17
5. Input Wiring Connection (Optional Hardwire Connection)
1. Choose the appropriate conduit in accordance with all applicable, local, and electrical
safety codes and standards.
2. Using the appropriate tool, clamp the ring wire terminal to the copper wire. For non-
insulated terminals, use heat shrink tube to cover the non-insulated portion of the
terminal. Choose a terminal ring with the following characteristics:
»
Recommended Wire Strip length: 8mm (0.32in)
»
Width of the terminal block opening: 10.2mm (0.41in)
3. Remove the front cover by removing the 4 screws at each corner of the charging station.
For more information on how to remove the front cover refer to Chapter 3.1 Adjust
Maximum Current Output on page 10.
4. With the front cover placed to the side, use Philips screwdriver to release terminal screws
of the input cable. Loosen the Strain Relief Fitting for the 6-50 or 14-50 Plug and Remove
the Plug. Remove the Strain Relief connector.
5. Insert the wire end passing through the conduit and insert them into the input wiring hole.
(Use Red wire for L1, Black wire for L2, Green wire for G). Attach the copper wire on the
corresponding terminal block. Use the following wire and torque force when connecting to
input terminal block.