TO TURN OFF GAS TO UNIT
1.
Set the thermostat to the OFF position.
2.
Turn off all electric power to the appliance if service is to
be performed.
3.
Remove the control access panel.
4.
Turn the gas valve switch to the OFF position. DO NOT
FORCE.
5.
Replace the control access panel.
POST-START CHECK LIST (GAS)
After the entire control circuit has been energized and the
heating section is operating, make the following checks:
1.
Check for gas leaks in the unit piping as well as the sup-
ply piping.
2.
Check for correct manifold gas pressures. See Checking
Gas Input.
3.
Check the supply gas pressure. It must be within the lim-
its shown on rating nameplate. Supply pressure should
be checked with all gas appliances in the building at full
fire. At no time should the standby gas line pressure
exceed 13.5", nor the operating pressure drop below
4.5" for natural gas units. If gas pressure is outside these
limits, contact the local gas utility for corrective action.
MANIFOLD GAS PRESSURE ADJUSTMENT
Small adjustments to the gas flow may be made by turning
the pressure regulator adjusting screw on the automatic gas
valve. Refer to Figure 10.
Adjust as follows:
1.
Remove the cap from the valve body. See Figure 11 for
location.
2.
To decrease the gas pressure, turn the adjusting screw
counterclockwise.
3.
To increase the gas pressure, turn the adjusting screw
clockwise.
NOTE:
The correct manifold pressure for natural gas fur-
naces is 3.5 IWG. The correct manifold pressure for
propane (LP) is 10.0 IWG.
BURNER INSTRUCTIONS
To check or change the burners, CLOSE THE MAIN MAN-
UAL SHUT-OFF VALVE AND SHUT OFF ALL POWER TO
THE UNIT.
1.
Remove the two (2) #8 screws holding each burner in
place.
2.
Remove the burner assembly from the manifold assem-
bly by moving the burner assembly forward, turn at an
angle and pull back.
3.
Burners are now accessible for service.
FIGURE 10 - GAS VALVE - FRONT
MANUALGAS
SWITCH
(SHOWNIN"OFF
POSITION)
CONTROL
ELECTRICAL
CONNECTION
IGNITORELECTRICAL
CONNECTION
MANIFOLD
PRESSURE
TAP
GROUND
TERMINAL
1/2-14NPT
(OUTLET)
PILOTGAS
CONNECTION
PILOT
ADJUSTMENT
FIGURE 11 - GAS VALVE - REAR
V E N T P R E S S U R E L I M I T E R
1 / 2 - 1 4 N P T
( I N L E T )
L I N E P R E S S U R E T A P
M A N I F O L D P R E S S U R E
A D J U S T M E N T
( R E M O V E C A P )
Содержание D YP024 Series
Страница 19: ...176230 BIM A 0206 Unitary Products Group 19 FIGURE 14 TYPICAL WIRING DIAGRAM DAYP 024 208 230 1 60 POWER SUPPLY...
Страница 21: ...176230 BIM A 0206 Unitary Products Group 21 FIGURE 16 TYPICAL WIRING DIAGRAM DAYP 060 208 230 1 60 POWER SUPPLY...
Страница 23: ...176230 BIM A 0206 Unitary Products Group 23 FIGURE 18 TYPICAL WIRING DIAGRAM DAYP 060 208 230 3 60 POWER SUPPLY...
Страница 25: ...176230 BIM A 0206 Unitary Products Group 25 FIGURE 20 TYPICAL WIRING DIAGRAM DAYP 060 460 3 60 POWER SUPPLY...
Страница 27: ...176230 BIM A 0206 Unitary Products Group 27...