background image

035-18549-000-B-0402

Unitary Products Group

11

Oil return will be critical during:

1.

The cooling cycle when the outdoor unit is above
the indoor unit (detail 1 of Figure 5).

2.

The heating cycle when the indoor unit is above
the outdoor unit (detail 4 of Figure 5).

When the indoor unit is above the outdoor unit, the size
of the vapor riser must be reduced to 1-1/8" OD so that
the velocity of the refrigerant will be great enough to
carry oil up the riser during the heating cycle.

When 1-1/8" OD tubing must be used for the riser, the
maximum length for the vapor line will be greatly
reduced as shown in the following examples.

EXAMPLES:

#1 - 10 Ton System
89 feet of 1-3/8" OD, type “L” copper tubing

(89 feet x 2.8 psi/100 feet) . . . . . . . . . . . . . . . . .2.5 psi

Fitting* . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.5 psi

Vapor Line Pressure Drop = 3.0 psi

#2 - 10 Ton System
29 feet of 1-1/8" OD, type “L” copper tubing (vertical)

(29 feet x 8.0 psi/100 feet) . . . . . . . . . . . . . . . . .2.3 psi

7 feet of 1-3/8" OD, type “L” copper tubing (horizontal)

(7 feet x 2.8 psi/100 feet) . . . . . . . . . . . . . . . . . .0.2 psi

Fitting* . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.5 psi

Vapor Line Pressure Drop = 3.0 psi

*Determine the pressure drop of the fittings for each installation - DO NOT use
the estimated values as shown in the above examples.

Although longer vapor lines are permissible, friction
losses exceeding 3 psi (2°F) will reduce system capac-
ity in both the cooling and heating cycles.

SERVICE VALVES

These outdoor units have both vapor and liquid line
service valves.

Both valves are shipped from the factory front-seated
and closed with the valve stem in the maximum clock-
wise position.

These service valves are the back-seating type and
have a 1/4" male flare access port for evacuating and
charging the system.

Shrader access valves are provided on the compressor
vapor and discharge lines for pressure checking the
system.

All access ports are sealed with a removable cap.
Never remove a cap unless the valve is fully back-
seated with its valve stem in the maximum counter-
clockwise position because the refrigerant charge will
be lost.

EXTENDING THE SERVICE PORTS

Refer to Fig.6:

1.

Loosen the screws securing the service ports in
shipping position. (See FIG 6).

2.

Push the service ports through the corner post.

3.

Tighten the screws to secure the service ports for
installation.

INSTALLATION

Since the condensing units are shipped with a holding
charge of refrigerant-22, they can be checked for a
refrigerant leak by depressing the stem on either of the
service ports that extend through the cabinet. As soon
as some internal pressure is relieved release the stem.
DO NOT release the entire holding charge.

TABLE 5: VAPOR LINES

System

Model

Refrigerant

Flow Rate,

1

(Lbs/Min)

1.

Based on Refrigerant-22 at the nominal cooling capacity of the system, a
vapor temperature of 40ºF and a liquid temperature of 105ºF. Since refriger-
ant flow rates will be a little lower at the nominal heating capacity of each sys-
tem, vapor line friction loss should always be based on cooling operation.

Type “L”

Copper Tubing

(In. OD)

Friction

Loss, 2,3

(PSI/100 Ft.)

2.

Although vapor lines should be sized for a friction loss equivalent to a 2ºF
change in saturation temperature (or approximately 3 psi), sizing the lines for
the proper return of oil is more important.

3.

These friction losses do not include any allowance for fittings. Only use a
1-1/8” riser when the indoor unit is above the outdoor unit.

EA120/FA120

30.0

1-1/8

4.7

1-3/8

1.6

TABLE 6: REFRIGERANT LINE CHARGE

1

1.

Charges are based on 40ºF suction temperature and 105ºF liquid tempera-
ture.

Refrigerant

Line

2

2.

Type “L” copper tubing.

Line Size,

OD (In.)

Refrigerant Charge

(Lb/Ft)

Liquid

3/4

0.113

Vapor

1-1/8

0.013

1-3/8

Содержание EA120

Страница 1: ...YOU START TO INSTALL YOUR UNIT SAVE THIS MANUAL SPLIT SYSTEM HEAT PUMPS OUTDOOR UNITS MODEL EA120 035 18549 000 B 0402 CONTENTS GENERAL INFORMATION 3 INSTALLATION 5 OPERATION 17 START UP 20 MAINTENAN...

Страница 2: ...UENCE OF OPERATION 17 Cooling Operation 17 Heating Operation 18 Defrost Cycle 18 Operation Below 0 F 19 Emergency Heat Operation 19 START UP CRANKCASE HEATER 20 PRE START CHECK 20 INITIAL START UP 20...

Страница 3: ...8475 000 All accessories come with a separate installation man ual Refer to Parts Manual for complete listing of replacement parts on this equipment The above forms may be ordered from Standard Regist...

Страница 4: ...andard Efficiency 4 Pipe 120 Nominal Cooling Capacity MBH 090 7 1 2 Ton 120 10 Ton 150 12 1 2 Ton 180 15 Ton 240 20 Ton 300 25 Ton 360 30 Ton 480 40 Ton 600 50 Ton C Heat Type C Cooling Only 00 Nomina...

Страница 5: ...rt the unit The unit must be mounted on solid level supports The supports can be channel iron beams or wooden beams treated to reduce deterioration A minimum of two 2 beams are required to support eac...

Страница 6: ...he top of the unit is less than 5 feet See Figure 2 BEFORE LIFTING A UNIT MAKE SURE THAT ITS WEIGHT IS DISTRIBUTED EQUALLY ON THE STRAPS SO THAT IT WILL LIFT EVENLY Units may also be moved or lifted w...

Страница 7: ...st be suitable for an outdoor location Although it should be installed near the unit do NOT secure it to the unit cabinet Refer to Figure 3 for typical field wiring CONTROL WIRING Refer to Figure 4 fo...

Страница 8: ...ld become excessive and result in malfunctioning of the unit controls REFRIGERANT PIPING GENERAL GUIDELINES Many service problems can be avoided by taking ade quate precautions to provide an internall...

Страница 9: ...d 0 FIGURE 4 UNIT DIMENSIONS AND CLEARANCES AIR OUT AIR IN AIR OUT 2 3 4 32 2 1 4 32 1 2 70 1 2 8 3 4 5 3 8 CONTROL BOX ACCESS SERVICE PORT LOCATION 39 1 1 8 OD 10 TON 1 3 8 OD 12 1 2 TON SUCTION LINE...

Страница 10: ...flashing will not only cause erratic valve operation and poor system performance but could also damage the expansion valve Total pressure loss includes the static head loss explained above plus the fr...

Страница 11: ...por and discharge lines for pressure checking the system All access ports are sealed with a removable cap Never remove a cap unless the valve is fully back seated with its valve stem in the maximum co...

Страница 12: ...ended period of time it should be cleaned before being used The liquid line connections can now be brazed while maintaining a minimum flow of dry nitrogen through the piping NOTE A filter drier is fac...

Страница 13: ...ough the access port of the vapor line service valve and the hole in the vapor disc 5 After the disc has been removed burnish the exter nal surfaces and clean the internal surfaces of the vapor connec...

Страница 14: ...of the condenser air if necessary to assure a head pressure of 280 psig during the charging procedure NOTE The installer should return to the job to verify the operating charge when the ambient tem p...

Страница 15: ...035 18549 000 B 0402 Unitary Products Group 15 FIGURE 7 REFRIGERANT FLOW DIAGRAM...

Страница 16: ...16 Unitary Products Group FIGURE 8 CHARGING CURVE EA120 EA120 Charge Curve 170 190 210 230 250 270 290 310 330 65 70 75 80 85 90 Suction Pressure Discharge Pressure 115 Ambient 105 Ambient 95 Ambient...

Страница 17: ...rs 4 Relay RY1 also prevents the 10KW portion of accessory electric heat referenced as standby electric heat from being utilized whenever the com pressor is in operation This part of the circuit is co...

Страница 18: ...int on the thermostat below the temperature in the conditioned space and then returning it to its original setting c Opening and closing the power supply main dis connect switch IN ALL THREE RESET MET...

Страница 19: ...by the second stage TH2 of the room ther mostat same as described under Item 8 of HEATING OPERATION 2 The indoor section blower operation will be con trolled by the first stage heating TH1 of the room...

Страница 20: ...t lines will be hot during the HEAT and COOL cycles Only two lines will remain cool for all cycles the line between the compressor and the accumulator and the line between the accumulator and the reve...

Страница 21: ...lded closed 3 Every compressor is protected by crankcase heat ers to prevent refrigerant from accumulating in the crankcases of the compressor during an OFF cycle 4 Outdoor fan motors and the secondar...

Страница 22: ...The outdoor fan motors are equipped with factory lubri cated and sealed ball bearings They do not require any maintenance REPLACEMENT PARTS Contact your local UPG Distribution Center for replace ment...

Страница 23: ...035 18549 000 B 0402 Unitary Products Group 23 NOTES...

Страница 24: ...hange without notice Printed in U S A 035 18549 000 B 0402 Copyright by Unitary Products Group 2002 All rights reserved Supersedes 035 18549 000 A 0102 Unitary 5005 Norman Products York OK Group Drive...

Отзывы: