Explanation of the Alarm Detection Function
37
Chapter
6
Alarm can be output as a contact signal that can be utilized for emergency stoppage of system and
so on, when voltage, current or electric power exceeds the set value.
Measurements in between seven seconds before and three seconds after the alarm is detected are
recorded in the main unit 10 times per second.
This can be used for examining the cause and mechanism of faults occurred.
A single item from voltage, current or electric power is settable for each of the two settings.
The order of priority is voltage > current > electric power.
For example, when UV interphase voltage and effective power are set, only the UV interphase
voltage is enabled and the effective power is canceled.
Same types may be selected multiply.
As for same types, the alarm is detected whenever any one of the selected items exceeds the alarm
detection level.
6-1.
Alarm detection item setting 1
Configure alarm detection item setting 1.
<<Setting value>>
0 0 0 0 0 0
6
Explanation of the Alarm
Detection Function
6HYHQVHFRQGVEHIRUH
7KUHHVHFRQGVDIWHU
7KUHVKROGYDOXHVDUHVHWIRU
YROWDJHRIDODUPGHWHFWLRQ
IXQFWLRQFXUUHQWDQGVRRQ
DQGDQDODUPLVGHWHFWHGLI
WKHVHWYDOXHVDUHH[FHHGHG
$ODUPUHFRUGHUIXQFWLRQ
VHFRQGV[ SRLQW
LVDXWRPDWLFDOO\UHFRUGHGD
VLQJOHZDYHIRUPLVUHFRUGHG
Invalid
0 fixed.
0 to 7
Turns UV interphase voltage (B0) VW interphase voltage (B1) WU interphase voltage (B2)
0/1
Turns average phase current (B0) ON and OFF.
0/1
Turns average interphase voltage (B0) ON and OFF.
0 to 7
Turns effective power (B0) / reactive power (B1) / apparent power (B2) ON and OFF.
0 to 7
Turns U phase current (B0) V phase current (B1) W phase current (B2) ON and OFF by BIT.
ON and OFF by BIT.