2.CONNECTION
5
2. CONNECTION
2-1. F159 Block Terminal
2-2. Load Cell Connection
Connect leads from the load cell to F159 terminal block.
+EXC
B1
+S
B2
-EXC
B3
-S
B4
RSV
B5
RSV
B6
RSV
B7
OUT1
B8
OUT1
B9
A1
SHIELD
A2
+SIG
A3
-SIG
A4
RSV
A5
RSV
A6
RSV
A7
RSV
A8
OUT2
A9
OUT2
Load cell signal
F159
6-wire connection
4-wire connection
+EXC
+EXC
+EXC
+S
+S
connected to +EXC
-EXC
-EXC
-EXC
-S
-S
connected to -EXC
+SIG
+SIG
+SIG
-SIG
-SIG
-SIG
SHIELD
SHIELD
SHIELD