8
TMN/TMP SERIES
OPERATING MANUAL
GENERAL SPECIFICATIONS
Efficiency .................................................................. 85% at Full Load
Switching Frequency ................................................ 150kHz Nominal
Overtemperature Protection .................................... Power Shutdown
Isolation, class I
5
, min. ............................................ 3000VAC Input-Output
....................................................... 1500VAC Input-Ground
....................................................... 50VDC Output-Ground
Safety Standards ..................................................... EN60-950, UL1950, CSA22.2-950
ENVIRONMENTAL SPECIFICATIONS
Operating Temperature ........................................... 0
o
C to 70
o
C Ambient
Derating .................................................................... 2.5% /
o
C, 50
o
C to 70
o
C
Storage Temperature ............................................... -40
o
C to +85
o
C
Cooling ..................................................................... Integral Ball Bearing Fan
PHYSICAL SPECIFICATIONS
Case Material, Module ............................................. Aluminum
Rack Mount ..................................... Steel
Finish, Rack Mount .................................................. Powder Coat Gray
Dimensions, Inches (mm)
Hot-Swap Module .................................. 3.30 H x 4.90 W x 13.09 D
.......................................... (84 x 124 x 332)
3-Module Rack ....................................... 3.5 H x 17.20 W x 19.90D
............................................. (89 x 437 x 505)
NOTES:
1.
At remote sense point, over full line range and 0-100% load change.
2.
20MHz bandwidth. Measured with 0.1µF ceramic and 10µF tantalum capacitors in parallel
across the output.
3.
1000W output power at nominal AC line.
4.
<5% deviation recovering to within 1% for 50% load change.
5.
Using single-wire current share with remote sense connected.
6.
Input-output isolation figure is for isolation components only.
100% production Hipot tested.