background image

166753-UIM-C-0706

EFFICIENCY
RATING
CERTIFIED

ISO 9001

Certified Quality

Management System

HIGH EFFICIENCY

TUBULAR HEAT EXCHANGER SERIES

MODELS:  GY8S*UH / GM8S*UH / GR8S*UH / LY8S*UH / LM8S*UH / LF8*UH

(Single Stage Upflow / Horizontal / Low NOx)

40 - 130 MBH INPUT
(11.72 - 38.10 KW) INPUT

INSTALLATION MANUAL

INSTALLATION MANUAL

INSTALLATION MANUAL

INSTALLATION MANUAL

SECTION I: SAFETY

SECTION I: SAFETY

SECTION I: SAFETY

SECTION I: SAFETY

This  is  a  safety  alert  symbol.  When  you  see  this  symbol  on
labels  or  in  manuals,  be  alert  to  the  potential  for  personal
injury.

Understand and pay particular attention to the signal words 

DANGER

,

WARNING

, or 

CAUTION

DANGER 

indicates  an 

imminently

  hazardous  situation,  which,  if  not

avoided, 

will result in death or serious injury

.

WARNING 

indicates  a 

potentially

  hazardous  situation,  which,  if  not

avoided, 

could result in death or serious injury

.

CAUTION 

indicates  a  potentially  hazardous  situation,  which,  if  not

avoided 

may  result  in  minor  or  moderate  injury.

  It  is  also  used  to

alert against unsafe practices and hazards involving only property dam-
age.

Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper  installation,  adjustment,  alteration,  service  or  mainte-
nance  can  cause  injury  or  property  damage.  Refer  to  this  manual
for assistance or for additional information, consult a qualified con-
tractor, installer or service agency.

This product must be installed in strict compliance with the installa-
tion instructions and any applicable local, state, and national codes
including,  but  not  limited  to  building,  electrical,  and  mechanical
codes.

LIST OF SECTIONS

SAFETY  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
DUCTWORK   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
FILTERS   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
GAS PIPING   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
ELECTRICAL POWER   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

TWINNING AND STAGING  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
VENT SYSTEM   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
SAFETY CONTROLS   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
START-UP AND ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . .20
WIRING DIAGRAM   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SAFETY 1

LIST OF FIGURES

Dimensions   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Typical Attic Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Typical Suspended Furnace / Crawl Space Installation  . . . . . . . . . . . . 7
Side Return Cutout Markings  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Gas Valve - All Except GR Models   . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Gas Valve - GR Models Only  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Upflow Gas Piping  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Horizontal Gas Piping   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Electrical Wiring  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Thermostat Chart  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Accessory Connections  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Typical Twinned Furnace Application   . . . . . . . . . . . . . . . . . . . . . . . . 12
Single Stage Twinning Wiring Diagram  . . . . . . . . . . . . . . . . . . . . . . . 13
Two-Stage Twinning Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . 13
Vent Termination   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Vent Termination   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Typical Sidewall Vent Application   . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Typical Sidewall Vent and Termination Configuration   . . . . . . . . . . . .15
Home Layout   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Combustion Airflow Path Through The Furnace 
Casing to the Burner Box  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Alternate Air Intake, Air Outlet and Chimney Connections  . . . . . . . . .17
Air Inlet, Outlet and Chimney Connections . . . . . . . . . . . . . . . . . . . . .17
Typical Chimney Connections   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Horizontal Air Inlet, Outlet and Chimney Connections  . . . . . . . . . . . .18
Outside and Ambient Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . .18
Pressure Switch Tubing Routing   . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Gas Valve  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Gas Valve - GR Models Only  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Reading Gas Pressure  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Typical Heat/Cool Speed Tap Connections  . . . . . . . . . . . . . . . . . . . .24
Wiring Diagram  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28

LIST OF TABLES

Unit Clearances to Combustibles  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Minimum Duct Sizing For Proper Airflow  . . . . . . . . . . . . . . . . . . . . . . . 4
Round Duct Size   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Cabinet and Duct Dimensions  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Filter Sizes  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Nominal Manifold Pressure - High Fire   . . . . . . . . . . . . . . . . . . . . . . . . 9
Ratings & Physical / Electrical Data - Upflow Models   . . . . . . . . . . . . . 9
Roof Pitch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Estimated Free Area   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Free Area  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Unconfined Space Minimum Area in Square Inch   . . . . . . . . . . . . . . .18
Inlet Gas Pressure Range   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Nominal Manifold Pressure - All Except GR Models   . . . . . . . . . . . . .22
Nominal Manifold Pressure - GR Models  . . . . . . . . . . . . . . . . . . . . . .23
Filter Performance - Pressure Drop Inches W.C. and (kPa) . . . . . . . .24
Field Installed Accessories - Non Electrical  . . . . . . . . . . . . . . . . . . . .25
Blower Performance CFM - Upflow/Horizontal (without filter) - 
Bottom Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Blower Performance CFM - Upflow/Horizontal (without filter) - 
Left Side Return  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27

Содержание GM8S*UH

Страница 1: ...IPING 8 ELECTRICAL POWER 9 TWINNING AND STAGING 12 VENT SYSTEM 14 SAFETY CONTROLS 19 START UP AND ADJUSTMENTS 20 WIRING DIAGRAM SAFETY 1 LIST OF FIGURES Dimensions 5 Typical Attic Installation 6 Typic...

Страница 2: ...to be sure that the elec trical characteristics match All models use nominal 115 VAC 1 Phase 60 Hertz power supply DO NOT CONNECT THIS APPLI ANCE TO A 50 HZ POWER SUPPLY OR A VOLTAGE ABOVE 130 VOLTS...

Страница 3: ...earances shall take precedence over clear ances for combustible materials where accessibility clearances are greater Installation in a residential garage A gas fired furnace for installation in a resi...

Страница 4: ...y subtracting the Return Air Temperature Reading from the Supply Air Temperature Read ing 2 The External Static Pressure is determined by adding the Supply Duct Static Pressure reading to the Return D...

Страница 5: ...as orifice and or a faulty limit switch can cause the furnace to operate above the maximum supply air temperature Refer to sections II III and IX for additional informa tion on correcting the problem...

Страница 6: ...with the air conditioning coil for additional information Horizontal Installations Without a Cooling Coil Cabinet When installing this appliance the furnace must be installed so as to create a closed...

Страница 7: ...lter rack following the instructions provided with that accessory If a filter s is provided at another location in the return air system the ductwork may be directly attached to the furnace side panel...

Страница 8: ...factory for natural gas fired operation at 0 8 000 feet 0 m 2 438 m above sea level The manifold pressure must be changed in order to manitain proper and safe operation when the furnace is installed...

Страница 9: ...y using factory specified and or approved parts must perform the conversion The installer must take every precaution to insure that the furnace has been converted to the proper gas orifice size when t...

Страница 10: ...cut wire tie holding excess wiring Reposition on the left side of the furnace and fas ten using holes provided LOW VOLTAGE CONTROL WIRING CONNECTIONS LOW VOLTAGE CONTROL WIRING CONNECTIONS LOW VOLTAG...

Страница 11: ...mon C 24 Volt Common Optional w Batteries BN11C01124 DP11C40124 PSC FURNACE CONTROL SINGLE STAGE AIR CONDITIONING BN11C00124 BP11C50124 PP11C70224 THERMOSTAT THERMOSTAT THERMOSTAT HP1 W 031 01975 Seri...

Страница 12: ...s Separate plenums and supply ducts systems cannot be utilized A sin gle return air plenum common to both furnaces must be used It is sug gested that a return platform be utilized with bottom air entr...

Страница 13: ...single two stage furnace This allows only one furnace to supply heat during times when the heat output from one furnace is sufficient to satisfy the demand When one duct system is used for two furnac...

Страница 14: ...es the maximum allowable vent pipe length the furnace must be converted for high altitude operation Refer to SECTION IV GAS PIP ING of these instructions and the proper high altitude application instr...

Страница 15: ...to the proper length beginning at the furnace 2 Deburr the piping inside and outside 3 Dry fit the vent piping assembly from the furnace to the termination checking for proper fit support and slope Pi...

Страница 16: ...ionable 6 Horizontal portions of the vent system must slope upwards and be supported to prevent sagging The vent system may be supported by the use of clamps or hangers secured to a permanent part of...

Страница 17: ...d for use 4 A automatically operated damper or automatically adjustable lou vers shall be interlocked so that the main burner cannot operate unless either the damper or the louver is in the fully open...

Страница 18: ...izontally from the burner level of the appliance Refer to AIR SOURCE FROM OUTDOORS AND VENT AND SUPPLY AIR SAFETY CHECK in these instructions for additional information and safety check procedure 2 Th...

Страница 19: ...tion Corrective action is required These are manual reset controls that must be reset before operation can continue PRESSURE SWITCHES PRESSURE SWITCHES PRESSURE SWITCHES PRESSURE SWITCHES This furnace...

Страница 20: ...g 1 5 16 0 8 cm tee 1 5 16 0 8 cm x 1 8 3 175 mm reducing coupling 1 1 8 0 3 cm adapter There is a accessory kit 1PK0602 available from Source 1 which has the following items 12 30 cm length x 1 8 0 3...

Страница 21: ...er times a barometric pressure and temperature correction factor of 0 960 times 3600 then divided by the time it took to measure 2 cubic ft 0 0566 m3 of gas from the gas meter For Propane LP Gas multi...

Страница 22: ...ure 30 for connection details IMPORTANT The cap for the pressure regulator must be removed entirely to gain access to the adjustment screw Loosening or tightening the cap does not adjust the flow of g...

Страница 23: ...sure regulator adjustment cap and adjustment screws on main gas valve 7 After the manifold pressure has been adjusted re calculate the furnace input to make sure you have not exceeded the specified in...

Страница 24: ...ter pressure drop values in Table 15 are typical values for the type of filter listed and should only be used as a guideline Actual pres sure drop ratings for each filter type vary between filter manu...

Страница 25: ...is 0 58 w c To determine the system airflow complete the following steps Obtain the airflow values at 0 50 w c 125 Pa 0 60 w c 150 Pa ESP Airflow 0 50 1250 CFM 35 4 m3 min Airflow 0 60 1180 CFM 33 4...

Страница 26: ...35 7 Medium Low 1720 1700 1670 1620 1570 1500 1430 1310 1160 1000 48 7 48 1 47 3 45 9 44 5 42 5 40 5 37 1 32 8 28 3 Low 1410 1390 1360 1330 1280 1220 1170 1060 930 840 39 9 39 4 38 5 37 7 36 2 34 5 33...

Страница 27: ...030 1980 1910 1850 1710 1570 1300 59 7 59 7 58 6 57 5 56 1 54 1 52 4 48 4 44 5 36 8 Medium Low 1690 1690 1650 1610 1540 1480 1410 1280 1170 1030 47 9 47 9 46 7 45 6 43 6 41 9 39 9 36 2 33 1 29 2 Low 1...

Страница 28: ...opyright by York International Corp 2006 All rights reserved Supersedes 166753 UIM B 0306 Unitary 5005 Norman Product York OK Group Drive 73069 SECTION X WIRING DIAGRAM SECTION X WIRING DIAGRAM SECTIO...