Installation, Operation and Maintenance Manual
VariCool EZ-Fit
9
Subject to change without notice.
40.20-IM (0118)
Physical Data
continued
Model
30
35
40
45
Capacity (a) (MBH)
Total
382.2
451.6
Sensible
283.5
330.7
CFM
12000
14000
GPM
90.0
105.0
EER
14.0
14.0
Blower
Type (QTY)
DDP (2)
Size (Dia.)
16.5
18.2
CFM Range
4800-13000
5500 - 14900
Filter
Type
Pleated Throwaway
Size (All 2” Thick.)
24 x 20 / 20 x 20
20 x 20 / 20 x 24
/ 24 x 24
Qty
6 / 3
2 / 5 / 2
Efficiency
MERV 8
Evaporator
Coil
Type
Interlaced
Face Area (Sq. Ft.)
23.9
27.1
Rows
5
FPI
10
Condenser
Type
Co-Axial
Working Pressure - Fluid
400 psig
Return Air
Duct Size
69” H x 60” W
69” H x 64” W
Supply Air
Duct Size
24-7/8” H x 15-1/2” W
24-7/8” H x 19” W
Compressor
Type
Hermetic Scroll
Qty
2
Refrigerant
Type
R-410a
Lbs-Ozs
30
40
Weight (b)
(Net Operating)
Evaporator
1000
1170
Condensing
1340
1570
Blower (DWDI)
X
X
Blower (DDP)
800 (2)
1040 (2)
Assembly w/ DWDI
X
X
Assembly w/ DDP
3940
4820
Dimensions
Evap. & Filter
69” W x 27-1/2”
D x 71” H
76” W x 29-1/2”
D x 71” H
Comp. & Cond.
69” W x 34” D x 71” H 76” W x 34” D x 71” H
Blower
34-1/2” W x 56-1/2”
D x 34” H
38” W x 58-1/2”
D x 34” H
Assembly
69” W x 56-1/2”
D x 105” H
76” W x 58-1/2”
D x 105” H
(a) Capacity based on 80° F DB / 67° F WB with 85° F EFT
(b) Basic unit only� Options will add weight for general purposes only actual charge may vary due to options and available heat