76
Table 74 — Switch Logic Configuration
Table 75 — Display Configuration
Demand Limit Switch 2/Dehumidify — Off (
DL2.L
) —
The demand limit switch no. 2 input is set for normally open
for off. If a field-supplied demand limit switch is used that is
normally closed, change this variable to closed.
IAQ Discrete Input — Low (
IAQ.L
) — The IAQ discrete in-
put is set for normally open when low. If a field-supplied IAQ
discrete input is used that is normally closed, change this vari-
able to closed.
Fire Shutdown — Off (
FSD.L
) — The fire shutdown input is
set for normally open when off. If a field-supplied fire shut-
down input is used that is normally closed, change this variable
to closed.
Pressurization Switch — Off (
PRS.L
) — The pressurization
input is set for normally open when off. If a field-supplied pres-
surization input is used that is normally closed, change this
variable to closed.
Evacuation Switch — Off (
EVC.L
) — The evacuation input is
set for normally open when off. If a field-supplied evacuation in-
put is used that is normally closed, change this variable to closed.
Smoke Purge — Off (
PRG.L
) — The smoke purge input is set
for normally open when off. If a field-supplied smoke purge in-
put is used that is normally closed, change this variable to closed.
Display Configuration —
The
DISP
submenu is used
to configure the local display settings. A list is shown in
Table 75.
Test Display LEDs (
TEST
) — This is used to test the opera-
tion of the
Comfort
Link display.
Metric Display (
METR
) — This variable is used to change
the display from English units to Metric units.
Language Selection (
LANG
) — This variable is used to
change the language of the
Comfort
Link display. At this time,
only English is available.
Password Enable (
PAS.E
) — This variable enables or dis-
ables the use of a password. The password is used to restrict
use of the control to change configurations.
Service Password (
PASS
) — This variable is the 4-digit nu-
meric password that is required if enabled.
Remote Control Switch Input —
The remote switch
input is located on the ECB-1 board and connected to TB6
terminals 1 and 3. The switch can be used for several remote
control functions. See Table 76.
Remote Input State
(
Inputs
GEN.I
REMT
) — This is
the actual real time state of the remote input.
Remote Switch Config
(
Configuration
UNIT
RM.CF
)
— This is the configuration that allows the user to assign dif-
ferent types of functionality to the remote discrete input.
• 0 — NO REMOTE SW — The remote switch will not be
used.
• 1 — OCC-UNOCC SW — The remote switch input will
control the occupancy state. When the remote switch
input is ON, the unit will forced into the occupied mode.
When the remote switch is OFF, the unit will be forced
into the unoccupied mode.
• 2 — STRT/STOP — The remote switch input will start
and stop the unit. When the unit is commanded to stop,
any timeguards in place on compressors will be honored
first. When the remote switch is ON, the unit will be
commanded to stop. When the remote switch is OFF the
unit will be enabled to operate.
• 3 — OVERRIDE SW — The remote switch can be used
to override any internal or external time schedule being
used by the control and force the unit into an occupied
mode when the remote input state is ON. When the
remote switch is ON, the unit will be forced into an occu-
pied state. When the remote switch is OFF, the unit will
use its internal or external time schedules.
Table 76 — Remote Switch Configuration
Remote Switch Logic Configuration
(
Configuration
SW.LG
RMI.L
) — The control allows for the configuration
of a normally open/closed status of the remote input switch via
RMI.L
. If this variable is configured OPEN, then when the
switch is open, the remote input switch perceives the logic state
as OFF. Correspondingly, if
RMI.L
is set to CLOSED, the re-
mote input switch will perceive a closed switch as meaning
OFF. See Table 77.
ITEM
EXPANSION
RANGE
CCN POINT
DEFAULT
SW.LG
SWITCH LOGIC: NO / NC
FTS.L
Filter Status Inpt-Clean
Open/Close
FLTSLOGC
Open
IGC.L
IGC Feedback - Off
Open/Close
GASFANLG
Open
RMI.L
RemSw Off-Unoc-Strt-NoOv
Open/Close
RMTINLOG
Open
ECS.L
Economizer Switch - No
Open/Close
ECOSWLOG
Open
SFS.L
Fan Status Sw. - Off
Open/Close
SFSLOGIC
Open
DL1.L
Dmd.Lmt.Sw.1 - Off
Open/Close
DMD_SW1L
Open
DL2.L
Dmd.Lmt.2 Dehumid - Off
Open/Close
DMD_SW2L
Open
IAQ.L
IAQ Disc.Input - Low
Open/Close
IAQINLOG
Open
FSD.L
Fire Shutdown - Off
Open/Close
FSDLOGIC
Open
PRS.L
Pressurization Sw. - Off
Open/Close
PRESLOGC
Open
EVC.L
Evacuation Sw. - Off
Open/Close
EVACLOGC
Open
PRG.L
Smoke Purge Sw. - Off
Open/Close
PURGLOGC
Open
ITEM
EXPANSION
RANGE
UNITS
POINT
DEFAULT
TEST
Test Display LEDs
ON/OFF
TEST
Off
METR
Metric Display
ON/OFF
DISPUNIT
Off
LANG
Language Selection
0-1(multi-text strings)
LANGUAGE
0
PAS.E
Password Enable
ENABLE/DISABLE
PASS_EBL
Enable
PASS
Service Password
0000-9999
PASSWORD
1111
ITEM
EXPANSION
RANGE
CCN
POINT
REMT
Remote Input State
ON/OFF
RMTIN
RM.CF
Remote Switch Config 0 - 3
RMTINCFG
RMI.L
RemSw
Off-Unoc-Strt-NoOv
Open/Close
RMTINLOG
Содержание Carrier Weathermaker 48A2
Страница 105: ...105 Fig 20 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units...
Страница 106: ...106 Fig 21 Typical Auxiliary Control Box Wiring Schematic...
Страница 107: ...107 Fig 22 Typical 2 Stage Gas Heat Wiring Schematic Size 060 Units Shown a48 8357...
Страница 108: ...108 TO NEXT PAGE Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown A48 7296...
Страница 109: ...109 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown cont A48 8358...
Страница 110: ...110 Fig 24 Typical Electric Heat Control Schematic 50 Series Size 060 Units Shown a50 8228...
Страница 111: ...111 Fig 25 Typical Power Schematic 48 50A2 A3 A4 A5 060 Unit Shown...
Страница 112: ...112 Fig 26 Typical Low Ambient Controls Option Wiring...
Страница 113: ...113 Fig 27 Typical Small Chassis Component Location Size 020 035 Units...
Страница 114: ...114 Fig 28 Typical Large Chassis Component Locations Size 040 060 Units...
Страница 118: ...118 Fig 30 Economizer Control Board ECB1 and VAV Control Board ECB2 A48 7706...
Страница 142: ...142 A48 3733 Fig 56 Main Burner Removal...
Страница 176: ...176 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716...