TROUBLE SHOOTING

Unplug stove before preforming any maintenance work

PROBLEM

CAUSES

SOLUTIONS

Fire burns with a lazy, orange flame

and/or fuel builds up in the firepot

Insufficient combustion air

Feed rate too high

Corn or wood pellets have too much

moisture

Combustion/Exhaustion blower

plugged or going out

Venting plugged with fly ash or ice

House does not have adequate make

up air (negative pressure)

Inadequate “Draft” of PL Vent

Remove any clinkers or ash from the

firepot by using scraping tool.  Shake

ashes into ash pan.

Clean out primary air in firepot holes

if plugged.

Empty ash drawer and clean out back

heat exchanger by removing the

lower access plates.

Tap the side exhaust heat exchang-

ers to clean them as shown on page

Change to a better grade of fuel if

necessary.  See page 4 regarding

fuel quality.

Check that damper control knob is

adjusted properly.  Pull out to increase

fire burn.

Extend PL Vent to 5’

Check gasket seal around the door.

If the door is loose, adjust the handle

latch.  A small adjustment can be

made to the door seal by adjusting

the door latch rod and/or the door

hinges.  Replace the door gasket if

necessary.

Check for blockage in the air inlet

tube or exhaust pipe.  Clean out as

necessary.

Check combustion exhaust lower

impeller.  This can be done remov-

ing the exhaust pipe and shining a

light into the tube.

Replace combustion exhaust blower

if necessary.

NOTE:  

Negative pressure in a home is

a serious issue.  All American Harvest

appliances should be installed with

outside air hookups.

Also make sure that adequate ventila-

tion is supplied for the rest of the home

or the unit will become the air intake

causing problems.

Содержание American Harvest 6035

Страница 1: ...or fire officials about restrictions and installation requirements peculiar to your area Do Not Plug this appliance into an electrical outlet before reading and understanding all operations and alway...

Страница 2: ...s you re helping CONSERVE AMERICA S ENERGY CONGRATULATIONS Heat Output 50 000 BTU HR Heating Capacity 1 500 Sq Ft Fuel Storage Capacity 60 Lbs Width 28 in 711mm Height 33 in 838mm Depth 28 in 711mm BT...

Страница 3: ...alling the product The American Harvest stove is designed to burn shelled corn cherry pits or pelletized fuel such as wood pellets The burning of other solid fuels such as cord wood or wood chips in t...

Страница 4: ...attention to the draft setting on your stove Therefore purchasing corn from the same source will help achieve a more consistent burn DONOTUSECORNWITHAHIGHWAXCONTENT WOOD PELLETS As with corn be consis...

Страница 5: ...s to side and back wall combustible materials NOTE These are minimum clearances to combustible walls established by the testing lab The amount of room needed on the left side of the unit to access the...

Страница 6: ...nlet elevation It is recommended that at least 5 ft of vertical pipe be installed when the appliance is vented directly through a wall This will create some natural draft to prevent the possibility of...

Страница 7: ...When venting into an existing masonry or factory built chimney the chimney must be cleaned with all creosote re moved The chimney must be a type suited for solid fuel WARNING The chimney and the chimn...

Страница 8: ...end down or with a wind hood Failure to do so could result in a burn back during high winds blowing directly up the air inlet during a simulta neous power failure see diagram above Blockage excessive...

Страница 9: ...ON IN A MOBILE HOME WARNING DO NOT INSTALL IN SLEEPING ROOM 1 Stove must be permanently bolted to the floor 2 Stove must have permanent outside air source 60FAK 3 Stove must be permanently electricall...

Страница 10: ...f the opening a 1 clearance is all that is required ALCOVE CLEARANCE RECOMMENDATIONS ALCOVE THROUGH THE WALL INSTALLATION REQUIREMENTS The stove is approved for horizontal exhaust however we recommend...

Страница 11: ...th pipe attached towards wall Pipe B will go through the wall thimble F Be careful not to dislodge the thimble Position stove not closer than 1 to the wall NOTE Make sure that you leave enough clearan...

Страница 12: ...Intake Optional 60FAK With 90 Degree Elbow or Hood Pest Guard 3 8 Mesh Maximum Clean Out Cover Tee 3 Min Wall Thimble Flashing Rain Cap or Termination Cap Storm Collar 24 Min INSIDE VERTICAL PIPE WIT...

Страница 13: ...Non Combustible Hearth Plate Support Bracket Every 5 Feet 1 Min Keep Attic Insulation Away From Pipe THROUGH THE WALL VERTICAL PIPE INSTALLATION WITH TERMINATION THROUGH THE ROOF The Hearth Pad is no...

Страница 14: ...gasket WARNING Do not operate unit with broken glass Do not substitute original factory glass You must use only factory authorized glass Do not slam door shut Do not strike glass Do not use abrasive...

Страница 15: ...Manual Draft Adjustment Slide in or out to adjust the amount of draft flowing through the firebox Ash Dump Shutoff Pull out to empty ashes out of the firebox area and back heat exchanger area Make su...

Страница 16: ...ve you another 3 minutes before fuel feeds in If the fire is burning too fast and the fuel is being burned up too quickly push the manual draft knob in a little to slow the fire down This should be do...

Страница 17: ...used if the home is over 2000 square feet or the weather is extremely cold The high heat setting is intended for use with wood pellets and the highest heat setting for corn would be the number 4 sett...

Страница 18: ...changes MAINTENANCE INSTRUCTIONS Surfaces on the front of the stove will be extremely hot during operation Always wear heat resistant gloves to perform periodic maintenance Using a wooden stick tap t...

Страница 19: ...will require weekly cleaning Cleaner fuels will allow for monthly cleaning of the exhaust system Remove the exhaust pipe from the back of your stove and remove any ash that may have collected in the...

Страница 20: ...AUTOMATIC SAFETY FEATURES Power Outage During a power outage the stove will shut down safely It will not automatically restart when the power returns unless the exhaust is still up to temperature see...

Страница 21: ...male terminal connectors one for each wire from wall thermostat Back of Circuit Board It is a good idea to use the thermostat option to achieve uniform control over your heating needs If you are gone...

Страница 22: ...hown on page Change to a better grade of fuel if necessary See page 4 regarding fuel quality Check that damper control knob is adjusted properly Pull out to increase fire burn Extend PL Vent to 5 Chec...

Страница 23: ...ressure switch or relay Check contents of the hopper Add fuel if necessary Have your USSC reseller diagnose the problem and replace the part s Stove runs for 30 minutes and then shuts down Exhaust gas...

Страница 24: ...r fly ash in the house Cleaning the window particularly when the stove is operating Leakage on the joints between the combustion fan exhaust pipe and PL vent This will be evidenced by dust on the impe...

Страница 25: ...USSC 25 WIRING DIAGRAM...

Страница 26: ...26 USSC REPAIR PARTS DIAGRAM 6035...

Страница 27: ...ocket 1 31 80460 Terminal Block 1 N S 80464 Terminal Block Jumper 1 32 80381 Low Limit Switch F110 Thermodisc 60T12 1 33 80381 Distribution Blower Limit Switch F110 Thermodisc 60T12 1 34 80455 Auger S...

Страница 28: ...AYS GIVE THE FULL MODEL NUMBER WHICH IS ON THE NAMEPLATE ATTACHED TO THE HEATER WHEN ORDERING REPAIR PARTS ALWAYS GIVE THE FOLLOWING INFORMATION AS SHOWN IN THIS LIST 1 THE PART NUMBER 2 THE PART DESC...

Отзывы: