Power exhaust is not available as a field installed option.

Unitary Products Group

11

530.22-N5W

TABLE 6 - SUPPLY AIR BLOWER PERFORMANCE (20 TON)

BLOWER

SPEED,

(RPM)

MOTOR

PULLEY
(TURNS

OPEN)*

CFM

6000

7000

8000

9000

9400

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

208 VOLT AND STANDARD DRIVE

870

6.0**

0.4

2.1

1.8

0.1

2.3

2.0

-

-

-

-

-

-

-

-

-

900

5.0

0.8

3.2

2.7

0.5

3.5

2.9

0.2

3.8

3.2

-

-

-

-

-

-

930

4.0

1.1

4.1

3.4

0.9

4.5

3.8

0.6

4.9

4.1

0.1

5.1

4.3

-

-

-

950

3.0

1.3

4.6

3.9

1.1

5.1

4.3

0.8

5.5

4.6

0.4

5.9

5.0

-

-

-

980

2.0

1.6

5.3

4.5

1.4

5.8

4.9

1.2

6.3

5.3

0.7

6.9

5.8

0.2

7.3

6.1

1015

1.0

1.9

5.9

5.0

1.7

6.5

5.5

1.5

7.0

5.9

1.0

7.7

6.5

0.6

8.2

6.9

208 VOLT AND HIGH SPEED DRIVE ACCESSORY

950

6.0

1.3

4.6

3.9

1.1

5.1

4.3

0.8

5.5

4.6

0.4

5.9

5.0

-

-

-

980

5.0

1.6

5.3

4.5

1.4

5.8

4.9

1.2

6.3

5.3

0.7

6.9

5.8

0.2

7.3

6.1

1010

4.0

1.8

5.8

4.9

1.7

6.3

5.3

1.5

6.9

5.8

1.0

7.5

6.3

0.5

7.9

6.7

1020

3.5

1.9

6.1

5.1

1.8

6.5

5.5

1.6

7.1

6.0

1.1

7.8

6.6

0.6

8.3

7.0

1035

3.0

2.0

6.2

5.2

1.9

6.8

5.7

1.7

7.4

6.2

1.2

8.1

6.8

0.7

8.6

7.3

1050

2.5

2.1

6.4

5.4

2.0

7.0

5.9

1.8

7.6

6.4

1.3

8.3

7.0

-

-

-

1075

2.0

2.3

6.6

5.5

2.1

7.2

6.0

1.9

7.8

6.6

1.5

8.6

7.2

-

-

-

1100

1.0

2.4

6.7

5.6

2.2

7.3

6.1

2.1

7.9

6.7

-

-

-

-

-

-

230/460/575 VOLT AND STANDARD DRIVE

870

6.0**

0.4

2.1

1.8

0.1

2.3

2.0

-

-

-

-

-

-

-

-

-

900

5.0

0.8

3.2

2.7

0.5

3.5

2.9

0.2

3.8

3.2

-

-

-

-

-

-

930

4.0

1.1

4.1

3.4

0.9

4.5

3.8

0.6

4.9

4.1

0.1

5.1

4.3

-

-

-

950

3.5

1.3

4.6

3.9

1.1

5.1

4.3

0.8

5.5

4.6

0.4

5.9

5.0

-

-

-

980

2.5

1.6

5.3

4.5

1.4

5.8

4.9

1.2

6.3

5.3

0.7

6.9

5.8

0.2

7.3

6.1

1015

1.5

1.9

5.9

5.0

1.7

6.5

5.5

1.5

7.0

5.9

1.0

7.7

6.5

0.6

8.2

6.9

1025

1.0

2.0

6.1

5.1

1.8

6.6

5.6

1.6

7.3

6.1

1.1

7.9

6.7

0.7

8.6

7.3

230/460/575 VOLT AND HIGH SPEED DRIVE ACCESSORY

950

6.0

1.3

4.6

3.9

1.1

5.1

4.3

0.8

5.5

4.6

0.4

5.9

5.0

-

-

-

980

5.0

1.6

5.3

4.5

1.4

5.8

4.9

1.2

6.3

5.3

0.7

6.9

5.8

0.2

7.3

6.1

1015

4.0

1.9

5.9

5.0

1.7

6.5

5.5

1.5

7.0

5.9

1.0

7.7

6.5

0.6

8.2

6.9

1035

3.5

2.0

6.2

5.2

1.9

6.8

5.7

1.7

7.4

6.2

1.2

8.1

6.8

0.7

8.6

7.3

1050

3.0

2.1

6.4

5.4

2.0

7.0

5.9

1.8

7.6

6.4

1.3

8.3

7.0

-

-

-

1080

2.0

2.3

6.6

5.5

2.1

7.2

6.0

1.9

7.8

6.6

1.5

8.6

7.2

-

-

-

1100

1.5

2.4

6.7

5.6

2.2

7.3

6.1

2.1

7.9

6.7

-

-

-

-

-

-

1120

1.0

2.5

6.8

5.7

2.3

7.4

6.2

2.2

8.1

6.8

-

-

-

-

-

-

NOTES: 1. Blower performance includes fixed outdoor air, two-inch T/A filters, a dry evaporator coil and no electric heat.

2. Refer to Page 12 for additional static resistances.

ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been de-

ducted

from the total static pressure of the blower.

* Do NOT close the pulley below 1 turn open.

** Factory setting.

240 MBH - BOTTOM DUCT CONNECTIONS

Содержание DAHC180

Страница 1: ...al for complete listing of replacement parts on this equipment All forms referenced in this instruction may be ordered from Standard Register 2101 West Tecumseh Road Norman Oklahoma 73069 Toll Free Fax 877 379 7920 Toll Free Phone 877 319 9675 APPROVALS Design certified by ETL CGA as follows 1 For use as a central cooling only unit with or without supple mental electric heat 2 For outdoor installa...

Страница 2: ...ly Air Blower Perf 20 Ton 11 7 Static Resistances 12 8 Power Exhaust Performance 12 9 Blower Motor and Drive Data 12 10 Electrical Data Basic Units 13 11 Electrical Data Units w Elec Heat 13 12 Heat Anticipator Setpoints 15 FIGURES No Description Page 1 Typical Rigging 3 2 Center of Gravity 3 3 Fixed Outdoor Air Damper 4 4 Recommended Drain Piping 4 5 Typical Field Wiring 5 6 Adjusting Enthalpy Se...

Страница 3: ...n the base rails Spreaders whose length exceeds the larger dimension across the unit MUST be used across the top of the unit Refer to Figure 1 Units may also be moved or lifted with a forklift from the front or rear only providing that an accessory skid is used LENGTH OF FORKS MUSTBE AMINIMUM OF 90 INCHES Refer to Table 4 for unit weights and to Figure 2 for approximate center of gravity CLEARANCE...

Страница 4: ...it to an open drain An alternate drain connection one inch NPT female coupling is provided inboard on the same centerline as the exterior location NOTE The condensate drain line MUST be trapped to pro vide proper drainage See Figure 4 COMPRESSORS Units are shipped with compressor mountings factory adjusted and ready for operation CAUTION Do Not loosen compressor mounting bolts FILTERS Two inch fil...

Страница 5: ......

Страница 6: ...halpy setpoint may now be set by selecting the desired setpoint shown in Figure 8 Adjust by carefully turning the setpoint adjusting screw to the A B C or D setting corresponding to the lettered curve 7 To check that the damper blades move smoothly without binding carefully turn the minimum position adjusting screw fully clockwise and then energize and de energize terminals R to G With terminals R...

Страница 7: ...Unitary Products Group 7 530 22 N5W FIG 6 ENTHALPY SETPOINT ADJUSTMENT ...

Страница 8: ...20 FACE AREA Sq Ft Each 36 0 43 3 COMPRESSOR Qty Per Unit 10 TON TANDEM 1 2 5 TON HERMETIC 1 AIR FILTERS QUANTITY PER UNIT 16 X 20 X 2 4 QUANTITY PER UNIT 16 X 25 X 2 4 QUANTITY PER UNIT 18 X 24 X 2 5 TOTAL FACE AREA sq ft 15 0 20 0 CHARGE REFRIGERANT 22 lbs oz SYSTEM NO 1 20 8 18 8 SYSTEM NO 2 10 8 18 8 This compressor will be energized first OPERATING WEIGHTS LBS 15 TON 20 TON Basic Unit Cooling...

Страница 9: ...of the unit RETURN AIR OUTDOOR AIR Economizer SUPPLY AIR CONDENSER AIR DETAIL X ACCESSORY SIDE SUPPLY AND RETURN AIR OPENINGS Front 36 Back 24 Less Economizer 49 With Economizer Left Side Filter Access 24 Less Economizer 54 With Economizer Right Side Cond Coil 36 Below Unit1 20 Above Unit2 72 With 36 Maximum Horizontal Overhang For Condenser Air Discharge Outlet NOTE Unit and ductwork are approved...

Страница 10: ... 4 6 1170 1 0 2 1 3 9 3 5 2 0 4 7 4 2 1 8 5 5 4 9 230 460 575 VOLT AND STANDARD DRIVE 870 6 0 1 0 2 4 2 2 0 8 3 1 2 8 0 6 3 5 3 1 0 2 4 1 3 7 915 5 0 1 1 2 6 2 4 0 9 3 3 3 0 0 7 3 7 3 3 0 3 4 4 3 9 0 2 4 5 4 0 965 4 0 1 2 2 9 2 6 1 0 3 6 3 2 0 8 4 0 3 6 0 5 4 7 4 2 0 4 5 0 4 4 980 3 5 1 3 3 0 2 7 1 1 3 7 3 3 0 9 4 1 3 7 0 6 4 8 4 3 0 5 5 1 4 6 1040 2 0 1 5 3 2 2 9 1 3 3 9 3 5 1 1 4 5 4 0 0 9 5 3 4...

Страница 11: ...T AND STANDARD DRIVE 870 6 0 0 4 2 1 1 8 0 1 2 3 2 0 900 5 0 0 8 3 2 2 7 0 5 3 5 2 9 0 2 3 8 3 2 930 4 0 1 1 4 1 3 4 0 9 4 5 3 8 0 6 4 9 4 1 0 1 5 1 4 3 950 3 5 1 3 4 6 3 9 1 1 5 1 4 3 0 8 5 5 4 6 0 4 5 9 5 0 980 2 5 1 6 5 3 4 5 1 4 5 8 4 9 1 2 6 3 5 3 0 7 6 9 5 8 0 2 7 3 6 1 1015 1 5 1 9 5 9 5 0 1 7 6 5 5 5 1 5 7 0 5 9 1 0 7 7 6 5 0 6 8 2 6 9 1025 1 0 2 0 6 1 5 1 1 8 6 6 5 6 1 6 7 3 6 1 1 1 7 9 6...

Страница 12: ...75 11 4 1 3 16 BX83 84 8 1 High Speed Access 950 1120 BK110 10 75 10 4 1 3 16 BX81 81 8 1 1 All motors have a nominal speed of 1800 RPM a 1 15 service factor and a solid base They can operate to the limit of their service factor because they are located in the moving air upstream of any heating device 2 Do NOT close this pulley below 1 turn open TABLE 9 BLOWER MOTOR AND DRIVE DATA EXTERNAL STATIC ...

Страница 13: ... 0 40 6 54 1 1 2 2 2 37 5 75 1 112 6 150 1 77 0 11 8 158 7 168 1 90 125 175 200 3 2 00 00 230 3 60 E018 E036 E054 E072 18 0 36 0 54 0 72 0 1 2 2 2 43 3 86 6 129 9 173 2 77 0 126 3 147 9 191 2 90 150 175 225 4 1 0 000 W180A 460 3 60 E018 E036 E054 E072 18 0 36 0 54 0 72 0 1 2 2 2 21 7 43 3 65 0 86 6 42 9 63 1 74 0 95 6 50 70 90 110 8 6 4 3 X180A 575 3 60 E018 E036 E054 E072 18 0 36 0 54 0 72 0 1 2 ...

Страница 14: ...t is set in the ON position ECONOMIZER WITH POWER EXHAUST This system operates as specified above with one addition The power exhaust motor is energized whenever the economizer is chosen by the enthalpy sensor for first stage cooling Y1 As always the R to G connection provides minimum position but does not provide power exhaust operation MOTORIZED OUTDOOR AIR DAMPERS This system operation is the s...

Страница 15: ...n the equipment installer To check the supply air CFM after the initial balancing has been completed 1 Remove the two 5 16 inch dot plugs from the blower motor and the filter access panels shown in Figure 9 2 Insert at least 8 inches of 1 4 inch tubing into each of these holes for sufficient penetration into the air flow on both sides of the indoor coil NOTE The tubes must be inserted and held in ...

Страница 16: ...n grease fitting Using a low pressure grease gun pump grease Chevron SRI 2 or equivalent into the bearing cavity until new grease shows at the open port Do not over lubricate Run the motor for ten minutes until excess grease is purged from the cavity Replace the plugs On 20 ton only units are supplied with blower shaft bearings that do not require maintenance but may be relubricated if desired Eve...

Отзывы: