Unitary products group PM9 UP Series Скачать руководство пользователя страница 6

292453-UUM-A-0108

6

Unitary Products Group

NORMAL OPERATION SEQUENCE

The furnace control calculates the optimum firing rate each time the wall
thermostat R and W contacts close or open (at the beginning and at the
end of each call for heat) based on information from the thermostat and
past demand. UNLIKE CONVENTIONAL SYSTEMS, THE WALL
THERMOSTAT DOES NOT SIMPLY TURN THE FURNACE ON AND
OFF. THE FURNACE CONTROL CALCULATES THE DEMAND AND
MAY CONTINUE TO FIRE THE FURNACE DURING PORTIONS OF
THE THERMOSTAT "OFF" CYCLE. 

When the wall thermostat R and W contacts close, indicating a call for
heat, the following sequence occurs:

1.

The inducer is energized and ramps up its speed until airflow is
proven by the pressure switch and by the pressure sensor on the
control board.

2.

The hot surface ignitor is energized.

3.

After a 17-20 second igniter heatup, the gas valve opens and the
burners light.

4.

When the control senses that flame is present, the circulating
blower starts at low speed.

5.

The furnace fires at 70% of full rate for 30-45 seconds, then drops
to the minimum (35%) firing rate.

6.

The firing rate is automatically adjusted to meet demand, increas-
ing gradually to maximum (100%) firing rate if the thermostat is not
satisfied within a defined time.

7.

When the thermostat R and W contacts open (thermostat is satis-
fied) the furnace control recalculates the demand and a new firing
rate. 

a.

If demand exceeds the minimum firing rate, the burners will
continue to fire at a recalculated reduced firing rate, decreas-
ing if the thermostat remains off for a defined time. 

b.

If demand does not exceed the minimum firing rate, the burn-
ers will shut off immediately. 

8.

After the burners shut off, the circulating blower will continue to run
until the temperature sensor detects that the supply air tempera-
ture has dropped to the desired level, which should take from 30 to
90 seconds.

ADJUSTMENT OF FAN CONTROL SETTINGS

Cooling - 

The airflow delivered by the furnace during cooling operation

can be adjusted to match the cooling capacity of the A/C condensing
unit. This is done by moving the COOL jumper on the control board to
give the desired airflow. 

Do not move the motor wires to different positions on the
furnace control board!

 

The jumper has four positions, which will deliver sufficient airflow in
cooling mode for the cooling capacities shown in the table below. The
CFM delivery on each jumper position is shown in Table 14.

Continuous Fan Operation - 

The airflow delivered by the furnace dur-

ing continuous fan operation can be adjusted as desired. This is done
my moving the FAN jumper on the control board to give the desired air-
flow. 

Do not move the motor wires to different positions on the
furnace control board!

 

The jumper has three positions. The "A" position delivers maximum air-
flow, 100% of the blower capacity. Position "B" delivers approximately
70% of the blower capacity. And Position "C" delivers minimum airflow,
approximately 40% of the blower capacity. 

Hot Surface Ignition System

TROUBLESHOOTING

The following visual checks should be made before troubleshooting:

1.

Check to see that the power to the furnace and the ignition control
module is ON.

2.

The manual shut-off valves in the gas line to the furnace must be
open.

3.

Make sure all wiring connections are secure.

4.

Review the sequence of operation. Start the system by setting the
thermostat above the room temperature. Observe the system’s
response. Then use the troubleshooting section in this manual to
check the system’s operation.

TABLE 2: 

Cooling Airflow - A/C Capacity in Tons

Models

Jumper Position

D

C

B

A

60/1200

1-1/2

2

2-1/2

3

80/1200

1-1/2

2

2-1/2

3

80/1600

2-1/2

3

3-1/2

4

100/1600

2-1/2

3

3-1/2

4

100/2000

3

3-1/2

4

5

120/2000

3

3-1/2

4

5

 FIGURE 6:  

Furnace Control Board

HOT SURFACE IGNITION SYSTEM
Do not attempt to light this furnace by hand (with a
match or any other means). There may be a potential
shock hazard from the components of the hot surface
ignition system. The furnace can only be lit automatically
by its hot surface ignition system.

Never bypass any safety control to allow furnace opera-
tion. To do so will allow furnace to operate under poten-
tially hazardous conditions.
Do not try to repair controls. Replace defective controls
with UPG Source 1 Parts.
Never adjust pressure switch to allow furnace operation.

ERROR

TEST

A

B

C

BLOWER

D’AUX

LOW VOLTAGE
TERMINALS

DIAGNOSTIC
LIGHT

TEST
BUTTON

LAST ERROR
BUTTON

CONTINUOUS
FAN SPEED
JUMPER

COOLING
SPEED JUMPER

HUMIDIFIER
TERMINALS

EAC
TERMINALS

Содержание PM9 UP Series

Страница 1: ...have been wet or the furnace if deemed necessary FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damage Do not store or use gasoline...

Страница 2: ...e casing making sure the physical support is sound without sagging cracks or gaps Examine the furnace base making sure it is physically sound without cracks gaps or sagging and has a good seal 5 Exami...

Страница 3: ...o the appliance 4 Remove burner door 5 Move gas control switch to the OFF position Do not force See Figure 4 6 Wait five 5 minutes to clear out any gas If you then smell gas STOP Follow B in the safet...

Страница 4: ...mended filter size from Table 1 Replacing Filters Filters used with this furnace must be installed external to the furnace casing DO NOT attempt to install filters inside the furnace cabinet Some inst...

Страница 5: ...order Cleaning the Heat Exchanger 1 Turn off the electrical power to the unit 2 Turn off the gas supply at the external manual shut off valve and loosen the ground union joint 3 Remove the burner doo...

Страница 6: ...Do not move the motor wires to different positions on the furnace control board The jumper has four positions which will deliver sufficient airflow in cooling mode for the cooling capacities shown in...

Страница 7: ...use on the con trol board Five Red Flashes Rollout switch or auxiliary limit switch open Check the rollout switch on the side of the burner box It is a manual reset switch To reset push the small butt...

Страница 8: ...Products Group SECTION III REPLACEMENT PARTS LIST 53 27 28 37 33 30 7 10 11 12 57 2 5 13 18 26 31 62 60 63 64 41 2 3 1 4 16 15 19 21 22 23 23 44 45 46 47 48 50 52 55 26 14 71 57 6 8 36 9 39 20 24 29 3...

Страница 9: ...R 35 PLATE DIFFUSER 36 BRACKET IGNITER 37 WRAPPER INSULATED 38 ITEM DESCRIPTION MISCELLANEOUS 39 PLUG WINDOW CLEAR 1 5 40 CONNECTOR AIR INTAKE 2 41 HOSE ASSEMBLY VACUM 2 Req d 42 TUBING PREFORMED 43 G...

Страница 10: ...1BR0117 BOTTOM RETURN FILTER KIT 1 FILTER 17 1 2 CABINETS 1BR0217 BOTTOM RETURN FILTER KIT 1 4 FILTER 17 1 2 CABINETS 1BR0121 BOTTOM RETURN FILTER KIT 1 FILTER 21 CABINETS 1BR0221 BOTTOM RETURN FILTER...

Страница 11: ...292453 UUM A 0108 Unitary Products Group 11 SECTION IV WIRING DIAGRAM FIGURE 7 Wiring Diagram...

Страница 12: ...products installed in the United States and Canada EXCLUSIONS This warranty does not cover any 1 Shipping labor or material charges 2 Damages resulting from transportation installation or servicing 3...

Отзывы: