background image

035-14511-000 REV B (1299)

Unitary Products Group

11

® 

Two Stage Furnaces - The ideal fan setting is to set the high
speed (second stage) air flow at the fan motor high speed
and the low speed (first stage) airflow at the fan low speed. If
the low speed air flow is too high, unsatisfactory dehumidifac-
tion may occur on first stage operation. To correct for unsatis-
factory dehumidification, either add a dehumidistat per figure
10 or change the blower motor for better air flow perfor-
mance.

SYSTEM START-UP

ENERGIZE CRANKCASE HEATER

This unit is equipped with a crankcase heater for the compressor.

A warning label with an adhesive back is supplied in the unit
installation instruction packet. This label should be attached
to the field supplied disconnect switch where it will be easily
seen. See below.

In order to energize the crankcase heater:- Set indoor two
stage cooling thermostat to “OFF” position.- Close the line
power disconnect to the unit.

CHECKING SYSTEM CHARGE

The factory charge listed in the tabular data sheet and unit
nameplate data is for the smallest matching indoor coil and
15 feet of line set. The tabular data sheet also lists the addi-
tional charge for other matching indoor coils and the addi-
tional charge for longer line sets.

The H*TS condensing unit must only be used with the match-
ing thermostatic expansion valve kit listed in the tabular data
sheet. The best way to check the system charge is by checking
the system subcooling during the second stage of operation.

SERVICING AND VERIFY:

For 2nd stage (2 cylinder) operation, the recommended sub-
cooling for H*TS036 is 14°F and 20°F for all other models.
For 1st stage (1 cylinder) operation, the recommended sub-
cooling is 10F for all models.

1.

Set the system running in the second stage (2 cylinder
operation) by setting the thermostat at least 6°F below
the room temperature. Short the “TEST” pin to bypass
the 5 minute anti-short cycle timer if necessary.

2.

Operate the system for a minimum of 15 to 20 minutes.

3.

Refer to the tabular data sheet for the recommended air-
flow and verify this indoor air flow (it should be about 400
SCFM per ton)

4.

Measure the liquid refrigerant pressure P and tempera-
ture T at the service valve.

5.

Calculate the saturated liquid temperature ST from Table
1.

6.

Subcooling temperature TC = Saturated Temperature ST
- Liquid temp T

The recommended subcooling level should be about 14+/-3°F
for H*TS036 and 20+/-3°F for all other models. Add charge if
the calculated subcooling temperature TC in step 6 is lower
than the recommended level. Remove and recover the refrig-
erant if the subcooling TS are higher than the recommended
level.

IMPORTANT

An attempt to start the compressor without at least 8

hours of crankcase heat will damage the compressor.

It is unlawful to knowingly vent, release or discharge
refrigerant into the open air. It is necessary to recover
the refrigerant during any repair or installation of the
system.

WARNI

Refrigerant charging should only be carried out by a
qualified air conditioning contractor.

Example: The pressure P and temperature T measured at
the H*TS024 service port is 220 Psig and 95°F. From Table
1, page 12, the saturated temperature for 220 Psig is 108.
The subcooling temperature TC = 108 - 95 = 13°F.

CAUTIO

Содержание H4TS024

Страница 1: ...WIRING 8 THERMOSTAT MOUNTING WIRING 8 DE HUMIDIFICATION CONTROL 8 CONTROL WIRING 8 WIRING DIAGRAMS 9 10 INDOOR BLOWER SPEED SETTINGS 8 SYSTEM START UP 11 ENERGIZE CRANKCASE HEATER 11 CHECKING SYSTEM...

Страница 2: ...erly INSPECTION As soon as a unit is received it should be inspected for possi ble damage during transit If damage is evident the extent of the damage should be noted on the carrier s freight bill A s...

Страница 3: ...jectionable if the unit is placed directly under windows of certain rooms bed rooms study etc ROOF INSTALLATION When installing units on a roof the structure must be capable of supporting the total we...

Страница 4: ...7 Install TXV equalizer line in 1 8 hole previously made in vapor line Equalizer line can be bottomed out in vapor line as end of equalizer line is cut on 45 degrees angle to prevent blockage Braze e...

Страница 5: ...ter 3 Care must also be taken to isolate the refrigerant lines to minimize noise transmission from the equipment to the structure 4 The vapor line must be insulated with a minimum of 1 2 foam rubber i...

Страница 6: ...d line to the evaporator liquid connection The nitrogen shouldnowbeflowing throughtheevaporator coil 5 Slide the grommet away from the vapor connection at the coil Braze the vapor line to the evaporat...

Страница 7: ...supply to be sure that it meets the values specified on the unit nameplate and wiring label Power wiring control low voltage wiring disconnect switches and over current protection to be supplied by t...

Страница 8: ...RING The recommended field connections for specific indoor air handlers and furnaces are shown in Figures 7 through 10 All connects to the outdoor unit are made in the low voltage junc tion box in the...

Страница 9: ...H I S W I R E I F N O T U S E D 2 T H E R M O S T A T T S C O N T R O L G R D L U G 2 H U M I D I S T A T M A K E S C I R C U I T O N H U M I D I T Y F A L L J U M P E R O N C F M S E L E C T I O N B...

Страница 10: ...I R I N G 2 0 8 2 3 0 1 6 0 C O N T A C T O R M 1 T 1 L 1 L 2 T 2 P O W E R C O N T R O L F A C T O R Y C L A S S 2 W I R I N G C L A S S 1 W I R I N G H I G H L O W 2 D E H U M I D I S T A T M A K E...

Страница 11: ...age 2 cylinder operation the recommended sub cooling for H TS036 is 14 F and 20 F for all other models For 1st stage 1 cylinder operation the recommended sub cooling is 10F for all models 1 Set the sy...

Страница 12: ...ar single speed compressor system This additional run time provides for better dehumidification and consistent room temperatures However there may be installation environ ments that the humidity level...

Страница 13: ...y may be by passed by momentarily jumping the two test pins when there is a call for cooling Y1 or Y2 Pressure Switch Operation The condensing unit is provided with high and low pressure switches inst...

Страница 14: ...to be driven out of the compressor The installer should also instruct the owner on proper opera tion and maintenance of all other system components INDICATIONS OF PROPER OPERATION Cooling operation i...

Страница 15: ...035 14511 000REVB 1299 Unitary Products Group 15 NOTES...

Страница 16: ...o n d i t i o n i n g Unitary Products Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by Unitary Products Group 1999 All rights reserved Super...

Отзывы: