Unipower SAGEON Site Monitor Скачать руководство пользователя страница 5

Sageon Site Monitor (SSM) Application Note 

AN103-4012-00, Issue 3 

 

 

4.0

 

SYSTEM CONFIGURATION 

The SSM is easily configured using the SageView program included with each Sageon

 DC Power Plant.  The 

Site Monitor configuration screen is pictured below and provides a simple, intuitive user interface.  
 

 

 

Each input has a user-defined label field (up to 8 characters) to describe its function.  If a label field is left blank, 
the corresponding input is treated as not used.  Analog input fields also include a two-character field for the 
description of the units of measure as well as high and low alarm thresholds.  Scaling factor for analog inputs 
are set-up for 0 volts (0% F.S.) to 4 volts (100% F.S.).  The type of digital input source (normally open or 
normally closed) is user definable by selecting the appropriate check box.  Each discrete output can be 
automatically generated based on any combination of discrete and analog inputs. 

 

5.0

 

ELECTRICAL SPECIFICATION 

Analog inputs 

Number of inputs: 

Input Range: 

 

0 to +4Vdc Full Scale, 
Over-voltage and reverse polarity protected. 

Configuration: 

 

Scaling factor, low and high alarm levels are user programmable. 

Electrical Isolation: 

Non-isolated. Each analog input source must be isolated. 

 

Digital inputs 

Number of inputs: 

12 

Source type: 

 

Voltage free (dry) contact closure 

Active state: 

 

User defined (active open or active closed) 

Electrical Isolation: 

Non-isolated. Each digital input source must be isolated. 

 

Digital outputs 

Number of outputs: 

Output type: 

 

Voltage free (dry) 1 Form C relay contacts 

Output rating: 

 

1A@30VDC 

 

General 

Power Source: 

 

Self powered from the Sageon Interface Board 

Plant Connection:16 conductor cable to the Sageon Interface Board 
Maximum Distance: 

30 feet (9.14 meters) 
 
 
 
 