SPECIFICATIONS 

 

Table 5 - Line Mode Specifications 

 

MODEL INVC5048H INVC5096H 

Input Voltage Waveform 

Sinusoidal (Utility or Generator) 

Nominal Input Voltage 

230Vac 

Low Line Disconnect 

170Vac (Normal) 

90Vac (Generator / Wide Range) 

Low Line Reconnect 

180Vac (Normal) 

100Vac (Generator / Wide Range) 

High Line Disconnect 

280Vac 

High Line Re-connect 

270Vac 

Max AC Input Voltage 

300Vac rms 

Nominal Input Frequency 

50Hz / 60Hz  (Auto-detect) 

Low Line Frequency Disconnect  

40±1Hz 

Low Line Frequency Reconnect 

42±1Hz 

High Line Frequency Disconnect  

65±1Hz 

High Line Frequency Reconnect 

63±1Hz 

Output Voltage Waveform 

Same as Input Waveform 

Output Short Circuit Protection 

Circuit Breaker 40A 

Efficiency (Line Mode) 

>95% 

Transfer Switch Rating 

40A 

Transfer Time 
(AC to DC)  

10ms (typical) 
20ms (typical) 

Transfer Time 
(DC to AC) 

10ms (typical) 
20ms (typical) 

Power Limiting 

Input Voltage

Max Output power  

5KVA/4.2KW

2.5KVA/2.1KW

90V

180V

 

 

Содержание INVC4850H

Страница 1: ...r corp com EUROPE ParklandBusinessCentre ChartwellRoad Lancing BN158UE ENGLAND Tel 44 0 1903768200 Fax 44 0 1903764540 telecom unipower europe com OPERATING MANUAL INVO Series 5KVA INVERTER CHARGER IN...

Страница 2: ...INVO SERIES INVERTER CHARGER INSTALLATION OPERATING MANUAL Manual No INVO 1 Page 2 08 11 invo man...

Страница 3: ...al Precautions 5 INSTALLATION 6 Unpacking and Inspection 6 Basic Configuration 6 Batteries 7 Battery Cable Size 7 DC Disconnect and Over Current Protection 8 Battery Cable Connection 8 AC Cable Size 9...

Страница 4: ...ce risk of injury charge only deep cycle lead acid type rechargeable batteries Other types of batteries may burst causing personal injury and damage 3 Do not expose the inverter charger to rain snow o...

Страница 5: ...Lug should be bonded to the grounding system at ONLY one in the system All installations should comply with all national and local codes and ordinances Personal Precautions 1 Someone should be within...

Страница 6: ...below are present Please call customer service if any items are missing The Inverter Charger 1 DC red cable 1 DC black cable 1 User s manual this document Basic Configuration The following illustrati...

Страница 7: ...be held responsible Batteries The INVO inverter charger supports either a 48 volt or a 96 volt battery bank depending on the model Please refer to figure 2 for wiring the battery correctly Before proc...

Страница 8: ...he inverter charger s battery terminal Tighten the M8 screw to 5 8 Nm Do not place anything between the flat part of the Backup terminal and the battery cable ring terminal or overheating may occur DO...

Страница 9: ...terminal block is used to hardwire the AC input AC output and ground The National Electrical Code requires that an external disconnect switch be used in the AC input wiring circuit The AC breakers in...

Страница 10: ...terminal marked AC Line output following the wiring guide inside the compartment Connect the AC neutral out to the AC neutral out terminal Torque the wires into the terminal block 5 Use the two M3 sc...

Страница 11: ...above 42V for the INV5048H and 82V for the INV5096H Configuration Switch On the right of panel are the 4 configuration switches which setup the inverter charger operation parameters See table 3 for d...

Страница 12: ...on the battery voltage level Charging Indicator When line mode and input within range the charging symbol will show up And battery capacity segment will roll flashing in turn basing on capacity Charge...

Страница 13: ...is cycle the batteries are charged at a constant current 2 Constant Voltage Stage During this cycle the batteries are held at a constant voltage 14 1V per 12V block for AGM GEL 14 6V per 12V block for...

Страница 14: ...nnect 280Vac High Line Re connect 270Vac Max AC Input Voltage 300Vac rms Nominal Input Frequency 50Hz 60Hz Auto detect Low Line Frequency Disconnect 40 1Hz Low Line Frequency Reconnect 42 1Hz High Lin...

Страница 15: ...put Short Circuit Protection Current limit Fault after 4 cycles max Bypass Breaker Size 40A Nominal DC Input Voltage 48V 96V Min DC start voltage 40V 80V Low DC Alarm 42 0 1 2Vdc 84 0 2 4Vdc Low DC Al...

Страница 16: ...0A setting 10A 95 175V gen wide only 20A 175 275V 20A setting 10A 175 275v 10A setting Battery initial voltage sps setup 35Vdc 70Vdc Charger Short Circuit Protection Inverter charger shuts down automa...

Страница 17: ...own Beep continuous Auto Mains is normal 1 Over Charge Protection Line DC Voltage High DC input Shut down Beep continuous Manual 1 Over Voltage Protection Standby DC Voltage High DC input Shut down Be...

Страница 18: ...rify that the load matches the capability specified 2 Output short circuit 2 Check wiring or remove abnormal load 3 Over temp 3 Remove any obstruction in front of airflow inlet 4 Over charger 4 Restar...

Отзывы: