175615-YIM-A-0306
46
Unitary Products Group
CHARGING THE UNIT
These units will be charged using the superheat
method. Superheat charging data is shown in Tables
34 and 35. When charging each system, superheat
data should be taken at the compressor inlet.
The DJ060 uses a TXV. Charge the unit to 12°F subcooling.
TABLE 34: DJ036 COOLING SUPERHEAT CHARGING TABLE
OUTDOOR TEMP
(°F)
SUPERHEAT AT COMPRESSOR SUCTION (°F)
AIRFLOW=1200 CFM
INDOOR WET BULB TEMPERATURE (°F)
55
57
59
61
63
65
67
69
71
73
75
65
32.2 32.6 33.0 33.4 33.8 34.2 34.6 35.4 36.3 36.7 37.1
70
23.3 24.7 26.1 27.5 28.9 30.3 31.7 32.8 33.9 34.5 35.0
75
14.3 16.8 19.2 21.6 24.0 26.4 28.8 30.2 31.6 32.3 32.9
80
5.4 8.8 12.2 15.7 19.1 22.5 25.9 27.6 29.2 30.0 30.9
85
-
-
5.3 9.7 14.2 18.6 23.0 24.9 26.8 27.8 28.8
90
-
-
-
7.6 11.2 14.7 18.3 21.1 23.9 25.4 26.8
95
-
-
-
5.5 8.1 10.8 13.5 17.3 21.0 22.9 24.8
100
-
-
-
-
6.3 8.3 10.3 14.0 17.8 19.7 21.6
105
-
-
-
-
-
5.7 7.0 10.8 14.6 16.5 18.4
110
-
-
-
-
-
-
-
7.6 11.4 13.3 15.2
115 -
-
-
-
-
-
-
-
8.2
10.1
12.0
TABLE 35: DJ048 COOLING SUPERHEAT CHARGING TABLE
OUTDOOR TEMP
(°F)
SUPERHEAT AT COMPRESSOR SUCTION (°F)
AIRFLOW=1600 CFM
INDOOR WET BULB TEMPERATURE (°F)
55
57
59
61
63
65
67
69
71
73
75
65
36.9 37.0 37.1 37.2 37.3 37.4 37.5 37.7 37.8 37.9 38.0
70
31.1 31.8 32.5 33.1 33.8 34.5 35.1 35.5 35.9 36.1 36.3
75
25.4 26.6 27.8 29.1 30.3 31.5 32.8 33.4 34.0 34.3 34.6
80
19.6 21.4 23.2 25.0 26.8 28.6 30.4 31.2 32.1 32.5 32.9
85
13.8 16.2 18.6 20.9 23.3 25.6 28.0 29.1 30.2 30.7 31.2
90
6.9 9.5 12.1 14.7 17.3 19.9 22.6 25.1 27.6 28.8 30.1
95
-
-
5.7 8.5 11.4 14.2 17.1 21.0 24.9 26.9 28.9
100
-
-
5.0 7.1 9.3 11.4 13.5 16.6 19.6 21.2 22.7
105
-
-
-
5.8 7.1 8.5 9.9 12.1 14.3 15.4 16.5
110
-
-
-
-
5.0 5.7 6.3 7.6 9.0 9.7 10.3
115
-
-
-
-
-
-
-
-
-
-
-
Содержание DJ 060