TPCMQ48 SERIES
INSTALLATION & OPERATING MANUAL
Manual No. tpcmq48-4
tpcmq48-man-rev4-0116.indd
12.3
Module Evaluation Board
- A mating interface board which is available for simplifying
the testing of a TPCMQ48 module.
12.4
Output Voltage
- The output voltage is factory set to its nominal value to an accuracy of
±1%. The voltage can be adjusted to any value within the range given in the table below
using the remote adjust input.
Model
Adjustment Range
TPCMQ48-12/54
9.0-13.2V
TPCMQ48-24/29
18.0-26.4V
TPCMQ48-27/26
20.4-29.9V
TPCMQ48-48/21
36.0-52.8V
TPCMQ48-54/18
40.8-59.8V
12.5
Output Power & Current
- The following table shows the maximum output power and
current ratings for the various models:
Model
Output
Voltage
Maximum
Power
Maximum
Current
TPCMQ48-12/54
12.0VDC
650W
54.2A
TPCMQ48-24/29
24.0VDC
700W
29.2A
TPCMQ48-27/26
27.2VDC
25.7A
TPCMQ48-48/21
48.0VDC
1000W
20.8A
TPCMQ48-54/18
54.4VDC
18.4A
When the output voltage is adjusted below the nominal voltage shown in the table the
maximum current indicated will apply. Conversely, when the output voltage is adjusted
above the nominal voltage shown the maximum power indicated will apply.
The maximum output power may be drawn up to +50°C air inlet temperature. Above +50°C
the total output power must be derated by 2.5%/°C, up to an absolute maximum air inlet
temperature of +70°C. Note that dependent on actual airflow through the unit output power
may be further limited or a temperature alarm indicated at lower temperatures.