background image

MINIMUM 12 IN.
TO COMBUSTIBLES

PART A, FIGURE 8
(FIGURE 5 CONTIUED ON NEXT PAGE)

1.

Use a minimum 3-1/2" thick brick masonry wall framed into the combustible wall.  A fireclay liner (ASTM C315 or
equivalent) having a 5/8" minimum wall thickness must be used and it must be at least 12" away from any material
that could catch fire.  The inside diameter of the fireclay liner shall be sized for the proper snug fit of a 6" diameter
chimney connector pipe. The fireclay liner shall run from the outer surface of the brick wall to, but not beyond, the
inner surface of the chimney flue and shall be firmly cemented in place. See Part A of Figure 8.

2.

Use a solid insulated listed factory-built chimney length having an inside diameter of 6" and having 1" or more of
solid insulation.  There must be at least a 9" air space between the outer wall of the chimney length and any
combustible materials.  The inner end of the chimney length shall be flush with the inside of the masonry chimney
flue shall be sealed to the flue and to the brick masonry penetration with nonwater-soluble refractory cement.  Sheet
steel supports which are at least 24 gauge(0.024") in thickness shall be securely fastened to wall
surfaces on all sides.  Fasteners between supports and the chimney length shall not penetrate the chimney liner.
See Part B of Figure 8.

3.

Use a 10" diameter ventilated thimble made of at least 24 gauge(0.024") steel having two 1" air channels.  The venti-
lated thimble must be separated from combustible materials by a minimum of 6" glass fiber insulation.  The opening
in the combustible wall shall be covered and the thimble supported with sheet steel supports which are at least 24
gauge (0.024") in thickness.  The sheet steel supports shall be securely fastened to wall surfaces on all sides and
shall be sized to fit and hold the chimney section.  Fasteners used to secure chimney sections shall not penetrate
chimney flue liner.  See Part C of Figure 8.

4.

Use an 8" inside diameter solid insulated listed factory-built chimney length which has 1" or more of solid insulation.
The minimum length of this chimney section shall be 12" and will serve as a pass-through for the 6" diameter
chimney connector.  There must be at least a 12" air space between the outer wall of the chimney section and any
combustible materials.  The chimney section shall be concentric with and spaced 1" away from the chimney connec
tor by means of sheet steel support plates on both ends of the chimney section.  The opening in the combustible wall
shall be covered and the chimney section supported on both sides with sheet steel supports which are at least 24
gauge (0.024") in thickness.  The sheet steel supports shall be securely fastened to wall surfaces on all sides and
shall be sized to fit and hold the chimney section.  Fasteners used to secure chimney sections shall not penetrate
chimney flue liner. See Part C of Figure 8.

5.

A listed factory-built wall pass-through system may be purchased and installed according to the instructions pack
aged with it to provide a safe method of passing the chimney connector through a combustible wall for connection
to a masonry chimney.

Additional requirements pertaining to Figure 8 and the above wall pass-through systems:

1.

Insulation material used as part of wall pass-through system shall be of noncombustible material and shall have a
thermal conductivity of 1.0 Btu • in./ft.² • °F (4.88 kg • cal/hr • m² • °C) or less

2.

All clearances and thicknesses are minimums:  larger clearances and thickness are acceptable.

3.

A chimney thimble, as shown for 3" and 4" above (Parts C and D respectively of Figure 8) shall be for types "3" and
4" connections to facilitate removal of the chimney connector for cleaning.  The chimney thimble shall be of  ASTM
C315 fireclay with 5/8" minimum wall thickness , or material or equivalent durability.  The inside diameter of the
thimble shall be sized for the proper snug fit of a 6" diameter chimney connector pipe.  The thimble shall be installed
without  damage to the chimney flue.  The thimble shall extend through the chimney wall to, but not beyond, the
inner surface of the chimney flue and shall be permanently cemented in place with high temperature cement.

4.

A chimney connector to a masonry chimney, except for 2" above (Part B of Figure 8), shall extend through the wall
pass-through system to the inner face of the chimney flue, but not beyond.  It does not have to be fastened in place
so long as it cannot accidently be pulled out of the chimney or shoved into the chimney flue.  If fasteners are used
to secure the chimney connector to a masonry chimney, the fasteners shall not penetrate the chimney flue liner.

5.

Any material used to close up any opening for the connector shall be noncombustible.

CHIMNEY FLUE

MINIMUM CHIMNEY CLEARANCE TO
BRICK AND COMBUSTIBLES IS 2 IN.

MINIMUM CLEARANCES 12 IN.
OF BRICK ALL AROUND

CHINEY CONNECTOR TO
HEATER

FIRE CLAY LINER
(5/8" MIN. WALL THICKNESS)

MIN. 3-1/2" THICK BRICK
MASONRY WALL

MASONRY CHIMNEY
CONSTRUCTED TO
NFPA 211

7

Содержание LOGWOOD 2421

Страница 1: ...O OBTAIN EFFICIENT DEPENDABLE SERVICE FROM THE HEATER AND ENABLE YOU TO ORDER REPAIR PARTS CORRECTLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE UNITED STATES STOVE COMPANY 227 Industrial Park Road P O Box 151 South Pittsburg TN 37380 423 837 2100 COMPANY U NITED STATES STOV E C S S U 851094D Owners Manual Owners Manual Owners Manual Owners Manual Owners Manual Logwood 2421 EPA EXEMPT PER METHOD 28A...

Страница 2: ... or Electric Drill Bit 1 8 Dia For Sheet Metal Screws Adjustable Wrench Screw Driver Blade Type Gloves Safety Glasses MATERIALS 6 Elbow Collar and Thimble As Required 24 gauge min 1 2 Sheet Metal Screws No 10A x 1 2 6 Diameter 24 gauge black or blued steel Underwriters Laboratories UL Listed Residential Type HT 2100 F Chimney or use a Masonry Chimney in goor repair Floor Protector Material R value...

Страница 3: ...one to use this heater who is unfamiliar with the correct opera tion of the heater 1 2 3 4 5 6 7 8 9 10 11 12 13 14 For further information on using your heater safely obtain a copy of the National Fire Pro tection Association NFPA publication Using Coal and Wood Stoves Safely NFPA No HS 10 1978 The address of the NFPA is Batterymarch Park MA 02269 Disposal of Ashes Place ashes in a metal containe...

Страница 4: ...er the feed door and secure with screw in slot After consulting the installation instructions for mini mum clearances to combustibles locate your floor protector accordingly and carefully place the stove in your selected location Install stove pipe elbows and thimbleasnecessary utilizingeitherarecentlycleaned and inspected masonry chimney properly lined or a UL Listed chimney Insure that the dampe...

Страница 5: ... cement Also seal the pipe at the chimney Use 3 sheet metal screws at each joint to make the piping rigid It is recommended that no more than two 2 90 degree bends be used in the stove pipe installation as more than two 2 may decrease the amount of draw and possibly cause smoke spillage 1 2 3 4 5 6 7 NOTE The chimney connector shall not pass through an attic roof space floor ceiling or similar con...

Страница 6: ...e connected to a masonry chimney by passing through a combustible wall NFPA Standard 211 allows the following wall pass through systems MASONRY CHIMNEY CONSTRUCTED TO NFPA 211 AIRTIGHT CLEANOUT DOOR FLOOR PROTECTOR COMBUSTIBLE WALL TO HEATER CHIMNEY CONNECTOR CEILING SEE PARTS A B C D AND E OF THIS FIGURE FOR OPTIONS CHIMNEY FLUE FIGURE 8 CONNECTION OF CHIMNEY CONNECTOR TO A MASONRY CHIMNEY THROUG...

Страница 7: ... by means of sheet steel support plates on both ends of the chimney section The opening in the combustible wall shall be covered and the chimney section supported on both sides with sheet steel supports which are at least 24 gauge 0 024 in thickness The sheet steel supports shall be securely fastened to wall surfaces on all sides and shall be sized to fit and hold the chimney section Fasteners use...

Страница 8: ...NIMUM FACTORY BUILT CHIMNEY LENGHT SHEET STEEL SUPPORTS CHIMNEY SECTION CHIMNEY CONNECTOR AIR SPACE 2 IN TWO VENTILATED AIR CHANNELS EACH 1 INCH CONSTRUCED OF SHEET STEEL PART C FIGURE 8 PART D FIGURE 8 MASONRY CHIMNEY CONSTRUCTED TO NFPA 211 SHEET STEEL SUPPORTS 24 GAUGE MIN THICKNESS CHIMNEY CONNECTOR TO HEATER MINIMUM CHIMNEY CLEARANCES FROM MASONRY TO SHEET STEEL SUPPORTS AND COMBUSTIBLES 2 IN...

Страница 9: ...ralargequantity of coarse salt baking soda or cool ashes on top of the fire in the firebox CAUTION A chimney fire may cause ignition of wall studs or rafters which you thought were a safe distance from the chimney If you have a chimney fire have your chimney inspected by a qualified person before using again Service Hints Do not expect a heater to draw It is the chimney that creates the draft Smok...

Страница 10: ...327 40329 40330 40331 40332 D6 83427 40334 89971 89972 89973 89974 89975 851094 DESCRIPTION REAR LEG FRONT LEG MAIN BOTTOM MAIN SIDE MAIN BACK HEARTH PLATE SLIDING DRAFT PLATE DOOR FRAME DOOR MAIN TOP LID LID SUPPORT LID LIFTER FLUE COLLAR SOLID FLUE DAMPER DOOR PINS DRAFT CONTROL KNOB HANDLE LATCH NUTS HANDLE EXTENSION HANDLE BRACKET OWNERS MANUAL QNTY 2 2 1 2 1 1 1 1 1 1 2 1 1 1 1 2 1 1 1 2 1 1 ...

Страница 11: ...NOTES 11 ...

Страница 12: ...EN WRITING ALWAYS GIVE THE FULL MODEL NUMBER WHICH IS ON THE NAMEPLATE ATTACHED TO THE BACK OF THE HEATER WHEN ORDERING REPAIR PARTS ALWAYS GIVE THE FOLLOWING INFORMATION AS SHOWN IN THIS LIST 1 The PART NUMBER 2 The PART DESCRIPTION 3 The MODEL NUMBER 2421 4 The SERIAL NUMBER UNITED STATES STOVE COMPANY 227 Industrial Park Road P O Box 151 South Pittsburg TN 37380 423 837 2100 www USSTOVE com ...

Отзывы: