39
Table 39 — 48/50A030-060 Units VAV and Adaptive CV/SAV Staging Sequence with
Variable Capacity Compressor
*With minimum load valve ON.
Table 40 — 2-Stage Sequence —
48/50A2,A4020-027
Table 41 — 2-Stage Sequence —
48/50A2,A4030-060
Table 42 — Staging Sequence without Hot Gas Bypass —
48/50A3,A5020-027 and Multi-Stage 48/50A2,A4020-027
Table 43 — Staging Sequence with Hot Gas Bypass —
48/50A3,A5020-027 and Multi-Stage 48/50A2,A4020-027
*With minimum load valve ON.
STAGE
SEQUENCE 1
0
1
2
3
4
COMP
Compressor Status
A1*
OFF
ON
ON
ON
ON
A2
OFF
OFF
ON
ON
ON
B1
OFF
OFF
OFF
ON
ON
B2
OFF
OFF
OFF
OFF
ON
UNIT
Unit Capacity 48/50A
030
0%
12.5% to 25%
37.5% to 50%
62.5% to 75%
87.5% to 100%
035
0%
9.8% to 19.6%
29.4% to 29.4%
59.8% to 69.6%
90.2% to 100%
040
0%
12.5% to 25%
37.5% to 50%
62.5% to 75%
87.5% to 100%
050
0%
12.5% to 25%
37.5% to 50%
62.5% to 75%
87.5% to 100%
060
0%
12.5% to 25%
37.5% to 50%
62.5% to 75%
87.5% to 100%
STAGE
SEQUENCE 1
SEQUENCE 2
0
1
2
0
1
2
Thermostat Inputs
Thermostat Inputs
Y1
OPEN CLOSED CLOSED OPEN CLOSED CLOSED
Y2
OPEN
OPEN
CLOSED OPEN
OPEN
CLOSED
COMP
Compressor Status
Compressor Status
A1
OFF
ON
ON
OFF
OFF
ON
A2
OFF
OFF
ON
OFF
ON
ON
B1
OFF
OFF
ON
OFF
OFF
ON
UNIT
Unit Capacity
Unit Capacity
020
0%
30%
100%
0%
30%
100%
025
0%
33%
100%
0%
33%
100%
027
0%
33%
100%
0%
33%
100%
STAGE
SEQUENCE 1
SEQUENCE 2
0
1
2
0
1
2
Thermostat Inputs
Thermostat Inputs
Y1
OPEN CLOSED CLOSED OPEN CLOSED CLOSED
Y2
OPEN
OPEN
CLOSED OPEN
OPEN
CLOSED
COMP
Compressor Status
Compressor Status
A1
OFF
ON
ON
OFF
OFF
ON
A2
OFF
OFF
ON
OFF
ON
ON
B1
OFF
ON
ON
OFF
OFF
ON
B2
OFF
OFF
ON
OFF
ON
ON
UNIT
Unit Capacity
Unit Capacity
030
0%
50%
100%
0%
50%
100%
035
0%
50%
100%
0%
50%
100%
040
0%
50%
100%
0%
50%
100%
050
0%
50%
100%
0%
50%
100%
060
0%
50%
100%
0%
50%
100%
STAGE
SEQUENCE 1
SEQUENCE 2
0
1
2
3
0
1
2
3
COMP
Compressor Status
Compressor Status
A1
OFF
ON
ON
ON
OFF
OFF
OFF
ON
A2
OFF
OFF
OFF
ON
OFF
ON
ON
ON
B1
OFF
OFF
ON
ON
OFF
OFF
ON
ON
UNIT
Unit Capacity 48/50A
Unit Capacity 48/50A
020
0%
30%
70%
100%
0%
30%
70%
100%
025
0%
33%
67%
100%
0%
33%
67%
100%
027
0%
33%
67%
100%
0%
33%
67%
100%
STAGE
SEQUENCE 1
SEQUENCE 2
0
1
2
3
4
0
1
2
3
4
COMP
Compressor Status
Compressor Status
A1
OFF
ON*
ON
ON
ON
OFF
OFF
OFF
OFF
ON
A2
OFF
OFF
OFF
OFF
ON
OFF
ON*
ON
ON
ON
B1
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
ON
UNIT
Unit Capacity 48/50A
Unit Capacity 48/50A
020
0%
10%
30%
70%
100%
0%
10%
30%
70%
100%
025
0%
17%
33%
67%
100%
0%
17%
33%
67%
100%
027
0%
17%
33%
67%
100%
0%
17%
33%
67%
100%
Содержание Carrier Weathermaker 48A2
Страница 105: ...105 Fig 20 Typical Main Control Box Wiring Schematic 48 50A2 A3 A4 A5 Units...
Страница 106: ...106 Fig 21 Typical Auxiliary Control Box Wiring Schematic...
Страница 107: ...107 Fig 22 Typical 2 Stage Gas Heat Wiring Schematic Size 060 Units Shown a48 8357...
Страница 108: ...108 TO NEXT PAGE Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown A48 7296...
Страница 109: ...109 Fig 23 Typical Staged Gas Heat Wiring Schematic Size 060 Units Shown cont A48 8358...
Страница 110: ...110 Fig 24 Typical Electric Heat Control Schematic 50 Series Size 060 Units Shown a50 8228...
Страница 111: ...111 Fig 25 Typical Power Schematic 48 50A2 A3 A4 A5 060 Unit Shown...
Страница 112: ...112 Fig 26 Typical Low Ambient Controls Option Wiring...
Страница 113: ...113 Fig 27 Typical Small Chassis Component Location Size 020 035 Units...
Страница 114: ...114 Fig 28 Typical Large Chassis Component Locations Size 040 060 Units...
Страница 118: ...118 Fig 30 Economizer Control Board ECB1 and VAV Control Board ECB2 A48 7706...
Страница 142: ...142 A48 3733 Fig 56 Main Burner Removal...
Страница 176: ...176 APPENDIX C VFD INFORMATION cont Fig F Internal Enclosure Fan Replacement A48 7716...