9

CHECKING SUPPLY AIR CFM

To check the supply air CFM after the initial balancing has been 
completed:

1.

Remove the two ¼ inch dot plugs in the duct panel. 

2.

Insert at least 8 inches of ¼ inch tubing into each of these 
holes for sufficient penetration into the airflow on both 
sides of the indoor coil.

3.

Using an inclined manometer, determine the pressure drop 
across the dry evaporator coil. Since the moisture on an 
evaporator coil may vary greatly, measuring the pressure 
drop across a wet coil under field conditions would be 
inaccurate. To ensure a dry coil, the compressors should 
be deactivated while the test is being run.

4.

Knowing the pressure drop across a dry coil, the actual 
CFM through the unit can be determined from the curve in 
Coil Delta P vs. Supply Air CFM figure.

After readings have been obtained, remove the tubes and 
reinstall the two ¼ inch plugs removed in Step 1.

NOTE: 

De-energize the compressors before taking any test
measurements to ensure a dry indoor coil.

FIGURE 3: COIL DELTA P VS AIRFLOW

Failure to properly adjust the total system air quantity 
can result in extensive system damage.

0

0.05

0.1

0.15

0.2

0.25

0.3

0.35

0.4

400

600

800

1000

1200

1400

1600

1800

2000

7RQ

'30&RLO'HOWD3YV¶$LUIORZ

7RQ

7RQ

7RQ

,'&RLO'HOWD3

$LUIORZ&)0

Содержание DAPM024

Страница 1: ...alert installer that personal injury and or equipment damage may result if installation procedure is not handled properly CAUTION READ ALL SAFETY GUIDES BEFORE YOU BEGIN TO INSTALL YOUR UNIT SAVE THIS...

Страница 2: ...ATURE UTILIZES A THERMAL EXPANSION VALVE 12 6 DAPM060 SUCTION PRESSURE TEMPERATURE UTILIZES A THERMAL EXPANSION VALVE 12 7 DIMENSIONS AND CLEARANCES 13 8 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPP...

Страница 3: ...information REFERENCE Additional information on the design installation operation and service of this equipment is available in the following reference forms 55 70 N1 General Installation 55 70 N2 Pre...

Страница 4: ...of unit to 1 8 maximum RIGGING OR HANDLING Care must be exercised when moving the unit Do not remove any packaging until the unit is near the place of installation Rig unit with slings placed under t...

Страница 5: ...ine NPTF to spill into an open drain SERVICE ACCESS Access to all serviceable components is provided by the following removable panels Blower service access Electrical filter access Compressor service...

Страница 6: ...12 9 12 9 16 4 16 4 CHARGE REFRIGERANT 22 lbs oz 4 10 4 13 4 6 4 12 6 0 7 12 FILTER FACE AREA Sq Ft Qty Size 2 14 1 14 x 22 COMPRESSOR HERMETIC QTY 1 Type Recip Recip Scroll Scroll Scroll Scroll 1 ECM...

Страница 7: ...96 40 036 208 230 1 60 187 253 15 4 88 1 2 4 3 24 8 30 30 0 96 40 042 208 230 1 60 187 253 21 1 115 1 2 6 8 34 4 45 45 0 96 40 048 208 230 1 60 187 253 20 5 115 1 2 6 8 33 6 45 45 0 96 40 060 208 230...

Страница 8: ...06 2 11 3 15 0 54 2 62 5 76 4 86 6 80 90 80 90 2NH04502006 2 15 0 20 0 72 2 83 3 98 6 112 7 100 125 100 125 2NH04502506 2 18 8 25 0 90 3 104 2 121 5 138 7 125 150 125 150 060 208 230 1 60 25 0 169 0 1...

Страница 9: ...d conditions would be inaccurate To ensure a dry coil the compressors should be deactivated while the test is being run 4 Knowing the pressure drop across a dry coil the actual CFM through the unit ca...

Страница 10: ...1 1 22 9 24 6 26 3 27 7 29 2 30 6 32 1 70 15 0 16 7 18 4 20 1 21 8 23 5 25 3 26 7 28 1 29 6 31 0 75 13 9 15 7 17 4 19 1 20 8 22 5 24 2 25 6 27 1 28 5 30 0 80 12 9 14 6 16 3 18 0 19 7 21 4 23 2 24 6 26...

Страница 11: ...100 5 0 5 9 6 8 9 3 11 8 14 2 16 7 105 7 0 9 3 11 7 14 0 110 6 9 9 1 11 3 115 6 5 8 6 TABLE 10 DAPM048 SUPERHEAT CHARGING TABLE OUTDOOR TEMPERATURE F SUPERHEAT AT COMPRESSOR SUCTION F AIRFLOW 400 CFM...

Страница 12: ...MAL EXPANSION VALVE FIGURE 5 DAPM060 SUCTION PRESSURE TEMPERATURE UTILIZES A THERMAL EXPANSION VALVE FIGURE 6 DAPM060 SUCTION PRESSURE TEMPERATURE UTILIZES A THERMAL EXPANSION VALVE 287 225 5 8 7 03 5...

Страница 13: ...H ZLWKRXW QRWLFH HUWLILHG GLPHQVLRQV ZLOO EH SURYLGHG XSRQ UHTXHVW 81 7 21 16 7 211 7 21 137 75 3 5 48 5 29 5 6 6833 5 23 1 1 6 5 7851 5 23 1 1 2035 6625 6 59 66 203 570 17 3 1 92 7 211 12 287 92 7 21...

Страница 14: ...is in the AUTO position the 24 volt G signal will be removed and after a 30 second delay the indoor blower motor will shut down HEATING WITH POWER TO UNIT AND THERMOSTAT IN HEATING MODE 1 If the fan...

Страница 15: ...R 1 1 SECOND DELAY ON FAN 10 SECOND DELAY OFF OFF HEATER BANK 3 HTR 4 HTR 5 INSTANT OFF HEATER BANK 2 HTR 2 HTR 3 SEC DELAY ON HEATER BANK 1 HTR 1 1 SECOND DELAY ON FAN 10 SECOND DELAY OFF TABLE 12 TH...

Страница 16: ...d to clean the coil be sure that the power to the unit is shut off prior to cleaning TROUBLESHOOTING Prior to any of the following maintenance procedures shut off all power to the unit to avoid person...

Страница 17: ...176169 BIM A 0206 Unitary Products Group 17 Notes for wiring diagrams on pages 18 thru 21 Legend for wiring diagrams on pages 18 thru 21 6 F 9 N O T U S E D 2 M 3 2 3 0 V C O IL...

Страница 18: ...176169 BIM A 0206 18 Unitary Products Group FIGURE 8 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPPLY DPM MODELS 15556BBSH0301 SEE DETAIL A...

Страница 19: ...176169 BIM A 0206 Unitary Products Group 19 FIGURE 9 TYPICAL WIRING DIAGRAM 208 230 3 60 POWER SUPPLY DPM MODELS...

Страница 20: ...176169 BIM A 0206 20 Unitary Products Group FIGURE 10 TYPICAL WIRING DIAGRAM 208 230 3 60 POWER SUPPLY DPM MODELS...

Страница 21: ...176169 BIM A 0206 Unitary Products Group 21 FIGURE 11 TYPICAL WIRING DIAGRAM 460 3 60 POWER SUPPLY DPM MODELS...

Страница 22: ...176169 BIM A 0206 22 Unitary Products Group...

Страница 23: ...176169 BIM A 0206 Unitary Products Group 23...

Страница 24: ...t to change without notice Printed in U S A 176169 BIM A 0206 Copyright 2006 by Unitary Products Group All rights reserved Supersedes 161697 BIM A 1005 Unitary 5005 Norman Products York OK Group Drive...

Отзывы: