United CoolAir PAC12G3ASC Series Скачать руководство пользователя страница 12

 

12

 

Subject to change without notice.

Thermostat Bypass

The unit also has a Thermostat Bypass Switch 

which is used to manually force cooling or heating 

to be energized based on the mode selected by 

the Selector Switch. Thermostat bypass over-

rides the unit’s on-board thermostat and the 

Remote Thermostat. Both of the thermostats 

become non-functional in the bypass mode.
To operate in Bypass Mode, set the Selector 

Switch to the desired mode of operation (COOL 

or HEAT). Set the Thermostat Bypass Switch to 

the BYPASS position. At this point either COOL or 

HEAT will operate continuously without shutting 

down.

UNIT SAFETY DEVICES

Evaporator Motor Overload

The evaporator and condenser motors are 

protected by thermal overloads. The evaporator 

blower motor protection is internal and 

automatically resets once the temperature 

inside the windings of the motor falls below the 

temperature trip point.

Condenser Motor Overload

The condenser blower motor is external and 

protected manually with an overload block. This 

overload block is tied directly to the condenser 

motor contactor (CCM). This is a manual reset 

overload. If the condenser motor for any reason 

should cut out on overload, disconnect power 

using the unit’s circuit breaker then open the main 

control box. Press the reset button on the CCM 

overload block. Refer to the troubleshooting guide 

section for information on troubleshooting.

High Pressure Switch

The compressor system has a manual reset High 

Pressure Switch. If the unit is not providing cooling 

as evidenced by the Return Air Temperature “AIR 

IN” being approximately equal to the Supply Air 

Temperature “AIR OUT”, the compressor system 

may have tripped on high refrigerant pressure. 

Disconnect power using the unit’s circuit breaker. 

Remove the Access Panel to the Compressor 

Compartment and locate the Manual Reset High 

Pressure Switch. Press the button downward to 

verify if the switch tripped. If the button clicks the 

unit tripped on high pressure. Replace the access 

panel then reapply power using the unit’s circuit 

breaker. Set the unit to Cool Mode. Refer to the 

Troubleshooting section for causes and corrective 

actions. It may require a service technician to 

check system pressures if the switch trips more 

than 1-2 times.

Low Pressure Switch

The compressor system has an automatic reset 

low pressure safety switch. If the unit trips on 

low pressure, the compressor will shut down but 

automatically restart once the switch resets. The 

low pressure switch shuts down the compressor 

system if the refrigerant pressure falls below 70 

psig and automatically restarts the compressor 

once the pressure rises above 100 psig.

Compressor Internal Overload

Each compressor has an internal motor 

overload switch. This switch opens to protect the 

compressor motor when the temperature within 

the windings of the compressor motor exceeds 

the high temperature trip point. When this switch 

opens, the compressor motor will continue to 

operate but the compressor pumping mechanism 

“scroll” will become disconnected. To reset this 

condition, the power must be disconnected from 

the compressor contactor. Set the unit back to the 

FAN position and allow the unit to operate in the 

FAN position for approximately 30- 45 minutes. 

This should be enough time to cool the windings of 

the compressor motor which will allow the switch 

to reset (re-engaging the scroll). Set the Selector 

Switch back to COOL mode and the compressor 

should re-start. If this compressor goes out on 

internal overload condition, check the voltage. 

Since the compressor motor windings are cooled 

by the refrigerant gas as it enters the compressor, 

the unit may also be low on refrigerant.

Содержание PAC12G3ASC Series

Страница 1: ...Serial Number INSTALLATION AND OPERATION MANUAL 12 TON PORTABLE AIR CONDITIONING UNIT...

Страница 2: ...COMP LRA 351 EA QTY 2 RLA 53 6 EA EVAP MOTOR HP 15 0 FLA 35 COND MOTOR HP 3 0 EA QTY 2 RLA 8 6 EA ELEC HEATER KW 15 MCA 25 8 MOP 30 FACTORY CHARGE R 410A 46 lb 0oz CKT1 46 lb 0oz CKT2 TEST PRESS HISI...

Страница 3: ...path to ground are removed for servicing they must be reconnected at their original location Table of Contents IDENTIFICATION OF YOUR UNIT 2 PAC12G3ASC 208 230 Volt PRODUCT SPECIFICATIONS 4 PAC12G4ASC...

Страница 4: ...12 Ton Scroll Voltage Phasing Frequency 208 230 3 60 FLA Amps 48 1 LRA Amps 245 CONDENSER Airflow Belt Drive 6000 CFM 1 5 W C Horsepower 7 5 Voltage Phasing Frequency 208 230 3 60 FLA Amps 18 5 Speed...

Страница 5: ...FLA Amps 18 6 LRA Amps 125 CONDENSER Airflow Belt Drive 6000 CFM 1 5 W C Horsepower 7 5 Voltage Phasing Frequency 460 3 60 FLA Amps 8 4 Speed RPM 3450 EVAPORATOR Airflow Belt Drive 4800 CFM 1 0 W C H...

Страница 6: ...eration of this unit require that you follow them carefully The manufacturer assumes no liability for installations or servicing performed by non qualified personnel UNIT INSPECTION Upon receiving the...

Страница 7: ...condenser blower assembly motor mounting hardware pulley belt blower shaft blower bearings and blower wheel for proper tightness 3 Close and lock all panel doors Electrical Connection Refer to the uni...

Страница 8: ...anel Figure 2 f At this point TURN OFF POWER to the unit at the main power source g If the Red OPI light is illuminated switch any two leads of the three main power wires connected from the main power...

Страница 9: ...to a suitable drainage point such as a storm drain using a hose The hose must still have a form of trap to allow the water to drain Fill the trap with water before operation to form a seal Or 2 Draint...

Страница 10: ...Temperature AIR IN is greater than the Thermostat setting sensed by the thermostats temperature measuring bulb the compressor contactor CCR will energize the Compressor CR and the Amber Cool Indicato...

Страница 11: ...n REMOTE THERMOSTAT CONTROL RTC OPTION These units are pre wired for this specific option If remote thermostat control is desired contact your representatives at 800 367 8675 1 When the remote thermos...

Страница 12: ...t s circuit breaker Remove the Access Panel to the Compressor Compartment and locate the Manual Reset High Pressure Switch Press the button downward to verify if the switch tripped If the button click...

Страница 13: ...to the unit At this point the unit will not start in any mode Swapping any two leads of the incoming line voltage at the power connection block on the PAC12 unit will correct the phasing to the unit T...

Страница 14: ...the space being conditioned the compressor system s head pressure starts to fall As the compressor s refrigerant discharge pressure starts to fall below 290 psig the valve mechanically modulates open...

Страница 15: ...once each month when the system is in constant operation If the unit is equipped with disposable type air filters replace them with the same type and size NOTE Do not attempt to clean disposable air f...

Страница 16: ...ves the frequency of lubrication based upon operational duty and should be used as a guide for determining when bearings should be lubricated Duty Grease Interval Low Usage Periodic Continuous 12 mont...

Страница 17: ...33 1 2 57 7 8 36 9 16 60 15 16 39 5 8 63 1 Check the sheave alignment to make sure that the sheave faces are in the same plane Check this by placing a straight edge across the face of the sheaves Any...

Страница 18: ...start 7 Compression pressures almost equalized 8 Condenser motor tripped on overload may have also caused high pressure trip 1 Clean or replace air filters in front of evaporator coil 2 Reset thermos...

Страница 19: ...e locate objects in front of air grills or re locate supply and return air grills in space 2 Clean or replace air filter 3 Replace low pressure switch 4 Replace evaporator blower motor 5 Replace defec...

Отзывы: