GUIDE SPECIFICATIONS

GENERAL

Units shall be manufactured by Unitary Products Group in an 
ISO 9001 certified facility.

BCB Series units are convertible single package heat pumps. 
Although the units are primarily designed for curb mounting 
on a roof, they can also be slab-mounted at ground level or 
set on steel beams above a finished roof. Models are avail-
able with a wide variety of factory-mounted options and field-
installed accessories to make them suitable for almost every 
application. All units are self-contained and assembled on full 
perimeter base rails with holes in the four corners for over-
head rigging. Every unit is completely piped, wired, charged 
and tested at the factory to simplify the field installation and to 
provide years of dependable operation. All models (including 
those with an economizer) are suitable for either bottom or 
horizontal duct connections. Models with power exhaust are 
suitable for bottom duct connections only. For bottom duct, 
remove the sheet metal panels from the supply and return air 
openings through the base of the unit. For horizontal duct, 
remove the supply and return air panels on the rear of the 
unit. 

All non-Scroll compressors include crankcase heaters and all 
compressors have internal pressure relief. Every refrigerant 
circuit includes a liquid line filter-drier, a discharge line high 
pressure switch and a suction line with a freezestat and low 
pressure/loss of charge switch.The unit control circuit 
includes a 75 VA transformer, a 24-volt circuit breaker and a 
relay board with a compressor lockout circuit, a terminal strip 
for thermostat wiring, plus an additional set of pin connectors 
to simplify the interface of additional field controls. All units 
have long lasting powder paint cabinets with 1000 hour salt 
spray test approval under ASTMB117 procedures. All models 
are CSA listed. All models include a 1-year limited warranty 
on the complete unit. Compressors and electric heater ele-
ments carry a 5-year warranty. 

DESCRIPTION

Units shall be factory-assembled, single packaged heat 
pumps designed for outdoor mounted installation.

The units shall have minimum SEER ratings of 10.0. They 
shall have built-in field convertible duct connections for down 
discharge supply/return or horizontal discharge supply/return, 
and be available with factory installed options or field installed 
accessories. The units shall be factory wired, piped, charged 
with R-22 refrigerant and factory tested prior to shipment. All 
unit wiring shall be both numbered and color coded. All units 
the cooling performance shall be rated in accordance with 
DOE and ARI test procedures. Units shall be CSA listed, 
classified to ANSI Z21.47, UL 1995/CSA No. 236 standards.

UNIT CABINET

Unit cabinet shall be constructed of G90 galvanized steel,
with exterior surfaces coated with a non-chalking, powdered 
paint finish, certified at 1000 hours salt spray test per 

ASTMB117 standards. Indoor blower section shall be insu-
lated with a minimum 1/2” thick insulation, coated on the air-
side. Aluminum foil faced insulation shall be used in the 
furnace compartment and be fastened with ridged fasteners 
to prevent insulation from entering the air stream. Cabinet 
panels shall be “large” size, easily removable for servicing 
and maintenance. Full perimeter base rails shall be provided 
to assure reliable transit of equipment, overhead rigging and 
proper sealing on roof curb applications. Disposable 1" filters 
shall be furnished and be accessible through a removable 
access door, sealed airtight. Units filter track shall be 
designed to accommodate either 1” or 2” filters. Fan perfor-
mance measuring ports shall be provided on the outside of 
the cabinet to allow accurate air measurements of evaporator 
fan performance without removing panels or creating air by-
pass of the coils. Condensate pan shall be internally sloped 
and conform to ASHRAE 62-89 self-draining standards. Con-
densate connection shall be a minimum of 3/4” I.D. female 
and be a ridged mount connection.

INDOOR (EVAPORATOR) FAN ASSEMBLY

The indoor fan shall be direct drive, multi-speed, or a factory 
installed belt drive assembly that includes an adjustable pitch 
motor pulley. Job site selected (B.H.P.) brake horsepower 
shall not exceed the motors nameplate horsepower rating, 
plus the service factor. Units shall be designed not to operate 
above service factor. Fan wheel shall be double-inlet type 
with forward-curved blades, dynamically balanced to operate 
smoothly throughout the entire range of operation. Airflow 
design shall be constant air volume. Bearings shall be sealed 
and permanently lubricated for longer life and no mainte-
nance.

OUTDOOR (CONDENSER) FAN ASSEMBLY

The outdoor fan shall be of the direct-driven propeller type, 
discharge air vertically, have aluminum blades riveted to a 
corrosion resistant steel spider bracket and shall be dynami-
cally balanced for smooth operation. The outdoor fan motor 
shall be totally enclosed with permanently lubricated bear-
ings, internally protected against overload conditions and 
staged independently.

REFRIGERANT COMPONENTS

Compressor:

a.

Shall be  internally protected with internal high-pres-
sure relief and over temperature protection.

b.

Shall have internal spring isolation and sound muf-
fling to minimize vibration and noise, and be exter-
nally isolated on a dedicated, independent 
mounting.

Coils:

a.

Evaporator and condenser coils shall have alumi-
num plate fins mechanically bonded to seamless 
internally enhanced copper tubes with all joints 

Содержание BCB Series

Страница 1: ...b slab roof jack or frame All units include Powder Paint finish that meets ASTM B 117 1000 hour salt spray standards Permanently lubricated motors Bottom or side air discharge configuration capability...

Страница 2: ...LOWER DIAGRAM 33 17 HEAT PUMP POWER CIRCUIT 460 3 60 BELT DRIVE INDOOR BLOWER DIAGRAM 34 18 HEAT PUMP POWER CIRCUIT 575 3 60 DIRECT DRIVE INDOOR BLOWER DIAGRAM 35 19 HEAT PUMP POWER CIRCUIT 575 3 60 B...

Страница 3: ...ycle delay is incorporated into the standard controls Compressor reliability is further ensured by programmable minimum run times For testing the anti short cycle delay can be temporarily overridden w...

Страница 4: ...e a bank of nickel chromium elements mounted at the discharge of the supply air blower to provide a high velocity and uni form distribution of air across the heating elements Every element is fully pr...

Страница 5: ...alling ELECTRIC HEATERS wired for single point power supply These nickel chromium heater elements are pro vided with limit and automatic reset capability to prevent operation at excessive temperatures...

Страница 6: ...67 69 62 57 52 74 41 048 1 600 0 55 HIGH 0 80 85 85 75 68 70 63 58 53 75 42 060 2 000 0 45 HIGH 1 00 86 86 76 69 71 64 59 54 76 43 1 These values have been accessed using a model of sound propagation...

Страница 7: ...25 22 18 15 11 62 34 3 9 34 34 33 30 26 23 19 33 4 1 33 33 32 29 25 22 19 57 34 3 9 34 34 34 31 28 24 20 32 4 1 32 32 32 29 26 22 19 72 42 4 0 28 25 21 17 14 39 4 2 26 23 19 16 13 67 37 4 0 32 30 26...

Страница 8: ...2 4 6 42 42 41 37 32 27 22 39 4 8 39 39 37 34 29 24 19 57 42 4 5 42 42 42 37 33 27 23 38 4 7 38 38 38 33 30 25 20 72 49 4 8 35 31 26 22 46 5 1 34 29 25 20 67 44 4 6 40 40 35 31 26 22 39 4 9 36 36 32 2...

Страница 9: ...3 5 8 53 53 52 46 40 34 28 49 6 5 49 49 47 42 36 30 24 57 53 5 8 53 53 52 46 41 35 27 49 6 4 49 49 48 43 37 31 25 72 62 5 9 45 39 34 28 59 6 8 44 38 33 27 67 57 5 9 51 49 44 38 33 27 53 6 5 45 45 42 3...

Страница 10: ...24 9 32 1 39 4 47 6 54 5 KW 3 6 3 7 4 4 4 1 4 4 5 5 7 MBH 12 1 17 22 27 7 34 5 42 3 51 2 58 6 KW 3 3 3 4 3 5 3 6 3 6 3 8 4 4 5 MBH 11 6 16 3 21 2 26 6 33 2 40 7 49 2 56 3 KW 3 4 3 5 3 6 3 7 3 8 4 4 6...

Страница 11: ...680 916 730 RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 1103 1270 1900 1085 1210 1800 1064 1145 1102 1180 1700 1040 1075 1081 1115 1121 1140 1600 1020 1005 1060 1050 110...

Страница 12: ...680 916 730 RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 1103 1270 1900 1085 1210 1800 1064 1145 1102 1180 1700 1040 1075 1081 1115 1121 1140 1600 1020 1005 1060 1050 110...

Страница 13: ...740 926 780 965 830 RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2500 2400 1193 1665 2300 1170 1580 1202 1620 2200 1148 1480 1180 1530 2100 1121 1385 1155 1425 1190 1475 2000...

Страница 14: ...1900 970 LOW 2030 1070 1960 1020 1890 970 1810 920 3 1 4 1 0 70 AVAILABLE EXTERNAL STATIC PRESSURE IWG 2 0 90 0 0 1 0 8 0 3 1 4 1 5 1 AVAILABLE EXTERNAL STATIC PRESSURE IWG 2 5 1 0 60 0 20 0 30 0 40 0...

Страница 15: ...Y AIR BLOWER PERFORMANCE Tables 2 The pressure through the economizer is greater for 100 outdoor air than for 100 return air If the resistance of the return air duct system is less than 0 25 IWG the u...

Страница 16: ...8 8 2 20 8 25 2CE045110462 10 1 12 1 25 8 30 2CE045115462 13 6 16 4 31 0 35 2CE045120462 19 5 23 5 39 9 40 575 3 60 4 8 34 0 1 0 2 2 None 8 6 15 2CE04511058 10 6 10 2 21 3 25 2CE04511558 15 9 15 3 27...

Страница 17: ...CE04511025 10 6 25 5 64 9 70 2CE04511525 15 9 38 2 80 8 90 2CE04512025 21 2 51 0 96 8 100 2CE04513025 29 6 71 2 122 0 125 460 3 60 10 0 62 0 1 3 3 3 None 17 1 25 2CE045107462 6 8 8 2 27 3 35 2CE045110...

Страница 18: ...8 8 2 21 2 25 2CE045110462 10 1 12 1 26 2 30 2CE045115462 13 6 16 4 31 4 35 2CE045120462 19 5 23 5 40 3 45 575 3 60 4 8 34 0 1 0 2 0 None 8 8 15 2CE04511058 10 6 10 2 21 5 25 2CE04511558 15 9 15 3 27...

Страница 19: ...2CE04511025 10 6 25 5 63 5 70 2CE04511525 15 9 38 2 79 4 80 2CE04512025 21 2 51 0 95 4 100 2CE04513025 29 6 71 2 120 6 125 460 3 60 10 0 62 0 1 3 2 6 None 16 4 25 2CE045107462 6 8 8 2 26 6 30 2CE04511...

Страница 20: ...CONDENSER COILS Rows Deep 1 1 1 Fins Per Inch 20 20 20 Face Area Sq Ft 17 1 17 1 17 1 COMPRESSOR Qty Per Unit Reciprocating Type 1 1 1 AIR FILTERS Quantity Per Unit 15 X 20 X 1 or 2 2 2 2 Quantity Per...

Страница 21: ...TRANSFORMER TO REMOTE SENSOR 2TH040702224 IF USED NOT USED ADD JUMPER ADD JUMPER 4 4 3 2 1 ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 INCLUDES SUBBASE SECOND STAGE COOLING IS NOT REQUIRED ON UNITS...

Страница 22: ...257098 BTG A 0506 22 Unitary Products Group FIGURE 3 UNIT DIMENSIONS 3 5 TON HEAT PUMP FRONT VIEW FIGURE 4 UNIT WITH ECONOMIZER RAINHOOD DETAIL A...

Страница 23: ...257098 BTG A 0506 Unitary Products Group 23 FIGURE 5 UNIT WITH FIXED OUTDOOR AIR MOTORIZED DAMPER RAINHOOD DETAIL B FIGURE 6 UNIT DIMENSIONS REAR VIEW...

Страница 24: ...ring Side Bottom C 1 5 8 KO Gas Piping Front D 1 1 2 KO Gas Piping Bottom 1 Opening in the bottom to the unit can be located by the side in the insulation 2 Do not remove the 2 knockout ring TABLE 20...

Страница 25: ...257098 BTG A 0506 Unitary Products Group 25 FIGURE 8 TYPICAL APPLICATIONS...

Страница 26: ...D BCB036 628 139 137 174 177 BCB048 668 148 146 185 189 BCB060 693 154 151 192 196 TABLE 22 BCB 6 POINT LOADS WEIGHT DISTRIBUTION UNIT TOTAL A B C D E F BCB036 628 93 92 91 116 117 119 BCB048 668 99 9...

Страница 27: ...257098 BTG A 0506 Unitary Products Group 27 FIGURE 10 ROOF CURB DIMENSIONS...

Страница 28: ...257098 BTG A 0506 28 Unitary Products Group FIGURE 11 HEAT PUMP WITH ELECTRIC HEAT CONTROL CIRCUIT 208 230 3 60 DIAGRAM...

Страница 29: ...257098 BTG A 0506 Unitary Products Group 29 FIGURE 12 HEAT PUMP WITH ELECTRIC HEAT CONTROL CIRCUIT 460 3 60 DIAGRAM...

Страница 30: ...257098 BTG A 0506 30 Unitary Products Group FIGURE 13 HEAT PUMP WITH ELECTRIC HEAT CONTROL CIRCUIT 575 3 60 DIAGRAM...

Страница 31: ...257098 BTG A 0506 Unitary Products Group 31 FIGURE 14 HEAT PUMP POWER CIRCUIT 208 230 3 60 DIRECT DRIVE INDOOR BLOWER DIAGRAM...

Страница 32: ...257098 BTG A 0506 32 Unitary Products Group FIGURE 15 HEAT PUMP WITH ELECTRIC HEAT POWER CIRCUIT 208 230 3 60 BELT DRIVE INDOOR BLOWER DIAGRAM...

Страница 33: ...257098 BTG A 0506 Unitary Products Group 33 FIGURE 16 HEAT PUMP POWER CIRCUIT 460 3 60 DIRECT DRIVE INDOOR BLOWER DIAGRAM...

Страница 34: ...257098 BTG A 0506 34 Unitary Products Group FIGURE 17 HEAT PUMP POWER CIRCUIT 460 3 60 BELT DRIVE INDOOR BLOWER DIAGRAM...

Страница 35: ...257098 BTG A 0506 Unitary Products Group 35 FIGURE 18 HEAT PUMP POWER CIRCUIT 575 3 60 DIRECT DRIVE INDOOR BLOWER DIAGRAM...

Страница 36: ...257098 BTG A 0506 36 Unitary Products Group FIGURE 19 HEAT PUMP POWER CIRCUIT 575 3 60 BELT DRIVE INDOOR BLOWER DIAGRAM...

Страница 37: ...ures Units shall be CSA listed classified to ANSI Z21 47 UL 1995 CSA No 236 standards UNIT CABINET Unit cabinet shall be constructed of G90 galvanized steel with exterior surfaces coated with a non ch...

Страница 38: ...and above on 460 and 575 volt heaters The heating section shall have a primary limit control s and auto matic reset to prevent the heating element system from oper ating at an excessive temperature Th...

Страница 39: ...eration Whenever the indoor fan motor is energized the dampers open up to one of two pre selected positions regardless of the outdoor air enthalpy Dampers return to the fully closed position when the...

Страница 40: ...to change without notice Printed in U S A 257098 BTG A 0506 Copyright 2006 by Unitary Products Group All rights reserved Supersedes 036 21565 003 A 1005 Unitary 5005 Norman Products York OK Group Driv...

Отзывы: