background image

IMT117-06

www.ueonline.com

IMT117-06

www.ueonline.com

117 Series

Temperature Switch

Types B117, E117

U N I T E D   E L E C T R I C  

C O N T R O L S

Installation and Maintenance 

Instructions

IMT117-06

GENERAL

MISUSE OF THIS PRODUCT MAY CAUSE EXPLOSION AND PERSONAL 

INJURY.  THESE INSTRUCTIONS MUST BE THOROUGHLY READ AND 

UNDERSTOOD BEFORE UNIT IS INSTALLED.

            THIS  EQUIPMENT  IS  SUITABLE  FOR  CLASS  I,  DIVISION  2, 

GROUPS A,B,C,D; CLASS II, DIVISION 2, GROUPS F AND G; CLASS III; 

OR NON-HAZARDOUS LOCATIONS ONLY.

Types B117 (Immersion Stem)

The  117  Series  temperature  switch  utilizes  a  liquid  filled  sensor  which 

expands  or  contracts  against  a  bellows  to  detect  a  temperature  change.  

The  response,  at  a  pre-determined  set  point,  actuates  or  deactuates  a 

SPDT or DPDT snap-acting switch, converting the temperature signal into an 

electrical signal.  Control set point is adjusted by turning an internal dial (see 

adjustment - Part II).

Types E117 (Bulb & Capillary)

The 117 Series temperature switch utilizes a liquid-filled sensing bulb which 

hydraulically transmits temperature change to a bellows.  The response, at 

a pre-determined set point, actuates or deactuates a SPDT or DPDT snap-

acting  switch,  converting  the  temperature  signal  into  an  electrical  signal.  

Control  set  point  is  adjusted  by  turning  an  internal  dial  (see  adjustment 

- Part II).

MAXIMUM  TEMPERATURE:    THE  HIGHEST  TEMPERATURE  TO  WHICH 

A  SENSING  ELEMENT  MAY  BE  OCCASIONALLY  EXPOSED  TO  WITH-

OUT  ADVERSELY  AFFECTING  SET  POINT  CALIBRATION  AND  REPEAT-

ABILITY.  MAXIMUM  TEMPERATURE  STATED  IN  LITERATURE  AND  ON 

NAMEPLATE  MUST  NEVER  BE  EXCEEDED,  EVEN  BY  TEMPERATURE  OVER-

SHOOTS  IN  THE  SYSTEM.    OCCASIONAL  OPERATION  OF  UNIT  UP  TO  MAX. 

TEMPERATURE  IS  ACCEPTABLE  (E.G.,  START-UP,  TESTING).    CONTINUOUS 

OPERATION  SHOULD  BE  RESTRICTED  TO  THE  DESIGNATED  ADJUSTABLE 

RANGE.

THESE PRODUCTS DO NOT HAVE ANY FIELD REPLACEABLE PARTS.  

ANY SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR 

CLASS I, DIVISION 2

Part I - Installation

Tools Needed

Adjustable Wrench

Screwdriver

Hammer (for alternate wire knockouts)

MOUNTING

WARNING: EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT 

UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN 

TO BE NON-HAZARDOUS.

INSTALL  UNIT  WHERE  SHOCK,  VIBRATION  AND  TEMPERATURE 

FLUCTUATIONS ARE MINIMAL. MOUNT UNIT SO THAT MOISTURE IS 

PREVENTED  FROM  ENTERING  THE  ENCLOSURE.  IF  UNIT  IS  BEING 

INSTALLED WHERE HEAVY CONDENSATION IS EXPECTED, VERTICAL 

MOUNTING (TEMPERATURE SENSOR DOWN) IS REQUIRED. DO NOT MOUNT 

UNIT IN AMBIENT TEMPERATURES EXCEEDING PUBLISHED LIMITS.

ALWAYS  HOLD  A  WRENCH  ON  THE  TEMPERATURE  HOUSING  HEX 

WHEN MOUNTING UNIT. DO NOT TIGHTEN BY TURNING ENCLOSURE. 

THIS WILL DAMAGE SENSOR AND WEAKEN SOLDERED OR WELDED 

JOINTS.

117 Series Temperature Controls can be mounted in any position. Mount the 

unit via the (2) 1/4” screw clearance holes on the enclosure (see Mounting 

Dimensions).

Please read all instructional literature carefully and thoroughly before starting. Refer to the final page for the listing of Recommended 
Practices, Liabilities and Warranties.

For remote mounting, fully immerse the bulb and 6” capillary in the control 

zone. For best control, it is generally desirable to place the bulb close to the 

heating or cooling source in order to sense temperature fluctuations quickly. 

Be sure to locate the bulb so it will not be exposed to temperature beyond 

the instrument range limits.

WIRING

DISCONNECT  ALL  SUPPLY  CIRCUITS  BEFORE  WIRING  UNIT. 

WIRE  UNITS  ACCORDING  TO  NATIONAL  AND  LOCAL  ELECTRI-

CAL  CODES.  MAXIMUM  RECOMMENDED  WIRE  SIZE  IS  14  AWG.  

THE  RECOMMENDED  TIGHTENING  TORQUE  FOR  FIELD  WIRING 

TERMINALS IS 7 TO 17 IN-LBS.

ELECTRICAL RATINGS STATED IN LITERATURE AND ON NAMEPLATE 

SHOULD  NEVER  BE  EXCEEDED.  OVERLOAD  ON  A  SWITCH  CAN 
CAUSE FAILURE ON THE FIRST CYCLE.

Remove the two screws retaining the cover and cover gasket. A 1/2” NPT 
conduit connection is provided on the left hand side of the enclosure. Two 
cast-in 7/8” diameter knock outs for electrical conduits are located on the 
side  and  back  of  enclosure  (see  dimensional  drawings,  opposite  page). 
These  can  easily  be  knocked  out  by  placing  a  blade  of  a  screwdriver  in 
groove and tapping sharply with a hammer.  The terminal block terminals are 
clearly labeled “Common”, “Normally Open” and “Normally Closed.” For units 
supplied with DPDT, all terminals are labeled and the following color coding 
applies.

Grounding screw and clamp (cast in symbol) are provided. Keep the wire as 
short as possible to prevent interference with the plunger.

Part II - Adjustments

To change set point, turn dial and align with pointer.

Types B117 and E117

 with dial knob controls are factory calibrated for 

maximum accuracy at the midpoint of the scale.

Re-calibration

To re-calibrate, turn dial to desired set point. If the actual temperature and set point 
temperature do not agree, turn the 3/16” hex fine adjustment screw to the left to 
raise and to the right to lower temperature setting.

SPDT

DPDT

SWT1

SWT2

Common

Violet

Violet

Yellow

Normally Closed Black

Black

Red

Normally Open

Blue

Blue

Orange

Отзывы: