
T123
Circuit B High Saturated Suction Temperature
Stop circuit
Manual
TXV problem, high load
P126
Circuit A High Head Pressure, Comp Shutdown
Circuit staged down
Automatic
Dirty condenser, condenser fan fail-
ure, system overcharged
T126
Circuit A High Head Pressure Alert
Stop circuit
Automatic
Dirty condenser, condenser fan
failure, system overcharged
A126
Circuit A High Head Pressure Alarm
Stop circuit
Manual
Dirty condenser, condenser fan fail-
ure, system overcharged
P127
Circuit B High Head Pressure Comp Shutdown
Circuit staged down
Automatic
Dirty condenser, condenser fan fail-
ure, system overcharged.
T127
Circuit B High Head Pressure Alert
Stop circuit
Automatic
Dirty condenser, condenser fan
failure, system overcharged
A127
Circuit B High Head Pressure Alarm
Stop circuit
Manual
Dirty condenser, condenser fan fail-
ure, system overcharged
T128
Digital Scroll High Discharge Temperature Alert
Digital compressor A1 shutdown
Automatic
Refrigeration problem
A128
Digital Scroll High Discharge Temperature Alarm
Digital compressor A1 locked off
Manual
Refrigeration problem
A140
Reverse Rotation Detected
Stop unit
Manual
Incorrect compressor wiring
A150
Unit is in Emergency Stop
Stop unit
Manual
External shutdown command
T153
Real Time Clock Hardware Failure
Stop unit
Manual
Control Board failure, check lights
A154
Serial EEPROM Hardware Failure
Stop unit
Manual
Control Board failure, check lights
T155
Serial EEPROM Storage Failure Error
Stop unit
Manual
Control Board failure, check lights
A156
Critical Serial EEPROM Storage Failure Error
Stop unit
Manual
Control Board failure, check lights
A157
A/D Hardware Failure
Stop unit
Manual
Control Board failure, check lights
A168
Low Ambient Control Board (SCB2) Comm Failure
Cooling is disabled
Automatic
Incorrect wiring, power loss
A169
Expansion Valve Control Board Comm Failure
Humidi-MiZer Control Disabled
Automatic
Incorrect wiring, power loss
A171
Staged Gas Control Board Comm Failure
Stop gas heat
Automatic
Control Board failure, check lights
A172
Staged Gas Control Board 2 (SCB2) Comm Failure
Stop cooling function
Automatic
Incorrect wiring, power loss
A173
ECB1 Board Communication Failure
Stop economizer & power exh
Automatic
Control Board failure, check lights
A174
ECB2 Board Communication Failure
Stop unit
Automatic
Control Board failure, check lights
T177
4-20 mA Demand Limit Failure
Stop demand limiting
Automatic
Input failure, wiring error
T178
4-20 mA Static Pressure Reset/VFD Fail
Stop static pressure reset/VFD
Automatic
Input Failure, wiring error
Содержание Carrier Weathermaker 48A2
Страница 105: ...105 Fig 20 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units...
Страница 106: ...106 Fig 21 Typical Auxiliary Control Box Wiring Schematic...
Страница 107: ...107 Fig 22 Typical 2 Stage Gas Heat Wiring Schematic Size 060 Units Shown a48 8357...
Страница 108: ...108 TO NEXT PAGE Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown A48 7296...
Страница 109: ...109 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown cont A48 8358...
Страница 110: ...110 Fig 24 Typical Electric Heat Control Schematic 50 Series Size 060 Units Shown a50 8228...
Страница 111: ...111 Fig 25 Typical Power Schematic 48 50A2 A3 A4 A5 060 Unit Shown...
Страница 112: ...112 Fig 26 Typical Low Ambient Controls Option Wiring...
Страница 113: ...113 Fig 27 Typical Small Chassis Component Location Size 020 035 Units...
Страница 114: ...114 Fig 28 Typical Large Chassis Component Locations Size 040 060 Units...
Страница 118: ...118 Fig 30 Economizer Control Board ECB1 and VAV Control Board ECB2 A48 7706...
Страница 142: ...142 A48 3733 Fig 56 Main Burner Removal...
Страница 176: ...176 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716...