Page 32
P O W E R I N G T E C H N O L O G Y
Document Number: MS0031-MAN rev. 7
guardian_access_ms31-man-rev7-0521.indd
ACX External Connection Board: Select this if the ACX internal communication board is
selected and a maximum of 4 alarm relay outputs are required. (Figure 4-12)
ACX Alarm Relay Board: Select this if the ACX internal communication board is selected
and 5 - 10 alarm relay outputs are required. (Figure 4-13)
Alarm connections are Form C relays and can be monitored either Normally Closed (NC) or
Normally Opened (NO). When the power is OFF, NC is closed and when the power is ON,
the NC is open.
NOTE
Relays K1 - K6 (Alarm 5 - Alarm 10) on the Alarm Relay Board are set to the
alarm position if communication with the controller (due to a malfunction or being pulled
out) is lost for more than 7 minutes. (This function is available only for Alarm Relay Board
firmware version 1.2 or later.)
NOTE
The alarm configuration will be dependent on your system configuration.
XC3
3
2
1
Alarm 1
6
5
4
Alarm 2
XC6
3
2
1
Alarm 3
6
5
4
Alarm 4
XC5
2
1
Multi purpose 7-12
Multi purpose 1-6
XC2
+5V
0V
TEMP1(BATT)
3
2
1
XC4
50
XC1
Digital In 2
+5V
Digital In 1
XC7
Digital out 2
+V
Digital out 1
XC8
+5V
0V
TEMP2(AMB)
6
5
4
4
3
6
5
8
7
10
9
12
11
GND
GND
Symmetry#1
Symmetry#2
Temperature
sensor
Red
Green
Blue
Red
Green
Blue
Red
Green
Blue
Temperature
sensor
Red
Green
Blue
Figure 4-11 ACX External Connection Board