C O R P O R A T I O N
TPCMQ DC/DC CONVERTER SERIES
OPERATING MANUAL
18
16.0 DESCRIPTION OF RACK/SHELF CONTROL AND SUPERVISORY SIGNALS
SIGNAL
PIN
DESCRIPTION
Module Present - 1
Module Present - 2
Module Present - 3
20
21
22
A logic LO means the indicated module is present; an open
indicates the module is absent. This signal is referenced to
-Sense, Pin 23.
Remote Adjust - 1
Remote Adjust - 2
Remote Adjust - 3
24
12
25
These are analog voltage inputs to the designated convert-
er modules by which the output voltage is adjusted. A zero
to + 5V input represents approximately -25 to +10% output
change for a converter. This input should be driven from a
source impedance less than 100 ohms and is referenced to
-Sense, Pin 23.
-Sense
23