INSTALLATION – CONTROL BEFORE CONNECTION
Before connection, please consult the following element:
BATTERY
Unisolar has an automatic voltage detection. For its correct functioning, please check:
- If the battery voltage is higher than 6V (required voltage for the startup of the solar charge controller)
- For 24V batteries, that the voltage is not lower than 18V.
For flooded batteries, check the electrolyte level. If necessary, complete before charging.
For coupling, proceed as follows:
IN SERIES IN PARALLEL
IN SERIES AND IN PARALLEL
Tips :
In case of parallel
connection,
favour
diagonal wiring for a
standardization of the
charge/discharge
Do
not
couple
batteries
with
different capacities,
different
age
or
different technologies
Prefer a high-capacity
battery to 2 small
connected in parallel, for
equal capacity
PHOTOVOLTAIC PANEL
Check that the photovoltaic panel’s power does not exceed the power rating of the solar charge controller.
Do not connect solar panels whose voltage is higher than 50V.
ELECTRICAL CONSUMERS
Before connecting your consumers to the solar charge controller and to prevent the solar charge controller
switching into overload protection, check that the consumers do not exceed the Unisolar’s power rating
(See 12V/24V controlled output part for more details).